c-power-ACB (L&T)
c-power-ACB (L&T)
c-power-ACB (L&T)
About us
Larsen & Toubro infuses engineering with imagination. The Company offers a wide range of advanced solutions in the field of Engineering, Construction, Electrical & Automation, Machinery and Information Technology. L&T Switchgear, a part of the Electrical & Automation business, is India's largest manufacturer of low voltage switchgear, with the scale, sophistication and range to meet global benchmarks. With over five decades of experience in this field, the Company today enjoys a leadership position in the Indian market with a growing international presence. It offers a complete range of products including powergear, controlgear, industrial automation, building electricals & automation, reactive power management, energy meters, and protective relays. These products conform to Indian and International Standards.
Complete selectivity
Unique feature of lcu=lcs=lcw for 1 second across the entire range. This ensures complete selectivity for system with time based discrimination.
Optimal compactness
Designed to ensure l Low inherent temperature rise l Adequate interface clearances
Common door cutout for entire range Left aligned cutout for all ratings l Uniform height and depth for ACBs up to 4000 Amp
Safety
marked for C, S1 & H ranges Superior quality engineering grade plastics used for insulation purpose; conforms to Glow wire test (Ref: IEC 60695-2-1) l In-built mechanical anti-pumping to prevent auto-reclosing of ACB on persisting faults l In-built rating error preventor in drawout ACBs ensure correct rating of drawout portion in corresponding cradle l Safety shutters prevent accidental contact with live cradle terminals l Variety of Safety Interlocks l Easily removable arc chutes without use of any tool l Operating voltage ranges from 10% Un to 110% Un for shunt release ensures intentional tripping even at high voltage drops during short circuit Transparent safety shutter offers easy inspection of cradle contacts & reduces the maintenance time l
l l
Conformance to standards
IEC - 60947 (Part 1 & 2) IS/IEC - 60947 (Part 1 & 2) l IEC 60695 - 2 - 1 l BS EN 60947 - 2
l l
Range
Breaking capacities:
Icu = Ics = Icw Rated Current CN-CS : E 400A
50kA
630A
50kA
800A
50kA
1000A
50kA
1250A
50kA
1600A
50kA
2000A
50kA
2500A
3200A
4000A
5000A
6300A
Frame-1 CN-CS : S1
50kA 50kA 50kA 50kA 50kA 50kA 60kA 60kA
Frame-2
60kA 75kA 75kA 100kA 75kA 100kA 95kA 95kA
Frame-3
Frame-4
Rating (A) 1000 1250 1600 H E S1 C H C 2000 415 1000 3 3/4 50 55 40 55 40 50 50 105 143 105 73.5 12 8 105 55 55 50 121 84 12 50 75 65 75 65 75 75 65 165 143 60 60 60 60 50 132 65 50 65 50 65 65 50 50 50 50 415 1000 3/4 60 40 60 40 60 60 55 132 84 12 75 65 75 65 75 75 65 165 143 2500 E H 1600 415 1000 3 3/4 50 50 35 50 35 50 50 35 105 50 50 50 105 65 50 50 50 50 105 8 50 65 50 65 65 50 143 105 S1 S1 C H C 1250 415 1000 3 65 50 50 50 50 105 8 12 73.5 105 105 35 50 50 50 50 35 50 50 35 50 65 50 65 65 50 143 105 50 50 3/4 H E S1 C 2000 C E S1 1000 415 1000 3 3/4 50 50 35 50 35 50 50 35 105 73.5 12 50 50 50 105 65 50 50 50 50 105 8 50 65 50 65 65 50 143 105 800 415 1000 3 3/4 50 50 50 50 105 12 73.5 105 35 50 50 35 50 35 50 50 50 50 50 105 8 H E E S1 S1 630 415 1000 3 3/4 50 50 50 50 105 12 50 50 50 50 105 8 E 400 415 1000 3 50 50 50 50 105 8
