Plumbing Calculation.

This document contains calculations for the potable and non-potable water booster pump requirements for the Jeddah Governorate Building in Jeddah. For the potable water, the fixture unit count is 159, requiring a pump flow of 88 GPM. The potable pump head calculation is 31.5 meters or 45 PSI, so the pump to be provided is 100 GPM at 55 PSI head. For the non-potable water, the fixture unit count is 427, requiring a pump flow of 140 GPM. The non-potable pump head calculation is 42.5 meters or 60.34 PSI, so the pump to be provided is 160 GPM at 70 PSI head

Uploaded by

uddinnadeem
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (1 vote)
566 views2 pages

Plumbing Calculation.

This document contains calculations for the potable and non-potable water booster pump requirements for the Jeddah Governorate Building in Jeddah. For the potable water, the fixture unit count is 159, requiring a pump flow of 88 GPM. The potable pump head calculation is 31.5 meters or 45 PSI, so the pump to be provided is 100 GPM at 55 PSI head. For the non-potable water, the fixture unit count is 427, requiring a pump flow of 140 GPM. The non-potable pump head calculation is 42.5 meters or 60.34 PSI, so the pump to be provided is 160 GPM at 70 PSI head

Uploaded by

uddinnadeem
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 2

JEDDAH GOVERNORATE BUILDING , JEDDAH POTABLE WATER BOOSTER PUMP CALCULATIONS A. Item # I 1 2 3 4 5 6 II 1 2 3 4 5 6 Pump Flow Calculations:- (U.P.C.

TABLE 6-4) Qty Description (NOS.) BASEMENT FLOOR LAV (PUBLIC) 8 LAV (PRIVATE) 3 SHOWER TRAY 1 JANITOR SINK 2 KITCHEN SINK 4 HOSE BIB 2 GROUND FLOOR LAV (PUBLIC) 13 LAV (PRIVATE) 10 SHOWER TRAY 6 BIDET 1 JANITOR SINK 4 KITCHEN SINK 4

F. U.

Total F.U. 8 3 2 6 6 4 13 10 12 1 12 6

1 1 2 3 1.5 2 1 1 2 1 3 1.5

III 1 2 3 4 5 6 1 2 B. 1 2 3 4

TYPICAL FIRST & SECOND FLOORS LAV (PUBLIC) LAV (PRIVATE) SHOWER TRAY JANITOR SINK KITCHEN SINK HOSE BIB

24 1 4 1 4 2 8 3 8 1.5 2 2 TOTAL (F.U.)

24 4 8 24 12 4 159

AT 159 F.U. : (U.P.C. CHART A-2) 58 GPM IRRIGATION WATER REQUIREMENT: 30 GPM TOTAL: 88 GPM Potable Water Pump Head Calculations:Head Static Head (22 meters) 22 Mt. Friction Losses due to Pipes, Fittings & 4.5 " Valves Residual Pressure 7 " NPSH (Pumps Suction Head) -2 " = 31.5 Mt. Equivalent to: 45 PSI ACTUAL POTABLE BOOSTER PUMP TO BE PROVIDED:PUMP FLOW 100 GPM X 55 PSI HEAD

C. 1

159173311.xls.ms_office\CAL-2(hsn)

Page 1 of 2

7/21/2013(5:01 AM)

JEDDAH GOVERNORATE BUILDING , JEDDAH NON-POTABLE WATER BOOSTER PUMP CALCULATIONS A. Item # I 1 2 3 II 1 2 3 4 III 1 2 3 Pump Flow Calculations:- (U.P.C. TABLE 6-4) Qty Description (NOS.) BASEMENT FLOOR EWC (PUBLIC) 6 WC (PUBLIC) 1 WC (MANAGER & GUARD HOUSE) 3 GROUND FLOOR EWC (PUBLIC) WC (PUBLIC) WC (MANAGER ) WC (HANDICAPPED ) TYPICAL FIRST & SECOND FLOORS EWC (PUBLIC) WC (HANDICAPPED ) WC (MANAGER )

F. U.

Total F.U. 48 8 9

8 8 3

6 7 10 3

8 8 3 8

48 56 30 24

16 8 4

8 8 3

128 64 12

TOTAL (F.U.) AT 427 F.U. = 140 GPM B. 1 2 3 4 (U.P.C. CHART A-2) Non-Potable Water Pump Head Calculations:Head Static Head (22 meters) 22 Mt. Friction Losses due to Pipes, Fittings & 4.5 " Valves Residual Pressure 18 " NPSH (Pumps Suction Head) -2 " = 42.5 Mt. Equivalent to: 60.34 PSI ACTUAL NON-POTABLE BOOSTER PUMP TO BE PROVIDED:PUMP FLOW 160 GPM X 70 PSI HEAD

427

C. 1

159173311.xls.ms_office\CAL-1(hsn)

Page 2 of 2

7/21/2013(5:01 AM)