Protection Motor Tutorial
Protection Motor Tutorial
Arijit Banerjee, Arvind Tiwari- GE Global Research Jakov Vico, Craig Wester- GE Multilin
Presented at 2008 Texas A&M Protective Relaying Conference College Station, TX
33%
31%
21.00 32.00%
36%
Thermal Stress Causes Motor Failure Most of the motor failure contributors and failed motor
components are related to motor overheating. Thermal stress potentially can cause the failure of all the major motor parts: Stator, Rotor, Bearings, Shaft and Frame.
For F class insulation, stator temperature of 165C causes motor lifetime to decrease to 50%
50
100
150
200
250
300
TEMPERATURE (C)
Rotor Conductors Deforming or Melting (for rotor limited - thermal limit is defined by motor stall time)
6
Overload Protection - Thermal Model A motor can run overloaded without a fault in motor or supply
A primary motor protective element of the motor protection relay is the thermal overload element and this is accomplished through motor thermal image modeling. This model must account for thermal process in the motor while motor is starting, running at normal load, running overloaded and stopped. Algorithm of the thermal model integrates both stator and rotor heating into a single model. Main Factors and Elements Comprising the Thermal Model are:
Overload Pickup Level Overload Curve Running & Stopped Cooling Time Constants Hot/Cold Stall Time Ratio RTD & Unbalance Biasing Motor State Machine
8
Motor Starting:
Previous state is Stopped & Current > 0 threshold. Motor current must increase to the level higher than overload pickup within seconds otherwise motor algorithm will declare the Running state.
Motor Running:
Previous state is Starting or Overloading & Current drops below overload pickup level.
Motor Overloading:
Previous state is Running & Current raises above overload pickup level. Thermal Capacity Used (TCU)
9
A C B D
Cold Running Overload Hot Running Overload Cold Locked Rotor Curve Hot Locked Rotor Curve
11
Thermal Model Thermal Capacity Used Thermal Capacity Used (TCU) is a criterion selected in
thermal model to evaluate thermal condition of the motor. TCU is defined as percentage of motor thermal limit utilized during motor operation. A running motor will have some level of thermal capacity used due to Motor Losses. Thermal Trip when Thermal Capacity Used equals 100%
12
Overload Curve
Set the overload curve below cold thermal limit and above hot thermal limit If only hot curve is provided by mfgr, then must set below hot thermal limit
13
Thermal ModelHot/Cold Stall Time Typically motor manufacturer provides the values of the locked Ratio (HCR)
rotor thermal limits for 2 motor conditions:
COLD : motor @ ambient temperature HOT : motor @ rated temperature for specific class and service factor. NEMA standard temperature rises for motors up to 1500HP and
AMBIENT
When motor is running below overload pickup, the TCU will rise or fall to value based on average current and HCR. HCR is used to calculate level of TCU by relay, at which motor will settle for current below overload pickup.
14
CLASS A
CLASS B
CLASS F
CLASS H
15
16
17
Thermal Model Behavior - Long Starts Issue Duration of a high inertia load start is longer than the
allowed motor safe stall time.
For these starts, thermal model must account for the current change during acceleration and also use the acceleration thermal limits for TCU calculations. Motor thermal limit is growing along with motor rotation speed during acceleration. Starting current is proportional to system voltage during motor acceleration, thus voltage could be a good indication of the current level corresponding to the locked rotor conditions.
Voltage dependant dynamic thermal limit curve is employed to enhance the thermal model algorithm. Motor relay will shift acceleration thermal limit curve linearly and constantly based on measured line voltage during a motor start.
18
Thermal Model - Current Unbalance Bias Negative sequence currents (or unbalanced phase
currents) will cause additional rotor heating that will be accounted for in Thermal Model.
Positive Sequence
Blown fuses Loose connections Stator turn-to-turn faults System voltage distortion and unbalanc Faults
Negative Sequence
19
Thermal Model - Current Unbalance Bias Equivalent heating motor current is employed to bias
thermal model in response to current unbalance.