400
630
800
2500 S1
3200 H0 3200 415 1000 3/4 60 60 60 60 132 75 65 75 65 75 75 70 165 143 12 100 85 100 85 100 100 85 220 187 H1
4000 H0 4000 415 1000 3/4 75 65 75 65 75 75 70 165 143 12 100 85 100 85 100 100 85 220 187 H
5000 6300 C C 5000 6300 415 415 1000 1000 3/4 95 95 95 95 209 12 3/4 95 95 95 95 209 12
Type Designation
In
U e*
Ui
No. of poles
Icu
380/415/500V
690V
Ics
380/415/500V
690V
0.5 sec
withstand capacity
Icw
**
1 sec
3 sec
Icm
380/415/500V
690V
Uimp
Uimp
Utilization category
Fixed
Draw out
Manual x x 20000 15000 6000 385 316 423.5 399 487 587 8000 15000 15000 20000 15000 6000 6000 8000 6000 8000 8000 8000 385 385 468 431 414 326 468 399 487 587 423.5 316 316 316 423.5 423.5 385 394 x P 20000 8000 P P P x
P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P x P P P P P x 20000 8000 394 326 414 431 468 399 487 587 6000 385 316 423.5 7000 7000 468 399 487 587
Electrical
x P P P 20000 7000 394 326 414 431 6000 385 316 423.5 7000 7000 468 399 487 587 7000 394 326 414 431 4500 385 316 423.5 -
P P P P P P P P P P P P P 20000 5000 468 399 487 587 5000 5000 394 482 628 431 468 555 701 587 20000 10000 10000 5000 5000 5000 5000 5000 5000 5000 5000 5000 5000 2500 2500 394 482 628 431 468 555 701 587 468 555 701 587
Electrical life = Mechanical life. However, arcing contacts need to be replaced depending upon wear. Please consult us.
Fixed H
3 Pole
4 Pole
Draw out H
3 Pole
4 Pole
* Please consult us for application at dc voltages & higher operational voltage upto 1000V ac ** Icw values are indicated based on thermal considerations. While selecting a breaker please ensure that Icw requirement for the application is not more than Ics / Icu at the point of installation.
Protection releases
Microprocessor-based, Communication-capable Release - SR71
Salient Features
True RMS sensing Offers comprehensive protection for overload, short circuit, instantaneous, earth fault and neutral overload l High resolution backlit LCD display l Intelligent Pre-trip alarm to prevent system shutdown l Password protected settings and commands l MODBUS RTU protocol with intrinsic RS 485 port l LED indication for POWER ON, different faults and Pre-trip alarm l 2 sets of storable protection settings Last 5 trips & 128 Event records with time & date stamping l l 3 programmable contacts-1 for micro controller failure, 2 for basic fault annunciation 4 relay contacts for indication of exceeding maximum demand, Pre-trip l alarm and control on breaker (closing and opening) l Rating-plug for precise protection at lower load currents l Auto-doubling features to prevent nuisance tripping l Selectable I2t based current for short-time and earth fault zones l Thermal reflectivity enables faster tripping on recurrent overloads Inbuilt Zone Selective Interlocking l Provision for Self-diagnostic test l Conformance to EMI/EMC standards l
l l
Parameter Overload (Phase) Current Settings (A), Ir = In x .... Time Delay, Tr (sec) at 6 x Ir Pre-trip Alarm Settings Thermal Reflectivity Function Neutral Fault Short Circuit Current Settings (A), In = Irx .... Time Delay (sec) Current Settings (A), Isd = In x ....
