0% found this document useful (0 votes)
903 views9 pages

Static Pressure Calculator

The document provides instructions and reference tables for calculating static pressure in ductwork. It includes the following: 1) A step-by-step process for calculating static pressure that involves entering duct dimensions and airflow, then calculating friction and dynamic losses. 2) Reference tables that list common duct components and their dynamic loss coefficients, to allow calculating the dynamic loss component of static pressure. 3) Additional reference tables that define duct velocities based on common duct sizes and airflow volumes, to allow calculating friction loss. The document provides information and formulas needed to calculate the total static pressure of a duct system from its component losses.

Uploaded by

Tanveer Aziz
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
903 views9 pages

Static Pressure Calculator

The document provides instructions and reference tables for calculating static pressure in ductwork. It includes the following: 1) A step-by-step process for calculating static pressure that involves entering duct dimensions and airflow, then calculating friction and dynamic losses. 2) Reference tables that list common duct components and their dynamic loss coefficients, to allow calculating the dynamic loss component of static pressure. 3) Additional reference tables that define duct velocities based on common duct sizes and airflow volumes, to allow calculating friction loss. The document provides information and formulas needed to calculate the total static pressure of a duct system from its component losses.

Uploaded by

Tanveer Aziz
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 9

Static Pressure Calculator

L = CENTER DISTANCE INCHES DUCT DIA VELOCITY Q = Air Flow Rate, CFM D = DUCT DIA IN FEET A = AREA, Feet Squared V = AIR VELOCITY, Feet Per Minute VP = VELOCITY PRESSURE L = CENTER LINE DISTANCE, Feet C = DYNAMIC LOSS COEFFICIENT 34 18 1500 2650.725 1.5 1.76715 1500 0.1402741 2.8333333 1.25

1. Enter number for L in inches 2. Enter Duct Diameter 3. Enter Velocity 4. Enter C - dynamic loss coefficient 5. Then get SP for each piece of duct 6. Do this for each duct piece to get Total SP for system

DUCT STATIC PRESURE = FRICTION LOSS + DYNAMIC LOSS SPF = FRICTION LOSS SPD = DYNAMIC LOSS 0.0051668 0.1753426

SP = STATIC PRESSURE

0.18051

ystem

PART
Factory Installed Riser Field Installed Riser Straight Duct Adjustable Duct Adaptor (all sizes) 90 Elbow (8" diameter) 90 Elbow (10" diameter) 90 Elbow (12" diameter) 90 Elbow (14" diameter) 90 Elbow (16" diameter) 90 Elbow (18" diameter) 90 Elbow (20" diameter) 90 Elbow (24" diameter) 45 Elbow (8" diameter) 45 Elbow (10" diameter) 45 Elbow (12" diameter) 45 Elbow (14" diameter) 45 Elbow (16" diameter) 45 Elbow (18" diameter) 45 Elbow (20" diameter) 45 Elbow (24" diameter) Duct Tee (8" diameter) Duct Tee (10" diameter) Duct Tee (12" diameter) Duct Tee (14" diameter) Duct Tee (16" diameter) Duct Tee (18" diameter) Duct Tee (20" diameter) Duct Tee (24" diameter) Y Tee (12" diameter) Y Tee (14" diameter) Y Tee (18" diameter) Y Tee (20" diameter) Y Tee (24" diameter) Off Set Collar

L Center Distance in Inches


4 4 Depends on Length Depends on Length minus Minimum Overlap 13 15 16 17.5 18.7 21 22 23.5 26.5 8.8 9.5 10.2 10.9 11.6 12.3 13 14.4 15 17 19 21 23 25 27 31 28 30 33.5 35.5 54 4 when matched with horizontal run

8" Duct Diameter Duct Component


RISER/FRISER STRAIGHT/ADJ ADAPTOR (8 TO 12) 90 ELBOW 45 ELBOW DUCT TEE

Dynamic Loss Coefficient


0.017 See Design Guide 0.797 0.400 0.150 1.250

10" Duct Diameter Duct Component


RISER/FRISER STRAIGHT/ADJ ADAPTOR (10 TO 14) 90 ELBOW 45 ELBOW DUCT TEE

Dynamic Loss Coefficient


0.013 See Design Guide 0.470 0.420 0.150 1.250

12" Duct Diameter Duct Component


RISER/FRISER STRAIGHT/ADJ ADAPTOR (12 TO 18) 90 ELBOW 45 ELBOW DUCT TEE Y TEE

Dynamic Loss Coefficient


0.011 See Design Guide 0.797 0.440 0.150 1.250 0.600

14" Duct Diameter Duct Component


RISER/FRISER STRAIGHT/ADJ ADAPTOR (14 TO 20) 90 ELBOW 45 ELBOW DUCT TEE Y TEE

Dynamic Loss Coefficient


0.010 See Design Guide 0.522 0.460 0.150 1.250 0.600

16" Duct Diameter Duct Component


RISER/FRISER STRAIGHT/ADJ

Dynamic Loss Coefficient


0.008 See Design Guide

ADAPTOR (16 TO 24) 90 ELBOW 45 ELBOW DUCT TEE

0.797 0.480 0.150 1.250

18" Duct Diameter Duct Component


RISER/FRISER STRAIGHT/ADJ 90 ELBOW 45 ELBOW DUCT TEE Y TEE

Dynamic Loss Coefficient


0.006 See Design Guide 0.500 0.150 1.250 0.600

20" Duct Diameter Duct Component


RISER/FRISER STRAIGHT/ADJ 90 ELBOW 45 ELBOW DUCT TEE Y TEE

Dynamic Loss Coefficient


0.005 See Design Guide 0.520 0.150 1.250 0.600

24" Duct Diameter Duct Component


RISER/FRISER STRAIGHT/ADJ 90 ELBOW 45 ELBOW DUCT TEE Y TEE

Dynamic Loss Coefficient


0.004 See Design Guide 0.540 0.150 1.250 0.600

Straight and Adjustable Dynamic Loss Coefficient Table

nt Table

Duct Velocity (V) = CFM/Area (in ft sq) = FPM


Round Area 8" = 50.24 in sq or 0.348 ft sq 10" = 78.5 in sq or 0.545 ft sq 12" = 113.04 in sq or 0.79 ft sq 14" = 153.86 in sq or 1.07 ft sq 16" = 200.96 in sq or 1.40 ft sq 18" = 254.34 in sq or 1.77 ft sq 20" = 314.00 in sq or 2.18 ft sq 24" = 452.16 in sq or 3.14 ft sq Square Area 12" = 144 in sq or 1.00 ft sq 14" = 196 in sq or 1.36 ft sq 16" = 256 in sq or 1.78 ft sq 18" = 324 in sq or 2.25 ft sq 20" = 400 in sq or 2.78 ft sq 22" = 484 sq in or 3.36 ft sq 24" = 576 sq in or 2.00 ft sq