2 IEQ = IM (1+ K (I2 I1 )2)
Im - real motor current; K - unbalance bias factor; I1 & I2 positive and negative sequence components of motor current. K factor reflects the degree of extra heating caused by the negative sequence component of the motor current. IEEE guidelines for typical and conservative estimates of K. 2
K = 175 ILRC TYPICA L
2 CONSERVATIVE K = 230 ILRC
20
22
Overvoltage Protection
The overall result of an overvoltage condition is a decrease in load current and poor power factor. Although old motors had robust design, new motors are designed close to saturation point for better utilization of core materials and increasing the V/Hz ratio cause saturation of air gap flux leading to motor heating. The overvoltage element should be set to 110% of the motors nameplate unless otherwise started in the data sheets.
23
Undervoltage Protection
The overall result of an undervoltage condition is an increase in current and motor heating and a reduction in overall motor performance. The undervoltage protection element can be thought of as backup protection for the thermal overload element. In some cases, if an undervoltage condition exists it may be desirable to trip the motor faster than thermal overload element. The undervoltage trip should be set to 90% of nameplate unless otherwise stated on the motor data sheets. Motors that are connected to the same source/bus may experience a temporary undervoltage, when one of motors starts. To override this temporary voltage sags, a time delay setpoint should be set greater than the motor starting time.
24
Unbalance Protection
Indication of unbalance negative sequence current / voltage Unbalance causes motor stress and temperature rise Current unbalance in a motor is result of unequal line voltages
Unbalanced supply, blown fuse, single-phasing
25
To limit the level of the ground fault current connect an impedance between the supplies neutral and ground. This impedance can be in the form of a resistor or grounding transformer sized to ensure maximum ground fault current is
26
All phase conductors are passed through the window of the same CT referred to as the zero sequence CT Under normal circumstances, the three phase currents will sum to zero resulting in an output of zero from the Zero Sequence CTs secondary. If one of the motors phases were to shorted to ground, the sum of the phase currents would no longer equal zero causing a current to flow in the secondary of the zero sequence. This current would be detected by the motor relay as a ground fault.
27
For large cables that cannot be fit through the zero sequence CTs window, the residual ground fault configuration can be used. This configuration is inherently less sensitive than that of the zero sequence configuration owing to the fact that the CTs are not perfectly matched. During motor starting, the motors phase currents typically rise to magnitudes excess of 6 times motors full load current and are asymmetrical. The combination of non perfectly matched CTs and relative large phase current magnitudes produce a false residual current. This current will be misinterpreted by the motor relay as a ground fault
28
Differential Protection
Differential protection may be considered the first line of protection for internal phase-to-phase or phase-to-ground faults. In the event of such faults, the quick response of the differential element may limit the damage that may have otherwise occurred to the motor. Core balance method:
Two sets of CTs, one at the beginning of the motor feeder, and the other at the neutral point Alternatively, one set of three corebalance CTs can also be used The differential element subtracts the current coming out of each phase from the current going into each phase and compares the result or difference with the differential pickup level.
29
Differential Protection
Summation method with six CTs:
If six CTs are used in a summing configuration, during motor starting, the values from the two CTs on each phase may not be equal as the CTs are not perfectly identical and asymmetrical currents may cause the CTs on each phase to have different outputs. To prevent nuisance tripping in this configuration, the differential level may have to be set less sensitive, or the differential time delay may have to be extended to ride through the problem period during motor starting. The running differential delay can then be fine tuned to an application such that it responds very fast and is sensitive to low differential current levels.
30
Differential Protection
Biased differential protection six CTs:
Biased differential protection method allows for different ratios for system/line and the neutral CTs. This method has a dual slope characteristic. Main purpose of the percent-slope characteristic is to prevent a mis-operation caused by unbalances between CTs during external faults. CT unbalances arise as a result of CT accuracy errors or CT saturation. Characteristic allows for very sensitive settings when the fault current is low and less sensitive settings when the fault current is high and CT performance may produce incorrect operating signals.
31
33
Starts/Hour Time Between Starts (Jogging) Bearing RTD Protection Acceleration Trip
Set higher than the maximum starting time to avoid nuisance tripping when the voltage is lower or for varying loads during acceleration.
34
Conclusions
Induction & synchronous motors are valuable assets to todays industrial facilities. The temperature rise of motor dictates its life When applied, thermal protection can prevent loss of motor life Additional protection elements such as overvoltage, undervoltage, unbalance, ground fault, differential, short circuit and stator RTD supplement the thermal model protection and provide complete motor protection.
35