LT Acdb

Download as pdf or txt
Download as pdf or txt
You are on page 1of 44

Sabarmati River Front Development Corporation Limited

Page 148

TECHNICAL SPECIFICATION FOR ELECTRICAL WORK (MATERIAL SPECIFICATION)

Signature of Bidder

Sabarmati River Front Development Corporation Limited

Page 149

MATERIAL SPECIFICATION SUMMARY PAGE

I.

Electrical Works

Page No

______________________________________________________________________________

A.

Material Specification Section - 1 Section - 2 Section - 3 Section - 4 E-6 E-9, 10 E-14 E-17 LT Switchgear LT Cabling and Termination Earthing External Lighting 150 175 176 181 184 185 189

B C D

Special Condition for Testing Applicable Standards - IS codes List of Approved make

Sabarmati River Front Development Corporation Limited

Page 150

ELECTRICAL MATERIAL SPECIFICATION E-6 1.1 LT SWITCHGEAR & POWER PANEL Scope: The scope covers supply, installation, testing and commissioning of electrical panels, incorporating circuit breakers, fuse units, busbars, interconnections, earthing etc., meeting the requirements shown in equipment schedule and the drawings. Standards: AS PER SCHEDULE OF INDIAN STANDARD; ATTACHED WITH THE DOCUMENT. The PCCs & MCCs shall comply with the latest edition of relevant Indian standards and Indian Electricity rules and regulations. The following Indian Standards shall be complied with: IS : 4237 IS : 375 IS : 2147 IS : 8197 IS : 2557 IS : 2516 IS : 1818 IS : 3072 IS : 8623 : : : : : : : : : General requirements for switch gear and control gear for voltage not exceeding 1000 V. Switchgear bus-bars, main connection and auxiliary wiring, marking and arrangement. Degree of protection provided by enclosures for low voltage switch gear and control gear. Terminal marking for electrical measuring instrument and their accessories. Danger notice plates. Specification for AC circuit breaker. Specification for AC isolator and earthing switch. Code of practice for installation and maintenance of switchgear. Specification for factory built as symbolize of switch gear and control gear for voltage up to and including 1000v. A.C.& 1200 v. D.C. Miniature Circuit Breaker. Fuse switch and switch fuse unit. HRC fuse unit. Current transformer. Voltage transformer. Electrical relay for protection. indicating instrument. Integrating instrument. Control switches & push buttons. Auxiliary contactor. AC motor starters of voltage not exceeding 1000V.

1.2

IS : 8828 IS : 4064 IS : 9224 IS : 2705 IS : 3155 IS : 3231 IS : 1248 IS : 722 IS : 6875 IS : 2959 IS : 1822

: : : : : : : : : : :

Sabarmati River Front Development Corporation Limited

Page 151

1.3 1.3.1

TYPE OF LT SWITCH GEAR: All the PCCs / PDBs / MCCs shall be metal clad or - environment friendly, recyclable, halogen & silicon free, highly impact resistant, Anti Acid, Anti corrosive & fire retardant polycarbonate thermoplastic, - (for material of panel i.e. metal or thermo plastic, BOQ should be referred) totally enclosed, rigid, floor / wall mounted, air - insulation, cubical type suitable for operation on three phase / single phase, 415 / 230 volts, 50 Hz. neutral effectively / Non effectively grounded at transformer and short circuit level not less than 30 MVA at 415 volts. The PCCs / MCCs shall be designed to withstand heaviest condition at site, with minimum expected ambient temperature of 55 degree Celsius, 90 percent humidity and dusty weather. Should confirm to Indian Electricity Act and rules. (as amended up to date) & approval of FIA. of India. STRUCTURE: The PCCs, MCCs & PDBs shall be metal clad enclosed and be fabricated out of high quality CRCA sheet, suitable for outdoor installation having dead front operated and floor mounting type. (Applicable for Metallic Panels Only) All CRCA sheet steel used in the construction of PCCs / MCCs / PDBs shall be 2 mm thick and shall be folded and braced as necessary to provided a rigid support for all components. Joints of any kind in sheet shall be seam welded, all welding slag grounded off and welding pits wiped smooth with plumber metal. (Applicable for Metallic Panels Only) All Thermoplastic Panel Enclosures made out of environment friendly, recyclable polycarbonate thermoplastic, halogen & silicon free, highly impact resistant, Anti Acid, Anti corrosive, Colour Gray RAL 7032 ( or as specified later), fire retardant, self extinguishing glow wire tested at 960 deg. cent in acc with DIN VDE 0304 Part 3, with transparent / opaque lids having quick fastening mechanism. The panel should be Modular Panel Box System type with Degree of Protection IP 65, in accordance with IEC 60 529, type tested in accordance with IEC 60 439 - 1. (Applicable for Thermoplastic Panels Only) The PCCs / MCCs / PDBs shall be totally enclosed, completely dust and vermin proof and degree of protection being not less than IP-43 for Indoor panels & IP -54 for outdoor panels . Gaskets between all adjacent units and beneath all covers shall be provided to render the joints dust proof. All doors and covers shall be fully gasket with foam rubber and / or rubber strips and shall be lockable. All panels and covers shall be properly fitted and screwed with the frame, and holes in the panel correctly positioned. Fixing screw shall enter into holes taped into an adequate thickness of metal or provided with bolts and nuts. Self threading screws shall not be used in the construction of PCCs / MCCs / PDBs.

