Control Valves Tuning PDF
Control Valves Tuning PDF
Page 1 of 13
INTEGRAL OR RESET (T1) Integral action repeats the proportional controllers initial corrective signal until there is no difference between the PV and Setpoint. Integral ( T1 ) is expressed in "Minutes per Repeat" DERIVATIVE (T2) Changes the output of a controller in proportion to the "RATE" or "SPEED" at which the controlled variable is moving towards or away from the setpoint. Derivative action is expressed in minutes. Represents the time that the proportional plus derivative will take to reach a certain level of output, in advance of the time proportional action alone would produce the same output. i.e: When derivative is applied to a two mode controller ( PI ), to make it a three mode controller ( PID ), it's action consists of decreasing the number of repeats per minute required to drive the error back to setpoint.
Berrys Commissioning Handbook
PRESSURE (Liquid)
P + I Controllers. Low gain, fast reset, high PB Derivative hurts. Linear valves for differential pressure measurement. Equal percentage valves for linear measurement. Valve is the major dynamic element. P + I controllers. Gain near 1, fast reset rate. Derivative of no value. Linear valve. Self acting or high gain proportional controllers. Reset seldom necessary. Derivative unnecessary.
Valve characteristic relatively unimportant
LEVEL
TEMPERATURE
COMPOSITION
Three response controllers. Settings vary. Slow compared to other pressure valves. processes. Equal percentage Linear, no noise. Single capacity Precise control: No dead time. High gain controllers. Linear. Averaging control: Infrequent noise. Low gain, specialized controllers. Valve characteristic unimportant. Multiple capacity system. Three response controllers. Dead time possible (especially in Settings vary but gain usually above 1. heat exchangers). Derivative of limited value if dead time is large. Non linear. No Noise. Equal percentage valves. Measurement dynamics are important. Dynamics vary. P + I Controller. Dead time usually present. Low gain, variable reset rate. Usually linear. Derivative sometimes useful. Sometimes noisy due to poor On line analyzers fast. often noisy, pH mixing. nonlinear. Sampling systems complicate both measurement and control. add dead time. Linear valves.
TUNING CONTROLLERS
Since there are a very large number of combinations of the two or sometimes three, "knobs" provided for controller tuning, many methods have been developed over the years to aid in their proper adjustment. A few require upsetting the process to some extent, often an unacceptable practice in real life. These notes are intended to provide a few simple rules to use in tuning controllers which will minimize upsets and still get the job done. THE CONTROLLER MUST BE ADJUSTED TO BALANCE THE PROCESS. If the process is fast to respond (i.e. a flow loop), then the controller must be tuned fast too. Fast or slow for a controller refers to integral (or reset). NOT PROPORTIONAL BAND (or gain). Do not confuse these actions or grief will be your constant companion during your controller tuning efforts. If the process is slow (i.e. temperature control of a tray part way up a distillation column), then the controller must be tuned slow TO MATCH THE PROCESS. If you do not have a feel for the process characteristics or cannot find someone to enlighten you, leave controller tuning to someone else who can get the needed information. GENERAL RULES FOR COMMON LOOPS FLOW Usually, at least half of the control loops in a plant are flow loops. Set integral (I) at 0.1 minutes. Adjust the proportional band so that the measurement is not too noisy, usually about 300% although an occasional poor meter run installation may require as much as 1000%. A loop where a valve positioner has been used will require a proportional band setting two to three times larger than for a loop without a positioner. Slow moving or sticky control valves may require 0.2 or 0.3 minutes but are rare exceptions. If these settings do not work, inspect the valve and orifice installation to find the, problem. Fix the problem. Do not adjust the controller to some ridiculous setting such as a 10 minute reset time. Use the controller in manual or a hand valve if you think a 10 minute reset time is necessary. IMPORTANT NOTE: No controller will work when the valve is almost closed or almost wide open. Don't attempt tuning under these conditions. Have the operator open or close a bypass (if one exists) or wait until process conditions change enough to get the valve back within its operating range (from 5 to 95% of travel as extreme limits with 10 to 90% as a safer range). Never use derivative action in a flow loop. LEVEL The next most common loop after flow is level. DO NOT EVER USE A SHORT INTEGRAL VALUE IN A LEVEL LOOP. If you do, you will find the loop will always cycle, often with a period (time from the peak of one cycle to the peak of the next) of 10 to 15 minutes. The shorter the integral time, the longer the period. Set the integral at 10 minutes. This will satisfy 80 to 90% of the level applications in a plant, if the vessel time constant (volume/flow) is 1 to 2 minutes, then a shorter integral time can be used but remember that a large value is safer. If the vessel is large and the controlling flow is a trickle, then a greater value of integral must be used.
DEFAULT CONTROLLER TUNING PARAMETERS For the start-up of any plant, there are default tuning parameters that can be entered into each controller. These are start-up values only, and each controller will still require additional tuning. This tuning may occur several times on individual controllers, depending on plant start-up conditions. In fact, it can be some time (the plant has to stabilize) before all controllers have their
Berrys Commissioning Handbook
CONTROLLER INPUT/OUTPUT INDICATION Output to valves viewed by the operator shall indicate close as 0% and open as 100%. When a control valve is tripped on abnormal condition (Low-low level, etc.), the PID controller shall be configured to switch to manual output mode and the controller output to the fail-safe condition value. In case of sensing element failure, a "Bad PV" alarm will be generated and if it is a control point, controller shall switch to manual output mode. Controller output to field devices shall be -6.9% to 106.9% to compensate for calibration offsets in the field device. Master controller output in cascade loops shall be 0% to 100%.
CONTROL LOOP SCAN RATES The control loops shall be configured to achieve the functionality and philosophy of the P&IDs. Following are the basic types of control loops: - Analog Indication Only Loop; - Single Control Loop; - Cascade Control Loop; - Complex Control Loop; - Discrete 1/0 Loops within APM (Advanced Process Manager), and - Discrete 1/0 Loops within LM.