Rating of the Transformer in KVA Primary voltage in Volts Secondary Volatge in V % Impedance of the Transfromer Nos.

of Phases Full Load current on Secondary side in A Actual Impedance in Ohms of secondary wdgs. Short Circuit current on Secondary side in KA Alternately SC can be calculated with the help of % impedance and voltages as follows =kVA/(sqrt(3)*Sec.V%impedance)

SC at Panel end shall be low as this will have the Impedance of cables also Impedance of connecting medium No. of Runs Per Phase Length of cable in mtrs Impedance of cable in Ohm/kM Total Impedance per phase Total Impedance for overall circuit Total SC at Panels

50000 132000 11000 10.00% 3

kVA V V %

2624.32 A 0.419156 Ohms 26 kA

26 kA

1 10 0.159 0.00159 0.00477

nos mtrs ohm/km ohm/phase ohm

25.948 kA