2 2
Screen Abbreviation PICKUP TMS-tr PREALAR THM-MEM FUNC PICKUP DELAY PICKUP l t ON DELAY PREALAR lt COLDPIC CP_DLY FUNC PICKUP FUNC PICKUP DELAY PREALAR l2t COLDPIC
2
Details 0.4 to 1.0 In in steps of 0.05 In 0.5-1-2-4-6-12-18-24-30 0.5 to 0.95 Ir in steps of 0.05 Ir ON / OFF Enable / Disable 0.5-1.0 Same as 'Overload (Phase)' 2 to 10 In in steps of 0.5 In 20-100-200-300-400 20-100-200-300-400 0.5 to 0.95 Is in steps of 0.05 Is ON / OFF Enable / Disable 0.1 to 10 sec in steps of 0.1 sec Enable / Disable 2 to 16 In in steps of 0.1 In Enable / Disable 0.1 to 0.6 in steps of 0.05 In for l t ON 0.1 to 0.6 in steps of 0.01 In for l2t OFF 100 to 400 msecs in steps of 100 msec for l t ON 0.1 to 5 sec in steps of 100 msec for l t OFF
2 2 2
Factory Settings 1.0 In 30 sec 0.95 Ir OFF 1.0 Ir 30 sec 10 In 400 msec 400 msec 0.95 Is Disable 0.1 sec Enable 16 In Enable 0.6 In 3 sec 0.95 Ig OFF Disable
Time Delay, tsd (msec) at 10 x In l t OFF DELAY Pre-trip Alarm Settings lt Cold-load Pickup Cold-load Pickup Delay Instantaneous Function Current Settings (A), Ii = In x .... Earth Fault Function Current Settings (A), Ig = In x .... Time Delay (sec), tg Pre-trip Alarm Settings l2 t Cold-load Pickup
2
Note: Both Protection Groups 1 & 2 carry the same factory settings.
Additional Protections
Parameter Under Current Function Current Setting (A) x In Time Delay (secs) Trip / Alarm Current Unbalance Function Current Setting (A) x In Time Delay (secs) Over Voltage# Function Voltage Setting (V) Vs = Vn x .. Time Delay (secs) Reset Voltage Trip / Alarm Under Voltage# Function Voltage Setting (V) Vn x .. Time Delay (secs) Reset Voltage Trip / Alarm Under Frequency# Function Frequency Setting (Hz) Time Delay (secs) Drop Off Frequency Trip / Alarm Over Frequency# Function Frequency Setting (Hz) Time Delay (secs) Drop Off Frequency Trip / Alarm Reverse Power# Function Settings (kW) Time Delay (secs) Trip Alarm Phase Sequence# Function Settings Time Delay (secs) Trip / Alarm Breaker Failure Function Time Delay (secs) Maximum Demand Exceed Function Settings (kW) Step i -Discrimination Screen Abbreviation FUNC PICKUP DELAY MODE FUNC PICKUP DELAY FUNC PICKUP DELAY RSTSET MODE FUNC PICKUP DELAY RSTSET MODE FUNC PICKUP DELAY DRPOFF MODE FUNC PICKUP DELAY DRPOFF MODE FUNC PICKUP DELAY MODE FUNC PICKUP DELAY MODE FUNC DELAY FUNC PICKUP DELAY i -Discrimination Details Enable / Disable 15% to 80% in steps of 5% In 1 to 255 in steps of 1 second Either / Both Enable / Disable 10% to 95% in steps of 5% In 1 to 10 in steps of 5 secs Enable / Disable 105% to 150% in steps of 5% Vn 0.1 to 100 in steps of 0.1 secs 85% to 98% in steps of 1% Vs Either / Both Enable / Disable 45% to 65% in steps of 5% Vn 0.1 to 5 in steps of 0.1 secs 102% to 115% in steps of 1% Vs Either / Both Enable / Disable 45 to 50Hz for 50Hz in steps of 0.01Hz 57 to 60Hz for 60Hz in steps of 0.01Hz 0.1 to 100 secs in steps of 0.1 Second 0.02 to 0.10Hz in steps of 0.1Hz Either / Both Enable / Disable 50 to 55Hz for 50Hz in steps of 0.01Hz 60 to 62Hz for 60Hz in steps of 0.01Hz o.1 to 100 secs in steps of 0.1 second 0.02 to 0.10Hz in steps of 0.1Hz Either / Both Enable / Disable 0.02 to 0.4 in steps of 0.01 Pn 1 to 100 in steps of 0.1 secs Either / Both Enable / Disable 123 - 132 0 to 5 in steps of 0.5 secs Either / Both Enable / Disable 0.05 to 2 secs in steps of 0.01 secs Enable / Disable 40 kW - 1600 kW 10 kW - 1000 kW Enable / Disable Factory Settings Disable 0.8 In 1 second Alarm Disable 0.2 In 2.0 secs Disable 1.2 Vn 5.0 secs 0.95 Vs Alarm Disable 0.6 Vn 1 second 1.02 Vs Alarm Disable 48.0Hz 59.0Hz 0.2 secs 0.1Hz Alarm Disable 52.0Hz 61.0Hz 0.2 secs 0.1Hz Alarm Disable 0.2 Pn 2.0 secs Alarm Disable 123 2 secs Alarm Disable 1.0 second Disable 100 kW 10 kW Disable # Requires SR71-PM module