1.3.2

1.3.3

1.4 1.4.1

1.4.2

1.4.2a

1.4.3

1.4.4

Sabarmati River Front Development Corporation Limited

Page 152

1.4.5 1.4.6

A base channel of 75 mm x 75 mm x 5 mm thick shall be provided at the bottom. PCCs / MCCs /PDBs shall arrange in multi-tier formation. The PCCs / MCCs / PDBs shall be of adequate size with a provision of 20 percent spare space to accommodate possible future additional switch gear. The size of the PCCs / MCCs / PDBs shall be designed in such a way that the internal space is sufficient for hot air movement, and the electrical component dose not attains temperature more than 40 degree Celsius. If necessary openings shall provided for natural ventilation, but the said openings shall be screened with fine weld mesh. Knockout holes of appropriate size and number shall be provided in the PCCs / MCCs/ PDBs in conformity with number, and size of incoming and outgoing conduits / cables. Alternatively the PCCs / MCCs / PDBs shall provided with removable sheet plates at top and bottom to drill holes for cable / conduit entry at site. The PCCs / MCCs / PDBs shall be designed to facilitate easy inspection, maintenance and repair. The PCCs / MCCs / PDBs shall be sufficiently rugged in design and shall support the equipment without distortion under normal and short circuit condition, they shall be suitable braced for short circuit duty. PROTECTION CLASS: All the indoor PCCs / MCCs / PDBs shall have protection class as per IS.

1.4.7

1.4.8 1.4.9

1.4.10

1.5

1.6

PAINTING: All sheet steel work shall undergo a process of decreasing pickling in acid, cold rinsing, phosphating, pessivating and then sprayed with a high corrosion resistant primer. The primer shall be backed in an oven. The finishing treatment shall be by application. Three coats of synthetic enamel paint of approved colour shall be applied by spray and stoves in dust free atmosphere or the panel shall be powder coated.

1.7 1.7.1

CIRCUIT COMPARTMENT: Each circuit breaker and switch fuse units shall be housed in separate compartments and shall be enclosed an all sides. Sheet steel hinged lockable door shall be duly inter locked with the breaker / switch fuse units in ON and OFF position. Safety interlocks shall be from being drawn out when the breaker is in ON position. The door shall not form as integral part of the drawout position of the circuit breaker. All instruments and indicating lamp shall be mounted on the compartment door. Sheet steel barriers shall be provided between the tires in a vertical section. INSTRUMENT COMPARTMENT Separate and adequate compartment shall provided for accommodating instruments, indicating lamp, control contactors, relays and control fuses etc. These components shall be accessible for testing and maintenance without any danger of accidental contact with live parts of the circuit breaker, switch fuse units, busbars and connections.

1.7.2

1.8

Sabarmati River Front Development Corporation Limited

Page 153

1.9 1.9.1

BUSBARS The busbar shall be air insulated and made high quality, high conductivity, high strength copper and as per relevant IS code. The busbar shall of three phases and neutral system with separate neutral and earth bar. the busbar and interconnection between busbar and various components shall be of high conductivity, hard drawn, electrolytic copper. the busbar shall be of rectangular cross section designed to withstand full load current for phase busbar and full rated current for neutral busbar and shall be extensible type on either side. The busbar shall be rated for the frame size of the main incoming breaker but in any case not less than 200 amp capacity. The busbar shall have uniform cross section through out the length. The busbar and interconnection shall be insulated with heat shrinkable PVC sleeves and be colour coded in red, Yellow, Blue and Black to identify the three phases and neutral of the system. The busbar shall be supported on unbreakable, non hygroscopic DMC insulated supports at sufficientevely close interval to prevent busbar sag and shall effectively withstand electromagnetic stresses in the event of short circuit capacity of 50 KA RMS symmetrical for one second and a peak short circuit withstand of 105 KA minimum. The busbar shall be housed in a separate compartment. The busbar shall be isolated with 3 mm thick bakelite sheet to avoid any accidental contact. The busbar shall be arranged such that minimum clearance between the busbar are maintained as per below. Between phases Between phases and neutral Between phases and earth Between neutral and earth : : : : 27 mm min. 25 mm min. 25 mm min. 23 mm min.

1.9.2

1.9.3

1.9.4

All busbar connection shall be done by drilling holes in busbars and connecting by chromium plated brass bolt and nuts. Additional cross section of busbar shall be provided in all PCCs / MCCs / PDBs to cover-up the holes drilled in the busbars. Spring and flat washers shall be used for tightening the bolts. All connection between busbar and circuit breaker / switches and between circuit breaker/ switches and cable terminals shall be through solid copper strips of proper size to carry full rated current. These strips shall be insulated with insulating strips. ELECTRICAL POWER & CONTROL WIRING CONNECTION Terminal for both incoming and outgoing cable shall be suitable for 1100 volts grade, aluminium/copper conductor PVC insulated and sheathed, armoured cable and shall be suitable for connections of solder less sockets for the cable size as indicated on the appended drawing for the PCCs, MCCs, PDBs. Both control and power wiring shall be brought out in cable alley for ease of external connections, operation and maintenance. Both control and power terminals shall properly be shrouded. 10% spare terminal shall be provided on each terminal block. Sufficient terminals shall be provided on each terminal block so that not more than one outgoing wire connected per terminal. Terminal strip for power and control shall preferably be separated from each other by suitable barriers of enclosures.

