MV Design Guide Standards
MV Design Guide Standards
Where can you order IEC publications? Central Offices of the International Electrotechnical Commission 1, rue de Varemb Geneva - Switzerland. The documentation department (Factory A2) at Merlin Gerin can provide you with information on the standards.
c International Electrotechnical Vocabulary c High voltage alternating current circuit breakers c Current transformers c Voltage transformers c Alternating current disconnectors and earthing disconnectors c High voltage switches c Metal-enclosed switchgear for alternating current at rated voltage of over 1 kV and less than or equal to 72.5 kV c High-voltage alternating current combined fuse-switches and combined fuse-circuit breakers c High-voltage alternating current contactors c Specifications common to highvoltage switchgear standards c Calculation rules in industrial installations c Derating
IEC 60 050
IEC 60 298
IEC 60 420
IEC 60 470
IEC 60 694
Schneider Electric
71
Standards
ANSI
50% with current derating imposes chopped waves for outdoor equipment 115% Uw/3 s 129% Uw/2 s 2.7 Isc
IEC
30% without derating
short-time withstand current peak value Transient Recovery voltage(1) electrical endurance mechanical endurance motor overvoltages
(1) the
around twice as severe 4 times K.S.Isc 1 500 to 10 000 according to Ua and Isc no text
ANSI peak voltage is 10% greater than the voltage defined by the IEC. The E2/t2 slope is 50% greater than the Uc/t3 slope. However, the largest part of the graph is the initial part where the SF6 reconstitutes itself. The two standards easily allow the SF6 to reconstitute itself.
Rated voltages
According to IEC
c Standardised values for Ur (kV): 3.6 - 7.2 - 12 - 17.5 - 24 - 36 kV
According to ANSI
c The ANSI standard defines a class and a voltage range factor K which defines a range of rated voltages at constant power. Standardised values for Ur (kV)
Indoor equipment class (kV) 4.16 7.2 13.8 38 15.5 25 38 Umax (kV) 4.76 8.25 15 38 Umin (kV) 3.85 6.6 11.5 23 K 1.24 1.25 1.3 1.65 1 1 1
Outdoor equipment
10
50 s Standardised wave 1.2/50 s
t (s)
72
Schneider Electric
Standards
According to ANSI
Upeak (%)
100 90 70 50 10
tc
N.B. c BIL: Basic Insulation Level The outdoor equipment is tested with chopped waves.
c The impulse withstand is equal to: 1.29 BIL for a duration of tc = 2 s 1.15 BIL for a duration tc = 3 s
According to ANSI
c Values of rated current: 1200 - 2000 - 3000 A
According to ANSI
c Values of short-circuit rated breaking capacity: v indoor equipment: 12.5 - 20 - 25 - 31.5 - 40 kA v outdoor equipment: Class (MVA)
250 350 500 750 1000 1500 2750
Schneider Electric
73
Standards
According to ANSI
c The peak value of short-time withstand current is equal to: v 2.7 K Isc at peak value v 1.6 K Isc at rms. value. (K : voltage factor)
According to ANSI
c The rated short-circuit duration is equal to 3 seconds.
Rated supply voltage for closing and opening devices and auxiliary circuits
According to IEC
c Supply voltage values for auxiliary circuits: v for direct current (dc): 24 - 48 - 60 - 110 or 125 - 220 or 250 volts v for alternating current (ac): 120 - 220 - 230 - 240 volts. c Operating voltages must fall within the following ranges: v Motor and closing release units: -15% to +10% of Ur in dc et ac v opening release units: -15% to +10% of Ur in ac; -30% to +10% of Ur in dc v undervoltage opening release units
the release unit gives the command and forbids closing the release unit must not have an action
0%
35 %
70 %
100 %
(at 85%, the release unit must enable the device to close)
According to ANSI
c Supply voltage values for auxiliary circuits: v for direct current (dc): 24 - 48 - 125 - 250 volts. v for alternating (ac): 120 - 240 volts
74
Schneider Electric
Standards
Rated frequency
According to IEC
c Rated frequency: 50 Hz.
According to ANSI
c Rated frequency: 60 Hz.