Metering
Parameter Current Screen Abbreviation I Imax %Load Voltage# V Vph-Vph Frequency# Power Factor# Power# F PF kW kVAr kVA kW Energy# kWh kVArh kVAh Harmonic-Current I1HAR I2HAR I3HAR Harmonic-Voltage# V1HAR V2HAR V3HAR Display # Requires SR71-PM module Details Phase, Earth and Neutral Maximum running Current per Phase Percent Loading Phase-Neutral Phase-Phase System Frequency System Power Factor Active Power per Phase and Total (kW) Reactive Power per Phase and Total (kVAr) Apparent Power per Phase and Total (kVA) Maximum Demand (kW) Total Active Energy (kWh) Total Reactive Energy (kVArh) Total Apparent Energy (kVAh) R-Phase Current Harmonics Y-Phase Current Harmonics B-Phase Current Harmonics R-Phase Voltage Harmonics Y-Phase Voltage Harmonics B-Phase Voltage Harmonics High Resolution Backlit LCD
Additional Features
Parameter LED Indications Screen Abbreviation Auxiliary Power ON Overload Short Circuit Instantaneous Earth Fault Neutral Fault Trip Alarm Auxiliary Supply Digital Inputs Output Relays Rating Plug Communication Maintenance Indication Event Records (128) Trip Records Testing Supplementary Modules Self-Diagnostic Test Relay Module Power Supply Module Communication Module Comunication Module(SR71-COM) Power Supply Module(UN-PS) Power Metering Module(SR71-PM) Relay Module(SR71-REL) No. of Storable Settings In Multiplier Protocol Link used Details P P P P P P P P 24V DC 4 Nos. 3 Internal + 4 External Relays 240V AC / 5A, 30V DC / 5A (resistive load) 630-800-1000-1250-2000-3200-5000 MODBUS RTU RS 485 I2t based Pickup, Alarm, Trip, Date, Time and Cause of Event Last 5 records with date and time stamping, voltage and current readings in all phases P 4 Relay Outputs 24V DC Output MODBUS RTU MODBUS RTU using RS485 Input:26V to 60V DC, 90 to 300V AC/DC Output:24V DC 240V AC, 415V AC 4 Relay Outputs (Breaker OPEN, Breaker CLOSE, Pre Trip alarm and MD Exceed) 2
Protection releases
Microprocessor Based Release - SR21i
Salient Features
Self-powered & true RMS sensing Inbuilt Zone Selective Interlocking (ZSI) l Provision for Self-diagnostic test(without tripping the breaker) l Switchable thermal memory takes care of residual heat in case of repetitive overloads l Multi-state LED to indicate - Power ON condition - Test mode l Individual fault annunciation through LEDs l Provision for AN1 module for remote fault indication through LEDs with changeover contact for each kind of fault l Direct tripping of breaker-reliable tripping with minimum time delay l Test kit available for testing the release (SRT-2) l Realistic hot and cold curves which take into account integrated heating effect l Conformance to EMI/EMC standards
l l
Type of Protection
Setting Range Pick-up Current Ir - 0.5 to 1.0 times In Steps : 0.50, 0.60, 0.65, 0.70, 0.75, 0.80, 0.85, 0.9, 0.95, 1.00 2 to 10 times In Steps : 2, 3, 4, 5, 6, 7, 8, 9, 10 2 to 16 times In Steps : 2, 3, 4, 6, 8, 10, 12, 14, 16, OFF 0.2 to 0.6 times In Steps : 0.2, 0.3, 0.4, 0.5, 0.6 Time Delay 0.2 to 30 sec. at 6 times Ir Steps : 0.2, 0.5, 1, 1.5, 2, 3.5, 6, 12, 17, 30 Sec 20 ms to 600 ms Steps : 20, 60, 100, 160, 200, 260, 300, 400, 500, 600 ms -
Long Time
Short Time
Instantaneous
Ground Fault*
Test-kit SRT-2
Salient Features
l l l
Test-Kit for SR18/SR18G/SR21i Releases Operates from 230V AC supply & generates single-phase voltage test signals
Tests the release for - Phase fault i.e. for long time, short time and instantaneous protection - Ground fault protection