1.9.5

1.10 a)

b)

c) d)

e)

Sabarmati River Front Development Corporation Limited

Page 154

f)

Wiring inside the module for power, control protection and instrument etc. shall be done with use of 660/1100 confirming to IS 694 and IS 8130. Power wiring inside the starter module shall be rated for full current rating of contactor, but not less than 4 sq mm cross section area. For current transformer circuits, 2.5 sq mm copper conductor wire shall be used. Other control wiring shall be done with 2.5 sq mm copper conductor wires. Wires for connections to the door shall be flexible. All conductors shall be crimped with solder less sockets at the ends before connections are made to the terminals. Control power for the motor starter module shall be taken from the respective module switchgear outgoing from R phase and Neutral. Control wiring shall have control fuse (HRC type). Particular care shall be taken to ensure that the layout of wiring neat and orderly. Identification ferrules shall be filled to all the wire termination for ease of identification and to facilitate and testing. "CUPAL" washers shall be used for all copper and aluminum connections. Final wiring diagram of the PCC, MCC, PDB power and control circuit with ferrules number shall be submitted along with the PCC/MCC/PDB as one of the documents. TERMINALS The outgoing terminals and neural link shall be brought out to a cable alley suitably located and accessible from the panel front. The current transformer for instrument metering shall mount on the disconnecting type terminal blocks. No direct connection of incoming and outgoing cables to internal components connection of the distribution board is permitted, only one conductor may be connected in one terminal.

i)

j)

k) l)

1.11

1.12

WIREWAYS A horizontal PVC wire way with screwed covers shall provided at the top to take interconnecting control wiring between different vertical sections.

1.13

CABLE COMPARTMENT Cable compartment of adequate size shall be provided in the PCCs, MCCs, PDBS for easy termination of all incoming and outgoing cables entering from bottom or top. Adequate support shall be provided in the cable compartment shall be brought out to terminal blocks in the cable compartment.

1.14 a)

EARTHING Copper earth busbar of 25 mm x 3 mm shall be provided in the PCCs, MCCs, PDBs for the entire length of panel. The frame work of the PCCs, MCCs, PDBs shall be connected to this earth busbar. Provisions shall be made for connection from earth busbar to the main earthing bar coming from the earth pit on both sides of the PCCs, MCCs, PDBs. The earth continuity conductor of each incoming and outgoing feeder shall be connected to this earth bar. The armour shall be properly connected with earthing clamp and the clamp shall be ultimately bounded with the earth bar. LABELS Engraved PVC labels shall be provided on all incoming and outgoing feeders. Single line circuit diagram showing the arrangements of circuit inside the distribution board shall be pasted on inside of the panel door and covered with transparent laminated plastic sheet.

b)

1.15

Sabarmati River Front Development Corporation Limited

Page 155

1.16 a)

NAME PLATE A name plate with panel designation in bold letter shall be fixed at top of the central in panel. A separate name plate giving feeder giving feeder details shall be provided for each feeder module door. Inside the feeder compartment, the electrical component, equipments, accessories like switchgear, contactor, lamp, relays etc. shall suitably be identified by providing stickers. Engraved name plates shall preferably be of 3 ply, (red-white-red or black-white-black) lamicold sheet. However black engraved perplex sheet name plates shall also be applicable. Engraving shall be done with square groove cutters. Name plate shall be fastened by counter sunk screws and not by adhesives. DANGER NOTICE PLATE The danger plate shall be affixed in a permanent manner on operating side of the panel. The danger notice plate shall indicate danger notice both in Hindi and English and with a sign of skull and bones. The danger notice plate in general shall meet to requirements of local inspecting authorities. Overall dimension of the danger notice plate shall be 200 mm wide and 150 mm high. The danger notice plate shall be made from minimum 1.6 mm thick mild steel sheet and after due pre-treatment to the plate, the same shall be painted white with vitreous enamel paint on both front and rear surface of the plate. The letter, the figure, the conventional skull and bones shall etc. shall be positioned on the plate as per recommendations of IS : 2551-1982. The said letter, the figure and the sign of skull and bones be painted in single red colour as per IS : 5-1978. The danger plate shall have rounded corners. Locations of fixing holes for the plate shall be decided to suit design of the panel. The danger notice plate, if possible, be of ISI certification mark. INTERNAL COMPONENTS The PCC / MCC / PDB shall be equipped complete with all type of required number of air circuit breakers, switch fuse unit, contactor, relays, fuses, meters, instruments, indicating lamps, push buttons, equipment, fittings, busbar, cable boxes, cable glands etc. and all the necessary internal connections /wiring as required and as indicated on relevant drawings. Components necessary for proper complete functioning of the PCC / MCC / PDB but not indicated on the drawings shall be supplied and installed on the PCC / MCC / PDB. All part of the PCC / MCC/ PDB carrying current including the components, connections, joints and instruments shall be capable of carrying their specified rated current continuously, without temperature rise exceeding the acceptable values of the relevant specifications at any part of the PCC / MCC / PDB. All units of the same rating and specifications shall be fully interchangeable.

