Detailed Specification For The Design of Narrow Base Tower
Detailed Specification For The Design of Narrow Base Tower
Detailed Specification For The Design of Narrow Base Tower
Type of Tower Angle of Deviation Extensions Base Width Type of Power Conductor Type of Ground wire Wind Zone Reliability level 220 KV Double Circuit tower 15 to 30 Degree 3M, 6 M and 9 M 7.0M for 9M extension Twin moose ACSR 7/3.66 Galvanised steel 2 1
Conductor Details
Conductor type Overall Diameter Gross sectional area Unit weight Ultimate tensile strength Coefficient of thermal expansion Modulus of elasticity -
Ground wire
Conductor type Overall Diameter
Galvanised steel
10.98 mm
73.646 sq mm 575 KG/KM 6974 KGs 11.5 X106 /deg C 1927263 KG/sq cm -
Span Details
Normal span Wind span 335 M 325 M Weight span Max 600 500 Min -200 -200
The existing sag tension calculation of Moose conductor and earth wire may be adopted based on normal span
Moose Conductor
Sl no 1 2 3 4 5 Temperature 32 32 0 0 75 Wind factor 0 1 0 0.36 0 Vertical sag 8.565 4.959 7.27 6.46 10.18 Tension Kg 3305.17 5708.46 3893.67 4382.33 2780.87 Factor of safety 4.924 2.851 4.18 3.714 5.852
75
7.905
1030.57
6.767
Climatic Conditions
Everyday Temperature Minimum Temperature Maximum Temperature Conductor Maximum Temperature Ground wire 32 degree 0 degree 75 degree 53 degree
Maximum tensions
Maximum tensions are based up on following At 0 degree with 36 % full wind pressure or At 32 degree with full wind pressure whichever is more stringent
The height of Lowest cross arm may be fixed at 19.85 M from ground to suit the existing sag template for normal tower.
Base dimensions for 9M Extension Tower may be fixed as 7.0 M Length of Bottom cross arm dimension 5950 mm as per the clearance diagram may be reduced to the maximum possible.
The design of tower shall be as per IS 802 ( Part 1, 2,3,4 ) 1995