Test current multiples - For phase faults: 2.5In, 4.5In, 6.5In, 9.5In, 11In, 13In - For ground fault: 0.25In, 0.35In, 0.45In, 0.55In l Five 7-segments LED display indicates the trip time (two places after decimal)
l
Protection releases
Microprocessor Based Release - SR18 & SR18G
Salient Features
Self-powered & true RMS sensing Comprehensive protection - SR18; Long Time and Short Time - SR18G; Long Time, Short Time and Ground fault protection l True Hot & Cold characteristics & switchable thermal memory l Multi-state LED to indicate - Power ON condition - Test mode l Individual fault annunciation through LEDs l AN1 module for remote fault indication through LEDs with changeover contact for each kind of fault l Provision for Self-diagnostic test(without tripping the breaker) l Test kit (SRT-2) available for testing the releases l Conformance to EMI/EMC standards
l l
Type of Protection
Setting Range Pick-up Current Ir - 0.5 to 1.0 times In Steps : 0.50, 0.60, 0.65, 0.70, 0.75, 0.80, 0.85, 0.9, 0.95, 1.00 2 to 10 times In Steps : 2, 3, 4, 5, 6, 7, 8, 9, 10 6 & 12 In 0.2 to 0.6 times In Steps : 0.2, 0.3, 0.4, 0.5, 0.6 Time Delay 2.5 sec at 6 times Ir
Long Time
Short Time
20 to 600 ms Steps: 20, 60, 100, 160, 200, 260, 300, 400, 500, 600 ms 100 to 400 ms Steps : 100, 200, 300, 400 ms & OFF
Instantaneous
Ground Fault*
* Available in SR18G release only In 3 phase, 4 wire system, Neutral CT is required for ground fault protection.
Protection
Overload Protection l Unique individual phase O/L setting adjustment helps to avoid the nuisance tripping of ACBs in unbalance load condition(due to single phase loads) on distribution transformer. Long time pick-up range: 0.75 to 1 times In Short Circuit Protection l Two taps on CTs (working as rating plug) help in selecting operating threshold. Short-time pick-up range: 5.5 to 7.5 times In with minimum impulsion time of 25ms to prevent nuisance tripping due to transients Ground Fault Protection l Offered with auxiliary earth fault release module. Ground-fault pick-up range: 0.2 to 0.5 times In
10
Protection Characteristic
Overload Curve (SR71)
10,000
1000
100
1 2 sec Tolerance: Trip Time: 20% 10,000 1 sec 0.5 sec 0.01 1.5 2 3 4 5 6 9 1000 Current Multiples ( x In)
0.6
1.0
1.5 2.0
100
3.0
10
9.0 10.0
0.1
0.1
0.02
11
Protection Characteristic
Short Circuit - I t OFF (SR71)
10,000 2
0.6
1000
1.0
1.5
2.0
100
3.0 4.0
6.0 8.0
10
9.0
10.0
0.4
0.3 0.2
0.1
0.1
Instantaneous (SR71)
10.000
0.01 0.05
0.1
10
50 1000
100
10
2.0
3.0
4.0
0.1
12
Protection Characteristic
Earth Fault - I2t ON (SR71)
10,000
1000
100
10
0.2
0.3
0.4
0.5
0.6
0.4s
0.1
0.1s
0.01 0.05
0.1
0.8
2.4 1 10 50 1000
100
0.2
0.3 0.4
0.5
10
0.6
5.0
1.0
0.4s 0.3s
0.2s
0.1
0.1s
13
Protection Characteristic
Overload (SR21i)
10000
1000
100
10
30 17 12 6 3.5
10
0.6
0.5 0.4
0.3
0.3 0.26
0.2
0.2 0.16
0.1
0.1
0.06
0.02
0.01 1 2 3 4 5 6 7 8 9 10 20 100
14
Protection Characteristic
Ground Fault (SR21i)
1
0.2
0.6 0.4
0.3
0.2
0.1
0.1
Overload (SR18/18G)
1000
0.01 0.1
10
100
100
10
15
Protection Characteristic
Short Circuit (SR18/18G)
1
0.3
0.3 0.26
0.2
0.2 0.16
0.1
0.1
0.06
0.02
1
0.3
0.2
0.1
0.1
16
Protection Characteristic
Time-current (DN1)
10000
1000
100
0.01
0.7
3 4 5 678910
20 304050
100
400
1000
17
CA-1
Only for DC
Internal Wiring
81
FCA
82
Internal Wiring
( (
( (
Load A Closing Electric Charging Coil Device 10 11 12 13 14 Neutral U/V Closing C.T. release Preventer Aux NO
40
10
12
14
16 B D 82 42 42
C6
52
55
74
75 71
72
89
Main Circuit
Micro switch Spring Common Separate Shunt Under Electrical for ground Charging fault fault trip voltage anti-pumping fault in DN1 Indication Indication Indication Indication Indication release 15 16 17 18 19 20 21
Ref no.