b)

c)

d) 1.17 a) b)

c) d)

e) f)

g) h) 1.18 a)

b)

c)

Sabarmati River Front Development Corporation Limited

Page 156

1.19

INSPECTIONS Each equipment should inspect and witness by client & consultant.

a)

The PCC / MCC / PDB shall be inspected and checked as per inspection manual of the PCC / MCC / PDB manufacturer. Various electrical components and accessories of the PCC / MCC / PDB shall be checked as per drawing for the respective PCC / MCC / PDB. The PCC / MCC / PDB shall be checked for rigid mounting, earthing connections, proper rating and size of components, internal wiring, etc. All mechanical fasteners and electrical connections shall be checked and tightened before installation. Type test certificates for all ACB for similar rating shall be submitted. Test: a) Prior to dispatch of the PCC / MCC / PDB following tests shall be carried out. b) Mechanical endurance test shall carry out by closing and opening of all the ACBs, MCB's switches etc. c) Over voltage and Insulation resistance test shall be carried out between phases and between phases to earth bus, keeping the isolating switch in ON position. Similar test shall be carried out keeping the isolating switch in closed position. d) All the interlocks, controls and tripping mechanism of the switch gears shall be tested for their proper functioning.

b) c) d)

e) f)

1.20 A) a) b)

COMPONENTS: GENERAL The type, size, and rating of the components shall be as indicated on the relevant drawings. While selection OD the capacity of the components resulting from the prevailing conditions like room temperature shall be allowed for the Thermal and magnetic trip rating shall be compensated for the ambient temperature. The rating indicated on the drawings are rating anticipated at prevailing site condition. FUSE SWITCH UNIT: NOT REQUIRED MINIATURE CIRCUIT BREAKER Miniature circuit breakers shall be quick make and break and break type conform with British standard BS: 3871 (Part-I) 1965 and IS: 8825 (1996). The housing of MCBs shall be heat resistant and having a high impact strength. The fault current of MCBs shall not be less than 10000 amps, at 230 volts. The MCBs shall be flush mounted and shall be provided with trip free manual operating mechanism with mechanical "ON" and "OFF" indications.

c) B) C)

Sabarmati River Front Development Corporation Limited

Page 157

The circuit breaker dollies shall be of trip free pattern to prevent closing the breaker on a faculty current. The MCB contact shall be silver nickel and silver graphite alloy and tip coated with silver. Proper arc chutes shall be provided to quench the arc immediately. MCB's shall be provided with magnetic fluid plunger relay 3 as for over current and short circuit protection. The over load or short circuit devices shall have a common trip bar in the case of DP and TPN miniature circuit breakers. All the MCB's shall be tested and certified as per Indian Standard, prior to Installation. D) E) FUSE:-NOT REQUIRED AIR CIRCUIT BREAKER The ACB shall meet with IS: 2516 part I, II and III. Each pole of the ACB's shall be equipped with and over current, earth fault and short circuit release. The ACB's shall be equipped with under voltage trip also. The trip devices shall be direct acting. Disconnecting devices of approved type shall be provided to facilitate the removal of the circuit breakers from the housing for test and maintenance purpose. The ACB's shall have an are quenching device on each pole. The ACB's shall have auxiliary contacts for signalling, interlocking etc. The ACB's shall have slow close facilities for checking contact operation and contact gap adjustment. All contacts subject to arcing shall be tipped with arc resisting material. main contacts shall be silver plated, multi-finger and spring loaded type. Facilities shall be provided to isolate the circuit breaker for inspection purpose. Interlocks shall be provided to : Prevent the breaker from being isolated unless it is in the "OFF" position. Prevent the breaker from being racked in to the service position unless it is in the "OFF" position. Prevent the breaker from being accidentally pulled completely "OFF" the guide rail. Safety shutters of an insulation material shall be provided to prevent access to all live contacts, when the breaker is in the inspection position or completely withdrawn. Facilities shall be provided for earthing the circuit breaker. Air circuit breaker shall be capable of clearing the maximum fault current which can occur. The breaker plates shall have an ON-OFF indicators, spring charge indicators, provision to padlock manual handle and provision to lock drawout mechanism. Electrically operated breaker shall have provision for emergency manual closing by inserting a tool through the fuse plate. A control isolating switch shall be provided on the fuse plate to isolate the supply to the charging motor. F) MOULDED CASE CIRCUIT BREAKER The MCCB shall be air break type and having quick make quick break with trip free operating mechanism. Housing of the MCCB shall be of heat resistant and flame retardant insulating material. Operating handle of the MCCB shall be in front and clearly indicate ON / OFF / TRIP positions.

