This document provides equipment listings and load calculations to size an electrical generator. It lists 8 loads with their absorbed power, rated power, load factor, efficiency, power factor, and whether they are continuous, intermittent, or standby loads. It then calculates the maximum normal running load as 100% of continuous load + 50% of intermittent load + 10% of the standby or biggest individual load. It also calculates the peak load with a 10% growth factor and recommends a generator size that allows for 70% loading.

Uploaded by

pvpavan
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
320 views1 page

Load Flow Analysis

This document provides equipment listings and load calculations to size an electrical generator. It lists 8 loads with their absorbed power, rated power, load factor, efficiency, power factor, and whether they are continuous, intermittent, or standby loads. It then calculates the maximum normal running load as 100% of continuous load + 50% of intermittent load + 10% of the standby or biggest individual load. It also calculates the peak load with a 10% growth factor and recommends a generator size that allows for 70% loading.

Uploaded by

pvpavan
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 1

LOAD LISTING, CALCULATIONS & GENERATOR SIZING

Sr. Equipment Name


1
2
3
4
5
6
7
8

Equip ID No

Pump Water
Pump Water
Pump Water
Exhaust Fan
Exhaust Fan
Fire Water Pump
Fire Water Pump
Lighting Load

WP 1
WP2
WP3
FN1
FN2
FP1
FP2

Absorbed
Power

Rated
Power

11
11
11
3
3
18
18
15

15
15
15
4
4
22
22
20

Load
Factor
0.7
0.7
0.7
0.7
0.7
0.75
0.75
0.75

Eff
0.85
0.85
0.85
0.85
0.85
0.89
0.89
0.89

cos
0.75
0.75
0.75
0.75
0.75
0.8
0.8
0.8

MCC
Maiin
Main
Main
Main
Main
Emer
Emer
Emer

Nature
Continous
of Load* KW
KVAR
C
C
S
I
S
I
S
C

Sum
Maximum Load

100%

of continous load +

50%

of Intermittent load +

10%

12.94
12.94

Intermittent
KW

KVAR

Standby
KW

KVAR

11.41
11.41
3.53
20.22

16.85

12.64

42.74

35.47

23.75

12.94

11.41

3.53

3.11

20.22

15.17

36.70

29.69

3.11
15.17

18.28

of standby or biggest individual load (higher one)

KW
55
75

cos
0.7745
0.7814

Amp
102
138

Volts
400
400

Maximum of normal running load with 10% Growth Factor


Peak load with 10% Growth Factor

60.075 49.068 77.567 0.7745


82.322 65.753 105.36 0.7814

112
152

400
400

Reccemended Generator Size when

117.6 93.933 150.51 0.7814

217

400

Maximum of normal running load


Peak load

70%

loading

KVAR
45
60

KVA
71
96

Remarks