As per order/requirement FCA R C11 C6 Limit switch(Shown in breaker reset condition) Economy Resistor Limit switch operates when closing electromagnet is held on Service position microswitch for withdrawable circuit breakers(shown in test position) For SR21i release (P&C unit) i discrimination i discrimination SI, SO GI, GO G
The above drawing is for EDO breakers. 1) For MDO/MF versions Ref no. 3, 10, 11 are not applicable E, B, C, D, A are applicable only in electrical breakers.
2) For EF versions The ref. no. 12, 13, 14, 15, 16, 17, 18, 19, 20, 21 are provided as per customer requirement.
Short circuit i/p & o/p Ground fault i/p & o/p Ground
( (
18
1 E 3 H 50 73 5 C 81 41 41 70 7 9 11 13 15 B 88
N R Y B
Wiring Diagram
( (
R
( (
x x x x
C11
H
ECD
4 CC NCT MV CP
DN1/SR18/SR18G SR21i/SR71
anti pumping
EA/ EA1 F
90
Accessories
Type Lockable Trip Push Button (LTPB) Data
Mounted in place of normal trip push button. With this, ACB can be locked in trip condition. For interlocking, LTPBs are offered in the following combinations: l 4 different types of keys i.e. AA, BB, CC and DD suitable for 2 I/C & 1 B/C
schemes
l
Combination of J, K, L, M, N, JK, KL, LM and MN locks, which are suitable for 5 I/C & 4 B/C schemes
Locking in Isolated Position (LIP) The facility of locking the ACB in Isolated position is available in Drawout ACBs. This is useful to achieve interlocking between Main & Standby source. Similar lock is available as LOCK IN ANY POSITION. Door Interlock This ensures: l Unless the panel door is closed, breaker cannot be racked in or out l Unless the breaker is in Isolated Position, it is not possible to open the panel door Racking Interlock This ensures that breaker cannot be racked in/out unless the ACB is in tripped/open condition.
Door Interlock
Racking Inerlock
Mechanical Interlock
It is possible to provide Mechanical Interlock between two breakers of the same or different ratings in vertical or horizontal configurations. Mechanical interlock is available for ACBs up to 4000A. Mechanical interlocking for ACBs in vertical configuration can be provided by links or by flexible cables. Same for horizontal configuration can be provided by flexible cables.