Sabarmati River Front Development Corporation Limited

Page 158

The electrical contact of the circuit breaker shall be of high conducting non deteriorating silver alloy contacts. The MCCB shall be provided with thermal / magnetic type bi-metal over load release and electro-magnetic short circuit protection device. All the releases shall operate on common trip busbar so that in case of operation of any one of the releases in any of the three phases, it will cut off all the three phases and thereby single phasing of the system is avoided. The MCCB whenever called for in the appendix drawings shall provide an earth fault relay. The MCCB shall provide two sets of extra auxiliary contacts with connections for additional controls at future date. The electrical parameters of the MCCB shall be as per the descriptions given in the appended drawings. G) CONTACTORS: The contactor shall meet with the requirements of IS : 2959 and BS : 775. The contactors shall have minimum making and breaking capacity in accordance with utilization category AC 3 and shall be suitable for minimum class II intermittent duty. If the contactor forms part of a distribution board then a separate enclosure is not required, but the installation of the contactor shall be such that it is not possible to make an accidental contact with live parts. H) LOAD MANAGER: The load manager should be 192 x 144 mm size having facility to read voltage current harmonics power parameters. It should contain real time clock. The meter should be field programmable and to generate high / low profile for all power parameters with date & time, also able to store previous period integrated data. The meter should have RS 485 port for networking purpose. All the programming should be pass word protected. I) CURRENT TRANSFORMER Where ammeter is called for, CT's shall provide for current measuring. Each phase shall be provided with separate CT of class I accuracy and suitable VA burden for operation of associated metering and controls. Current transformer shall be in accordance with IS : 2705 - 1964 as amended up to date. J) PUSH BUTTON: The push button unit shall comprise of the contact element, a fixing holder, and push button actuator. The push button shall be momentary contact type. The contacts shall be of silver alloy and rated at 10 Amps. continuous current rating. The actuator shall be of stranded type and colour as per its usage for ON, OFF and Trip. K) INDICATING LAMP: Indicating Lamp shall be transformer operated low voltage rated and shall supplied complete with translucent covers to diffuse the lamp light. Colour shade for the indicating lamps shall be as below:

Sabarmati River Front Development Corporation Limited

Page 159

ON indicating lamp OFF indicating lamp TRIP indicating lamp PHASE indicating lamp L) 1.0 1.1

: : : :

Red Green Amber Red, Yellow, Blue.

CAPACITOR BANKS WITH APFCR/RTPF PANEL: Scope The design, manufacture and performance of the power factor improvement capacitor / capacitor banks shall comply with all currently applicable statutes, regulations and safety codes in the locality where the equipment will be installed. The equipment shall also conform to the latest applicable Indian / British / IEC standards. In particular the equipment shall conform to the latest revisions of the following: IS: 2834 IS: 2208 : : Shunt capacitors for power system. HRC cartridge fuse and links up to 660 V.

When the above standards are in conflict with the stipulation of this specification, this specification supersedes them. CONSTRUCTION: CAPACITOR BANK Capacitors should be marked as per IS: 13340, IS: 13341 and should conform to IS: 12672. It should be suitable for temperature category of 50 deg. Cen. Capacitor banks shall comprise of identical delta connected three phase units. The individual capacitor unit shall be manufactured out of double layer mixed dielectric design comprising of basally oriented polypropylene film and capacitor tissue paper. Each individual element of the capacitor tissue unit shall be provided with silver fuse wire. The capacitor unit shall consist of many such elements in series / parallel combinations for getting the desired KVAR output. The capacitor shall be vacuum impregnated with liquid dielectric having high thermal stability. The dielectric losses of the capacitor shall be restricted to 1 watt per KVAR. The phase terminal connections of the capacitor unit shall be brought out at the top through metal insulators which should be soldered to the fabricated top cover. The capacitor shall be provided with suitably rated discharge resistors. The capacitor shall be designed to withstand the electrodynamics and thermal stresses caused by transient over current during switching. The capacitors should be provided with over pressure safety interrupter mechanism, which will automatically disconnect faulty capacitor unit from the network silently without bursting, bulging or exploding the capacitor. BUSBAR CHAMBER Capacitor bank shall be provided with a bus-bar chamber. The chamber shall be dust and vermin proof in construction, fabricated from 2 mm thick sheet steel. Continuous neoprene rubber gaskets shall be provided on all mating surfaces. TP Bus-bars shall be of copper supported on epoxy insulators of adequate rating and strips. The bus-bar sizes and clearances shall be suitable for connection of cables through crimping type cable lugs. Bus-bar chamber shall be extended suitably on one side to enable termination of cable. There shall be a provision of cable end box at the end of bus-bar chamber undrilled removable gland plate and access covers to be provided for cable entry as required.

