Insul Coord 800 KV

Download as pdf or txt
Download as pdf or txt
You are on page 1of 24

Insulation coordination for UHVDC 800 kV

Power Systems DC - 1

abb.com/hvdc

Presentation items
! ! ! ! !

Operating experience Principles Smoothing reactor Insulation levels for different components Staging

Power Systems DC - 2 -

Presentation items
! ! ! ! !

Operating experience Principles Smoothing reactor Insulation levels for different components Staging

Power Systems DC - 3 -

Insulation coordination. Experience from operation. " Creepage flashovers -- Accurate creepage distance -- Accurate insulator design " Flashover because of uneven wetting -- Attention to physical layout " Overvoltages -- Excellent experience, no flashovers (Overdesign) " Cost of withstand for Lightning Impulse and Switching Impulse is small (exception: Thyristor valve) at 500 kv rating (creepage was dimensioning) " At 800 kV the Lightning Impulse and Switching Impulse will influence size, weight and cost of equipment

Power Systems DC - 4 -

Presentation items
! ! ! ! !

Operating experience Principles Smoothing reactor Insulation levels for different components Staging

Power Systems DC - 5 -

Insulation coordination - principles


Limitation of switching surges is essential Highly efficient arresters Installation of additional arresters on 800 kV dc bus and converter bus between transformer and valve Arresters installed very close to object (no distance effects) Subdivision of smoothing reactor 50 % on 800 kV, 50 % on neutral bus Insulation margins
Lightning impulse Switching impulse Oil insulation 20 % 15 % Air insulation 20 % 15 % Single Valve 10 % 10 %

Power Systems DC - 6 -

Margin of insulation is sufficient standard levels not applicable

Presentation items
! ! ! ! !

Operating experience Principles Smoothing reactor Insulation levels for different components Staging

Power Systems DC - 7 -

Air insulated smoothing reactor


350 mH

U1 U1

175 mH

U2 U2
175 mH

U3 U3

Power Systems DC - 8 -

Air insulated smoothing reactor


350 mH

175 mH

175 mH

Power Systems DC - 9 -

Smoothing reactor is located on neutral bus at Skagerrak, CU and Inga-Shaba +/-500 kV project

Air core smoothing reactors in ABB projects


kV Rihand-Delhi HQ-NEH Sylmar Vizag UHVDC 500 500 500 BtB 800 A 1500 2250 3100 3900 3750 mH 180 2x150 2x150 2 x 30 4x90

Dimensions Sylmar UHVDC

Weight ton 43 40

Height m 4.0 4.0

Diameter m 4.2 4.0

Power Systems DC - 10 -

Platform for smoothing reactor and arrester

Power Systems DC - 11 -

Presentation items
! ! ! !

Operating experience Principles Smoothing reactor Insulation levels for different components from a study using typical data NB! Only the upper 12-pulse converter is shown Staging

Power Systems DC - 12 -

800 kV DC bus outside smoothing reactor


LIWL 1950 kV SIWL 1546 kV LIPL 1625 kV SIPL 1345 kV

Switching overvoltages By-pass blocking w/o by-pass pair (1345 kV) Ground fault on line (1040 kV) 1) Disconnection of last ac line in inverter (1216 kV) Lightning overvoltages Lightning surge (1625 kV) Shielding failure in dc switchyard OH line tower arcing horns 1) 1.7 p u at line midpoint
Two or three DC line arresters to cater for distance effects. All arresters are contributing to reduce switching surges

Power Systems DC - 13 -

800 kV bus in valve hall


LIWL 1800 kV SIWL 1518 kV CBH LIPL 1500 kV SIPL 1320 kV Arrester CBH may be necessary To be finally decided at detailed study Switching overvoltages AC bus switching overvoltages(1128 kV) Inverter blocked w/o by-pass pair(1096 kV) Disconnection of last ac line in inverter (1320 kV) Lightning overvoltages Lightning surge from line dc line Lightning surges from ac network

Power Systems DC - 14 -

Y/Y connected transformer

LIWL 1744 kV SIWL 1518 kV Switching overvoltages AC bus switching surges(1128 kV) Disconnection of last ac line in inverter (1312 kV) Inverter blocking w/o by-pass pair (1096 kV) Lightning overvoltages Lightning surge from ac network Lightning surge from dc line

LIPL 1453 kV SIPL 1320 kV

YG

V MH

Power Systems DC - 15 -

The arrester YG will be installed if necessary to reduce switching overvoltages. Otherwise arresters MH+V protect phase-to-ground insulation

Thyristor valve insulation

LIWL 425 kV SIPL 446 kV

LIPL 386 kV SIPL 405 kV Switching overvoltages AC network switching surge Earth fault between transformer and valve Lightning overvoltages Lightning stroke from ac yard Lightning stroke from dc yard

Power Systems DC - 16 -

Smoothing reactor on 800 kV pole bus


LIWL 2160 kV LIPL 1800 kV

Each arrester has LIPL 900 kV

Switching overvoltages NA Lightning overvoltages Ground fault beside reactor Lightning surge from dc line

Power Systems DC - 17 -

Smoothing reactor on neutral bus

Switching overvoltages NA Lightning overvoltages Ground fault beside reactor Lightning surge from dc line

Power Systems DC - 18 -

LIPL 450 kV SIPL 400 kV

LIWL 540 kV SIWL 460 kV

Neutral bus

Presentation items
! ! ! ! !

Operating experience Principles Smoothing reactor Insulation levels for different components Staging

Power Systems DC - 19 -

UHVDC, 2 x 12-pulse converters/pole

! ! !

2 x 12 pulse groups/pole Max power 6200 MW at 800 kV DC Transformer data (6200 MW)
! ! ! !

No 12W Weight LxWxH

24 units 310 MVA 310 tons 8 x 4 x 5 meter

Power Systems DC - 20 -

Installed at Itaipu, in operation for 20 years

2 x 12 pulse groups/pole, switching arrangements

Maximum flexibility & availability High speed by-pass switch Operational experience from Itaipu Operation at reduced voltage
! !

70 % 35 %

Power Systems DC - 21 -

UHVDC, stagewise extension


A 800 kV 800 kV 600 kV 600 kV B C 800 kV 600 kV

Power Systems DC - 22 -

Converter configurations, 6000 MW, +/-800 kV, 3750 A

irst stage

Second stage Connection Voltage kV 1x12pulse 1x12pulse 1x12pulse 1x6pulse 1x6pulse 800 800 800 800 800

Transformer MVA/MVA 1st / 2nd 300/300 375/225 450/150 450/300 300/300

Cost %

Connection Voltage kV 400 500 600 600 600

x12pulse x12pulse x12pulse

100 100 100 97 101

x12pulse

x6pulse

Power Systems DC - 23 -

You might also like