II
Explosion Protection Marking Equipment Group Equipment Category Explosive Atmosphere Suitability (G Gas, vapor or mist)
G / D
Ex
de
IIC
T6
Gb / Ex
1)
IIIC
T80C
Db
1)
Explosive Atmosphere Suitability (D Dust) Explosion Marking Type of protection (Gas) Explosion Group (Gas) Temperature Class (Gas) Equipment Protection Level (EPL-Gas)
Type of Protection ia ib ma mb mc p t
Description of Protection General Requirements Intrinsic Safety Intrinsic Safety Encapsulation Encapsulation Encapsulation Pressurized Protection by enclosure
ATEX Zone Zone 20, 21, 22 Zone 21, 22 Zone 20, 21, 22 Zone 21 or 22 Zone 20, 21, 22 Zone 22 Zone 20, 21, 22
CENELEC /IEC Standard EN 60079-0 / IEC 60079-0 /1D / Da EN 61241-11 / IEC 61241-11 /2D / Db EN 61241-11 / IEC 61241-11 /1D / Da EN 60079-18 / IEC 60079-18 /2D / Db EN 60079-18 / IEC 60079-18 /1D / Da EN 60079-18 / IEC 60079-18 /3D / Dc EN 61241-4 / IEC 61241-4 / 1 D, 2 D or 3 D / Da, Db, Dc EN 60079-31 / IEC 60079-31
Protection Concept Limit the surface temperature Limit the surface temperature Exclusion of Ex-atmosphere Exclusion of Ex-atmosphere Exclusion of Ex-atmosphere Exclusion of Ex-atmosphere Keep the combustible dust out and avoid hot surfaces
Explosion Groups
Typical Hazardous Material Acetylene Hydrogen Ethylene Propane Metal dust Coal dust Grain dust Wood, paper, or cotton processing Explosion Group Name and address of manufacturer Serial number including year of manufacture
Equipment name/type CE marking and number of Notified Body responsible for the monitoring of the Quality System (0102 = PTB Germany) Electrical parameters Ambient temperature -25C to +55C (if -20C to + 40C, marking is not required - Standard for all equipment) Other essential information required by the used Standards
Continuously for long Zone 0 periods or frequently Occasional occurrence Zone 1 Not likely, but if it does occur only rarely and for a short period Zone 2 Continuously for long Zone 20 periods or frequently Occasional occurrence Zone 21 Not likely, but if it does occur only rarely and for a short period Zone 22 Mining Mining
Certificate number May end with U Component cert. May end with X Special conditions for safe use Additional certificate (optional) Explosion protection marking (ATEX): Equipment Group (II) and Category (2) Type of explosive atmosphere G gas, vapor or mist / D dust Marking accd. IEC/CENELEC
eLLK 2010XYZ
www.ceag.de Made in Germany
S.Nr.: D123456 PTB 09 ATEX 12345 IECEx BVS 09.12345 II 2 G Ex de IIC T6 Gb II 2 D Ex t IIIC T80C Db 2010
0102
110 - 240 V 50 - 60 Hz 110 - 240 V DC Ta= -25C - +55C Lamp: G13 60081 IEC
Dust
Temperature Classification
Maximum Surface Temperature IEC NEC 505 T1 T2 NEC 500 Table 500.8(C) T1 T2 T2A T2B T2C T2D T3 T3A T3B T3C T4 T4A T5 T6 450C (842F) 300C (572F) 280C (536F) 260C (500F) 230C (446F) 215C (419F) 200C (392F) 180C (356F) 165C (329F) 160C (320F) 135C (275F) 120C (248F) 100C (212F) 85C (185F)
Intended Use
Indoor use, limited amounts of falling dirt Outdoor use, rain, sleet, windblown dust, external formation of ice Outdoor use, rain, sleet, external formation of ice Outdoor use, rain, sleet, windblown dust, external mechanisms operable when ice laden Indoor or outdoor use, windblown dust and rain, splashing water, hose directed water, external formation of ice Indoor or outdoor use, windblown dust and rain, splashing water, hose directed water, corrosion, external formation of ice Indoor use, settling airborne dust, falling dirt, non-corrosive liquids Indoor or outdoor use, hose directed water, temporary submersion, external formation of ice Indoor or outdoor use, hose directed water, prolonged submersion, external formation of ice Indoor use, Class I, Division 1, Groups A, B, C, and D hazardous locations, air-break equipment Indoor or outdoor use, Class I, Division 1 Groups A, B, C, and D hazardous locations, oil-immersed equipment Indoor use, Class II, Division 1, Groups E, F, and G hazardous locations, air-break equipment Mining applications Indoor use, circulating dust, falling dirt, dripping noncorrosive liquids Indoor use, circulating dust, falling dirt, dripping noncorrosive liquids, provided with knockouts Indoor use, lint, dust, spraying of water, oil and noncorrosive coolant
Zone Zone22
Zone 22 Zone 21
Zone Zone11
Zone 20
T3
IP56
T4 T5 T6
54 54 54
* NEMA Enclosure Type can be converted to IP Code rating, but IP Codes cannot be converted to NEMA Enclosure Type (Ref. NEMA 250) ** Enclosure Types for U.S. only (Ref. NEMA 250)
Hazardous Atmosphere Category (Gas or Dust Grouping) Temperature Classification Hazard Category Area Classification Explosion Protection Standard (EX-IEC/ATEX/CEC, AEx-NEC) Method of Explosion Protection Hazardous Atmosphere Category (Gas or Dust Grouping) Temperature Classification
e n
d q ia ib
1, 2 1, 2 -
1, 2 1, 2 0, 1, 2 1, 2
1, 2 1, 2 -
1, 2 1, 2
p m o
1, 2 2
1, 2 1, 2 1, 2
1, 2 2
1, 2 1, 2 1, 2
Area Classification
Continuous Hazard Division 1 Zone 0 (Zone 20 dust) Intermittent Hazard Division 1 Zone 1 (Zone 21 dust) Hazard under Abnormal Conditions Division 2 Zone 2 (Zone 22 dust)
Dusts
Cooper Crouse-Hinds GmbH Neuer Weg-Nord 49 D-69412 Eberbach/Germany Phone: +49 6271 806-500 Fax: +49 6271 806 476 E-mail [email protected]
Crouse-Hinds is a registered trademark of Cooper Industries, Inc. 2010 Cooper Industries, Inc./ 300 8000 2154/3/02.10/SL