19
Accessories
Type
C1
Data
Common indication of tripping due to overload, short circuit and ground faults. Provided by micro-switch C1 fitted inside the ACB l Available as an option in all releases l
C2
Separate indication of tripping due to overload, short circuit and ground faults. l For release type DN1, this is provided by micro-switch C1 & C2 (C2 fitted inside release) Available through in-built fault indicators in SR18, SR18G, l SR21i & SR71 releases
AN1-Annunciator Module
Remote indication of tripping due to overload, short circuit and ground faults. Can be used with releases type SR18/SR18G/SR21i l l Individual fault indication provided by three separate LEDs for - Long time faults - Short time fault/instantaneous fault - Ground fault - One potential free contact rated 5A at 230V AC available for each type of fault l Flush mounting on panel (H-W-D=92mm x 46mm x 105mm) l Operating voltage: 240V AC / 110V DC / 220V DC (other Voltages available on request)
C5
Indication for operation of shunt release or undervoltage release. Provided by micro-switch C5 fitted on the shunt release or l
undervoltage release
20
Accessories
Type Shunt Release
l
Data For remote tripping of the breaker l Shunt release coil is short time rated and is disconnected from the circuit by an auxiliary contact when the ACB trips (Refer to wiring diagram) l Low power consumption l Two types available: - EA for DC application - EA1 for AC application
Technical Data
Type Rated Power Operation of Operational consumLimit Release voltage ption at (Ue) pick-up EA1 240 AC 415 AC 24V DC 48V DC 110 DC 220 DC 800 VA 800 VA 32 W 125 W 45 W 30 W 10-130% Ue 65-130% Ue
EA
Undervoltage Release
Parameter Rated Operational voltage (Ue) Pick up (V) Drop OFF (V) Consumption (VA) Watt loss
Specification 240V & 415V: 50Hz 220V & 415V: 60Hz 80% Ue 35-65% Ue Pick up - 23 VA Hold on - 10 VA 6W
Notes: When undervoltage release is provided, the ACB can be closed only when supply is available to the undervoltage release.
Closing Release
Closing release remotely closes the circuit breaker if the mechanism spring is already charged.
Rated Power Range of operational consumption operation voltage (Ue) Pick-up Hold-up 110V AC 240V AC 220V AC 110V DC 220V DC 24V DC 320VA 50VA 85-110% Ue
300W 350W
50W 50W
Electrical charging device automatically charges the mechanism spring of the circuit-breaker. After circuitbreaker closing, the geared motor immediately recharges the closing spring. Thus instantaneous reclosing of the circuit-breaker is possible following opening operation. Two combinations available: l 2 NO + 2 NC l 6 NO + 6 NC
Power consumption
Range of operation
Auxiliary Contacts
21
Overall Dimensions
Fixed Breakers
For 800A to 2500A 3P/4P C/H
For Metallic Components 340 min For Insulating Sheet 140 min 100 min 20 min 9 To Remove Arc Chute 7 Door Bezel 27 26
36 min A 26 58 264
36 min
385
200 min
33
394 309
22 16 27 104 Earthing Terminal 30 35 20 2 Holes-6.3 405 230 301 2.6 min 86 10 54 68.8
21
16
Ratings CN - CS 800/1000A 1250/1600A 630/800/1000A 1250/1600A 2000/2500A 2000/2500A C/H C/H C/H C/H C/H C/H 3P 3P 4P 4P 3P 4P
F -
98 156
54 55 69 77
40 min 56
20 min 23.5
102
X 5 15
Y 150 140
X 4 Holes 12 385
325
286
32
20 22 137.5
20
179.5
22
256
Overall Dimensions
Fixed Breakers
Terminal
2 Holes-13 30 15 30
3 Holes-13 15
25 50
12.5
25
50 100
25
2000/2500C/H
Terminal Connections
23.5