According to IEC
c Short-circuit breaking tests must meet the following 5 test sequences: Sequence n % Isym % aperiodic component
1 2 3 4 5* 10 20 60 100 100 20 20 20 20 30
Schneider Electric
75
Standards
According to ANSI
c The circuit breaker must be able to break: v the rated short circuit current at the rated maximum voltage v K times the rated short-circuit current (maxi symmetrical interrupting capability with K: voltage range factor) at the operating voltage (maximum voltage/K) v between the two currents obtained by the equation: maxi symetrical current rated maxi voltage = =K rated short-circuit current rated voltage We therefore have a constant breaking power (in MVA) over a given voltage range. Moreover, the asymmetrical current will be a function of the following table taking S = 1.1 for Merlin Gerin circuit breakers.
1.8 1.7 1.6 1.5 1.4 1.3 1.2 1.1 1 0 0 ratio S
Asymmetrical interrupting capability = S x symetrical interrupting capability. Both at specified operating voltage
2 0.033
3 0.050
4 0.067
cycles seconds
c Rated short-circuit breaking capacity (kA) Sequence n Example: c Isc = 40 kA c % asymmetry = 50% c Iasym = 1.1 40 = 44 kA 44 44 c Isym = = = 36 kA 1,22 1 + 2(50%)2 Sequence 6 will therefore be tested at 36 kA + 50% asymmetry, this being 44 kA of total current.
1 2 3 4 5 6 7 8 9/10 11 12 13/14
current broken
% aperiodic component
10 50 - 100 30 < 20 60 50 - 100 100 < 20 KI to V/K < 20 SI to V 50 - 100 KSI to V/K 50 - 100 electrical endurance reclosing cycle at ASI and AKSI C - 2 s - O at KI rated Isc duration = KI for 3 s single phase testing at KI and KSI (0.58 V)
Short-circuit breaking testing must comply with the 14 test sequences above, with:
I R : : symmetrical breaking capacity at maximum voltage reclosing cycle coefficient (Reclosing factor) voltage range factor:
K=
Vmax Vmin
asymmetrical factor:
76
Schneider Electric
Standards
3150
7.2
400 400
2500 2500
3150
12
400 400
3150 3150
17.5
400
1600
2500
3150
24
400
1600 1600
2500 2500
3150
36
2500 2500
3150
According to ANSI
Maximum rated voltage
Umax (kV) 4.76
8.25
600
15
15.5
600
25.8 38
Schneider Electric
77
Standards
Derating
According to IEC
c Refer to "Switchgear definition/Derating" chapter.
According to ANSI
c The ANSI standard C37 04 gives for altitudes greater than 1 000 metres: v a correction factor for the applicable voltage on the rated insulation level and on the rated maximum voltage, v a correction factor for the rated operating current. The table of correction factors according to altitude (Altitude Corrections Factors: ACF). Altitude (ft)
3 300 5 000 10 000
(m)
1 000 1 500 3 000
continous current
1.00 0.99 0.96
N.B.: "sealed system" type circuit breakers, it is not necessairy to apply the voltage ACF on the maximum rated voltage
Electrical endurance
Merlin Gerin circuit breakers can withstand Isc at least 15 times. IEC and ANSI standards impose values well below this because they take account of oil breaking circuit breakers. These values are not very high and should the customer request it, we must provide those for the device being considered.
According to IEC
c The electrical endurance is equal to 3 times Isc.
According to ANSI
c The electrical endurance is equal to 4 times K.S.Isc.
Isc S K : : : symmetrical breaking capacity at maximum voltage asymmetrical factor voltage range factor
Mechanical endurance
According to IEC
c Mechanical endurance is of 2 000 switching cycles.
According to ANSI
c Mechanical endurance is of between 1 500 and 10 000 switching cycles according to the voltage and the breaking capacity.
Construction
According to IEC
c The IEC does not impose any particular constraints, however, the manufacturer has responsibility of determining what is required in terms of materials (thicknesses, etc) to meet performance requirements in terms of strength.
According to ANSI
c ANSI imposes a thickness of 3 mm for sheet metal.
78
Schneider Electric
Standards
Temperature
Standards IEC 0C ambient instantaneous
minimal maximal maximum average daily value minimal maximal
ANSI
N.B.: For all equipment operating under conditions other than those described above, derating must be provided (see derating chapter).
Altitude
According to IEC
c The altitude must not exceed 1 000 metres, otherwise the equipment should be derated.
According to ANSI
c The altitude must not exceed 3 300 feet (1 000 metres), otherwise the equipment should be derated.
Humidity
According to IEC
Average relative humidity value over a period
24 hours 1 month
Indoor equipment
95 % 90 %
According to ANSI
c No specific constraints.
Schneider Electric
79