Sabarmati River Front Development Corporation Limited

Page 160

EARTHING: The enclosure of individual capacitor unit shall be provided with 2 nos. 10 mm dia earth terminals, each complete with two plain and one spring washer, nuts etc. These terminals shall be effectively bonded to the common sheet steel frame work. Each bank will have two external earth terminals in the bus-bar chambers complete with hardware. PAINTING: All sheet steel shall be thoroughly cleaned, decreased and phosphate painted with two coats of suitable primer and finished with two coats of paint. The type and shade of paint be as specified in Data Sheet. DRAWINGS: The following drawings shall be submitted along with the bid: a. General arrangement drawing showing overall dimensions, weight, internal arrangement and mounting details. b. Terminal chamber, showing bus-bar arrangement with all dimensions. TEST & TEST CERTIFICATES: Vendor shall carry out all routine tests as specified in IS: 2834 and shall furnish the test certificates. The vendor shall also carry out the thermal stability test on the units in the presence of purchasers representatives. The capacitor units shall be tested from electric supply authorities like G. E. Board / A. E. Co. and the test certificates in duplicate shall be furnished to client and also the copy shall be submitted to the electric supply authority while getting the power supply released from them. CAPACITOR PANEL: Capacitor control panel should be automatic type. The panel for capacitor shall be fabricated from 2.0 mm thick sheet steel and shall be finished as per clause no. 5.0. Earthing terminals shall be provided as per clause no.4.0. The panel shall be provided with suitably rated TPN copper bus-bar supported on epoxy insulators and with heat shrinkable type sleeves. Each capacitor unit shall be connected to main busbar through contactors of suitable rating with safety margin. Protective breaker for each capacitor bank of suitable rating should be provided. Connections shall be made with PVC insulated flexible copper cables having crimped copper lugs. Continuous earthing conductor / strip of G.I shall run through and all capacitor units shall be earthed. Sufficient ventilation shall be provided in the capacitor compartment to limit the temperature rise. Cooling fans shall be provided with ON-OFF switches as per requirements. The main bus-bar shall be terminated on suitably rated MCCB. Vertical compartment with detachable gland plate shall be kept for incoming cable connections from bottom or top as specified.

Sabarmati River Front Development Corporation Limited

Page 161

Capacitors units shall be mounted on angle frame of strong construction. The panel shall be mounted on M.S. channel section at bottom for easy installation. The panel shall be provided with lifting hooks / Eye bolts for handling. Automatic power factor correction sensing relays (RTPFC) shall be provided with all related circuits and contactors for controlling the power factor by energizing the contactor and related capacitor bank "ON" or "OFF" as per load conditions. The controller shall be set for time lag of 45 seconds so that on sensing the low or high power factor it energies or de energizes the contactor after 45 seconds. The Dust and vermin proof switching compartment shall be isolated from capacitor mounting compartment. The panel shall be provided with: a. b. c. d. e. f. g. MCB /MCCB of adequate capacity as per rating. 100 x 100 mm. flush type 0-500 V voltmeter with selector switch. 100 x 100 mm. flush type Ammeter with suitably rated C.T. and selector switch. Supply "ON' indication lamp (R-Y-B). Power Factor meter 0.5 lag to 0.5 lead. KVAR meter of suitable rating. Each outgoing feeder should be provided with adequate size breaker, contactor, relay, ON/OFF push button with indicating lamp, auto/manual by pass switch with indicating lamp. h. By - pass switch for each capacitor unit. i. Automatic Power Factor correction relay unit with ON - OFF mode selector switch. The capacitor panel shall be installed away from wall with sufficient distance for better cooling and ease of maintenance. The following drawings shall be submitted before procurement for approval from the client. 1. 2. 3. 4. 1.2 1.2.1 General arrangement and Fabrication details. Power wiring diagram of capacitor panel. Control wiring diagram of capacitor panel. C.T. connection.

Approval, Testing & Co-ordination: The following drawings shall be submitted before procurement for approval from the client. 1. 2. 3. 4. 5. General arrangement and Fabrication details. Power wiring diagram of the panel. Control wiring diagram of panel. C.T. ratios with connection. Material list with make, catalogue nos and

1.2.2

Testing and setting the relay set point and co-ordination between relay on LT/HT fuses, breaker, setting shall be done by contractor. The down stream of the setting should be provided.

Sabarmati River Front Development Corporation Limited

Page 162

1.2.4

The relay should be tested by reputed agencies and test report of the relay should be submitted by the contractor. Technical Specifications for Single Phase & Three phase Electronic Energy Meter of Class 1.0 Accuracy SCOPE This specification covers the design, engineering, manufacture, testing and calibration at manufacturers works before dispatch, packing, supply and delivery of Class 1.0 accuracy, electronic energy meter, suitable for connection to LT A) Single phase 2 wire 240V system B) Three phase 3-phase, 4- wire 415V system The static whole current electronic meter shall offer current range of 5-30 A, 10-60A (first digit indicates the Basic Current & second digit indicates the Maximum Current of the respective meters) for tariff purposes, as per requirement given in this specification.

M) 1.0

2.0

STANDARDS APPLICABLE Unless specified elsewhere in this specification, the performance & testing of the meters shall conform to the following Indian/International standards, to be read with up to-date and latest amendments/revisions thereof. S. No. 1 2 Standard No. IS 13779 read with its latest amendments CBIP Report No.88 (revised July 1996) read with latest amendments Title Specification of AC Static Watt hour meters class 1.0 & 2.0 Specification for AC Static Electrical Energy Meters

3.0

CLIMATIC CONDITION The meters to be supplied against this specification shall be suitable for satisfactory continuous operation under the following tropical conditions. Meters shall be capable of maintaining required accuracy under hot, tropical and dusty climate. i) Maximum Ambient Air Temperature in shade ii) Minimum Ambient Air Temperature iii) Relative Humidity 100% Iv) Minimum Relative Humidity : : : : 50oC -10oC. 95% (noncondensing) 100%

4.0

SUPPLY SYSTEM 1 Phase 2 Wire 240 V Phase to Neutral Basic current 5/10/10 Amps (lb), Maximum current 30/60/100 Amps (l max) Rated Frequency 50 Hz POWER SUPPLY VARIATION System Rated voltage (Vref) Rated Basic Current (lb) 3 Phase 4 Wire 433 V Phase to Phase Basic current 5/10/10 Amps (lb), Maximum current 30/60/100 Amps (l max) 50 Hz

5.0

The meter should be suitable for working with following supply system variations.