23.5 10 15
10 227 227
15
145
12 Holes-4
305 101
140
332
112
112
Hinge
Hinge
325
112
5.5
91
11 min
59
294
15 min
Door Cutout
363
Bezel
23
Overall Dimensions
Drawout Breakers
For 630A to 3200A C/H/S1 3P/4P , 3200H1/4000H 3P
For Metallic Components A 122 94.5 264 40 max 40 64.5 *5 75 Isolated Position 200 min 380 min For Insulating Sheet
100 min
468
397.5
404
46 6 199.5 6
28
10
54
538
308.5
308.5
221.5
221.5
308.5
*Terminal for 1250/1600/2500C/H & 800/1000H Ratings CN - CS 630/800/1000A 2000A 1250/1600A 630/800/1000A 2000A 1250/1600A 2000/2500A 2500/3200A 2000/2500A 2500/3200A 3200A 4000A 3200A 4000A C/H/S1 S1 C/H/S1 C/H/S1 S1 C/H/S1 C/H S1 C/H S1 H0/H1 H0/H H0/H1 H0/H 3P 3P 3P 4P 4P 4P 3P 3P 4P 4P 3P 3P 4P 4P 909 151.5 202 701 148.5 202 701 122.5 150 555 123.5 154 487 96.5 98 399 97.5 102 Dimensions (mm) A D E
98
156
202
24
221.5
68.8
160
256
Overall Dimensions
Drawout Breakers
Flat Terminal Connections
50 25 19 12.5 4 slots 8.5 x 9.5 8.5 10.2 58.4 38 4 Slots 8.5 x 9.5 8.5 10.2 58.4 6 Slots 8.5 x 9.5 20 63 25 100 30 30 10.2 58.4 6 Holes-14 68.8 10 199.5 10 5 615 17.5 min 18.9 max. 8.9 min. 18 20 245 54 256 467 46 6 5 74 28 D E F E D 217 8 Holes-14 28 17.5 40 42
64.5
38
8.5
2000C
160 25 25 25 25
38
2500S1
3200S1
For 5000C/6300C 3P
For Metallic Components 75 A 124 96.5 264 20 max 102 200 min 400 min For Insulating Sheet
100 min
Isolated Position
Door
7 Bezel
404
683
50
40
43.5
Earthing Terminal
63
160
M 10
Dimensions (mm) D 187.5 187.5 187.5 187.5 E 269 269 269 269 F 269 269
12.5
25
25
Overall Dimensions
Mounting Details
For Horizontal Mounting of all Draw-out Breakers
For 630A to 3200A C/H/S1 3P/4P 3200 H0/H1, 4000 H0/H 3P/4P
107.5 367.5 40 10 Holes-11 24
G (mm) 280.3 280.3 368.3 368.3 436.3 582.3 436.3 582.3 582.3 790.3 582.3 790.3 863 1132
Front
24 64.1
20
481
37
25
50 108.5 184.5
412
224
199
Base of Cradle
5.5
20.5 min
294
5 min
Door Cutout
Note: For 5000C/6300C 3P ACB, A = 81.5 For other Drawout Breakers A = 79.5
26
450
Overall Dimensions
Terminals
Horizontal Terminals
80 80 80 80
Rear Side
10
15
10
308.5
800 - 1000C
2 Holes-14 12.5 15
2000C
4 Holes-14 20
221.5
15
25 25 25
63 16.5
16.5
12.5
25
12.5
30 12.5 25 12 43
Vertical Terminals
V U 4 Holes-T O P 40.0 Top S W
387.5
221.5
308.5
Side View Ratings 630-1250 S1 & 800-1000 C 1600-2000 S1 & 1250-1600 C/H 800-1000 H 2000C 2500 S1/C/H 2000 H 3200 S1 M 10.2 20 20 20 30 N 38 40 40 40 60 P 20 20 20 20 20 Q 25 25 40 40 40 R
Rear View S 5 5 22.5 7.5 7.5 T 9 9 14 14 14 U 65 65 80 80 105 V 95 95 110 110 100 W 10 10 15 15 15 X 58.4 80 80 80 120
Note : 1) All Dimensions are in mm. 2) Consult us for other Terminal Orientations.
33 33
100
160
50
25
27
Overall Dimensions
Terminals
Vertical Terminals
V U Q
T
S P 60 W
15
The dimensions for 3200 H1/H0 and 4000 H0 are as under: Ratings 3200 H1/H0 & 4000 H0 M 30 N 100 P 45 Q 40 R 29.5 S 95 T 14 U 80 V 140 W 15 X 160
Note : 1) All Dimensions are in mm. 2) Consult us for other Terminal Orientations.
28
221.5
308.5
Product improvement is a continuous process. For the latest information and special applications, please contact any of our offices listed here.
Larsen & Toubro Limited Electrical Standard Products Powai Campus, Mumbai 400 072 Customer Interaction Center (CIC) BSNL / MTNL (toll free) : 1800 233 5858 Reliance (toll free) : 1800 200 5858 Tel : 022 6774 5858 Fax : 022 6774 5859 E-mail : cic@LNTEBG.com Website : www.LNTEBG.com
SP 50437 R3
170412