Application Note CTAN #116
The Application Note is pertinent to the Unidrive Family
UniSoft and the Option Modules
Accessing Option Menus with UniSoft Off-Line When demonstrating UniSoft it is sometimes desirable to examine the graphic block diagram for the various SOMs ( Small Option Modules) however, UniSoft readily doesnt allow a SOM diagram to appear unless it is connected on-line with a Unidrive that has a particular SOM in it. Attempting to bring up an SOM block diagram will yield the message: No Option Module Fitted More importantly, it is desirable to be able to pre-configure a Unidrive using UniSoft while in the office and create a setup file without being connected to a drive. Your setup may be requiring a SOM but it not intuitively apparent how to achieve setting it up in the off-line state.
Hint:
The SOM block diagrams can be activated using the following procedure: 1) Go to the PARAMETER pull down menu and select DISPLAY BY MENU
2) Select MENU 16 from the pull down menu and this will make the SOM code number available
3) If you double-click on the Option module code line, a description of the option module codes will appear.
CTAN116.DOC v1.0
03/26/01
4) You would then change the code from 0 to 1-4 from the table above, this can be done from this description window.
CTAN116.DOC v1.0
03/26/01
5) After youve made your SOM selection, you can now go to the pull down menu and select MENU 16 and that block diagram will now be visible and will be able to be manipulated.
Menu 20 Application Parameter Access
For similar reasons mentioned above it may be necessary to pre-configure the MENU 20 parameters for a UD70 application program. UniSoft readily doesnt allow the LOM parameters to appear unless it is connected on-line with a Unidrive that has a LOM in it. Attempting to bring up Menu 20 will yield the message:
In a similar manner as outline above, Menu 20 parameters can be made visible to be viewed and manipulated.
CTAN116.DOC v1.0
03/26/01
1) Go to Menu 17 and double-click on parameter #17.01. Change the value of this parameter to 1. 2) You can now go to the pull down menu and select MENU 20 and those parameters will now be visible and will be able to be manipulated.
Questions ?? Ask the Author: Author: Ray McGranor (716)-774-0093 e-mail : [email protected]
CTAN116.DOC v1.0
03/26/01