Sabarmati River Front Development Corporation Limited

Page 163

System Specified range of operation Frequency 6.0 ACCURACY

1 Phase 2 Wire 70% to 120% of reference Voltage i.e. 240 V 50Hz+/-5%

3 Phase 4 Wire 70% to 120% of reference Voltage i.e. 415 V 50Hz+/-5%

Class of accuracy of the meter shall be 1.0. The accuracy shall not drift with time. 7.0 7.1 POWER CONSUMPTION Voltage Circuit: The active and apparent power consumption in each voltage circuit including the power supply of meter at reference voltage, reference temperature and reference frequency shall not exceed 1.5 Watt and 8 VA respectively Current Circuit: The apparent power taken by each current circuit at basic current, reference frequency and reference temperature shall not exceed 4 VA. GENERAL & CONSTRUCTIONAL REQUIREMENTS Meters shall be designed and constructed in such a way so as to avoid causing any danger during use and under normal conditions. However, the following should be ensured. a) Personal safety against electric shock b) Personal safety against effects of excessive temperature. c) Protection against spread of fire d) Protection against penetration of solid objects, dust & water The meter shall be designed with application specific integrated circuit and shall be manufactured using SMT (Surface Mount Technology) components. Power supply and voltage divider circuits may be of PTH technology. All insulating material used in the construction of meters shall be non-hygroscopic, non-ageing and of tested quality. All parts that are likely to develop corrosion shall be effectively protected against corrosion during operating life by providing suitable protective coating. The meter shall conform to the degree of protection IP 51 for protection against ingress of dust, moisture and vermins. The meter shall be capable of providing phase to phase protection upto 450V. The meter shall be supplied with a transparent extended terminal block cover (ETBC). The ETBC shall not be easily detachable from the base and preferably be secured to the base using a hinging arrangement. The meter-base, meter cover, terminal block and ETBC shall be made of unbreakable, high grade, fire resistant, reinforced, non-flammable, polycarbonate or equivalent high grade engineering plastic. The meter cover shall have a fully transparent window. The window shall be of transparent, high grade UV stabilized engineering plastic for easy reading of all the displayed values/parameters, and observation of operation indicator. The window shall preferably be an integral part of meter cover.

7.2 11.0 11.1

11.2

11.3

11.4

11.5 11.6 11.7

11.8

Sabarmati River Front Development Corporation Limited

Page 164

11.9

The meter cover shall be sealable to the meter base with at least 2 nos. seals. Also terminal cover shall have provision for sealing with at least one seal. The terminal block shall be made of high grade non-hygroscopic, fire retardant, low tracking, fire resistant, reinforced poly-carbonate or equivalent high grade engineering plastic with terminal holes of minimum dia 8.5 mm and shall be suitable to accommodate the insulation of the conductors, meeting the requirement of IS 13779 /CBIP technical report-88. The manner of fixing the conductors to the terminal block shall ensure adequate and durable contact such that there is no risk of loosening or undue heating. Meter shall have 2 screws in each terminal for effective clamping of cables. Screw connections transmitting contact force and screw fixing which may be loosened and tightened several times during the life of the meter shall be such that the risk of corrosion resulting from contact with any other metal part is minimized. Electrical connections shall be so designed that contact pressure is not transmitted through insulating material. The clearance and creepage distance shall conform to relevant clause of IS 13779/CBIP technical report No.88. The meter shall be compact in design. The entire construction shall be capable of withstanding stresses likely to occur in actual service and rough handling during transportation. The meter shall be convenient to transport and immune to shock and vibration during transportation and handling. The meter shall have 3 fixing holes, one at top and two at bottom. The top hole shall be such that the holding screw is not accessible to the consumer after fixing the meters. The lower fixing screws shall be provided under the sealable terminal cover. ANTI-TAMPER FEATURES The meter registration shall be immune to reversal in current direction. The meter shall have anti-tamper features

11.10

11.11

11.12

11.13

12.0

13.0 13.1

DISPLAY The measured value(s) shall be displayed on a Liquid Crystal display (LCD) register. The height of the digit shall be minimum 8.5 mm. The KWh energy registration shall take place with 6 complete digits. The display shall have backlit capability for easy reading. The data should be stored in non-volatile memory (NVM). The non-volatile memory should retain data for a period of not less than 10 years under un-powered condition. Battery back-up memory will not be considered as NVM. The register shall be able to record and display starting from zero, for a minimum of 1500 hours, the energy corresponding to rated maximum current at reference voltage and unity power factor. The register should not roll over in between this duration. In addition to providing serial number of the meter on the display plate, the meter serial number shall also be programmed into meter memory for identification through communication port for CMRI/meter reading print out.

13.2 13.3

13.4

Sabarmati River Front Development Corporation Limited

Page 165

14.0

DISPLAY SEQUENCE The meter shall display the required parameters in two different modes as follows:

A)

Auto Display Mode: The following parameters hereinafter referred to as Billing Parameters (B.P) shall be displayed in an auto-cycle mode, in the following sequence:LCD Test Real Time Date Cumulative Active energy (forwarded) reading (kWh) Instantaneous Load (KW) Billing period counts Each parameter shall be on meter display for 10 seconds and the time between two auto-cycles shall be 120 seconds.

B)

Push Button Mode:In addition to the auto display mode parameters, the following parameters shall be displayed on pressing the push button

C)

LCD Test Real Time Date Instantaneous voltage, current The meter shall also be capable of offering a high resolution display which shall enable conducting of dial testing by the user in the shortest possible time and as a minimum, the meter shall be capable of offering a resolution of 4 digits after decimal (and 2 digits before decimal) for the high resolution KWh display. COMMUNICATION PORT The meter should have a galvanic ally isolated optical communication port for data communication. Adequate sealing provision shall be provided.

15.0

16.0

MARKING OF THE METER The marking on the meter shall be in accordance with relevant clauses of IS 13779. The basic marking on the meter nameplate shall be as follows: a) b) c) d) e) f) g) h) i) j) k) l) Manufacturers name & trade mark Type Designation No. of phases & wires Serial number Year of manufacture Reference Voltage Rated Current Principal unit(s) of measurement Meter Constant ( imp/ kwh) Class index of meter Property of ______ Purchase Order No. & Date

Sabarmati River Front Development Corporation Limited

Page 166

17.0

CONNECTION DIAGRAM & TERMINAL MARKINGS The connection diagram of the meter shall be clearly shown on terminal cover. OUTPUT DEVICE The meter shall have a test output accessible from the front and capable of being monitored with suitable testing equipment while in operation at site. The test output device shall be provided in the form of LED output.

18.0

1.21 1.21.1

L T FEEDER SECTION PILLAR SCOPE: (i) This specification covers the scope of design, fabrication, assembling, inspection at vender's works and delivery in properly packed condition to project site of cubical pattern MV Switchgear. (ii) The switchgear would comprise Main L.T. power distribution panel, Section pillar, sub-section pillar, power distribution board (PDB).

1.21.2

CODES AND STANDARDS : (A) The equipment shall be designed to conform to Indian Standards: IS : 8623 and IEC-439 IS : 4237 IS : 2147 IS : 375 (B) : : : : the requirements of following

Factory built assemblies of switchgear and control gear. General requirements for switchgear and control gear for voltage not exceeding 1000 volts. Degree of protection provided by enclosures for low voltage switchgear and control gear. Marking and arrangement of bus bars.

Individual equipment housed in the Medium Voltage Switchgear shall conform to the following IS specifications. 1. IS : 13947(part-3) & IEC: 947-3 : : Air break switches and fuses combination units for voltage not exceeding 1000 Volts (specific requirements for the direct switching of individual motors) i.e. suitable for AC 23 duty. Direct acting electrical indicating instruments. PVC insulated cables and aluminium conductors. Low voltage fuses. Air circuit breakers. Current transformers Contactors.

2. 3. 4. 5. 6. 7. 8. 9. 10.

IS : 1248 : IS : 694 (1990) and IS : : 8130 (1994) IS : 13703 (PART 2 ) : IS : 13947 (PART 2 ) : IS : 2705 : IS:13947(PART-4/SEC-1) : & IEC-60947-4-1 IS:13947(PART-4/SEC-1) : Thermal overload relay & IEC-60947-4-1 Indian Electricity Rules : As amended up to date Approval From T.A.C./F.I.A. OR C.P.R.I. Tested.

Sabarmati River Front Development Corporation Limited

Page 167

8.3

DESIGN & CONSTRUCTION REQUIREMENTS: (a) The switch board shall be for outdoor application, metal enclosed or Polycarbonate Thermoplastic, dust & vermin roof, free standing, floor mounting, compartmentalized, modular type & extensible on both sides. (b) The switch board shall be fabricated from CRCA sheet steel having following minimum thickness (Applicable for metallic panels only): o o o o Frames, load bearing members & large doors : 2.5 mm(12 swg) Partitions & small doors : 2.03 mm(14 swg) Front, back & side covers : 2.03 mm(14 swg) Section pillar : outer side(Front, back & side covers) 12 SWG and inner side 14 SWG

(c) The switch board shall be totally insulated Section Feeder Pillar Panel made out of Modular Panel Box System, Degree of Protection IP 65, in accordance with IEC 60 529, type tested in accordance with IEC 60 439 - 1. Enclosures made out of environment friendly, recyclable polycarbonate thermoplastic, halogen & silicon free, highly impact resistant, Anti Acid, Anti corrosive, Colour Gray RAL 7032 (or as specified later), fire retardant, self extinguishing glow wire tested at 960 deg. cent in acc with DIN VDE 0304 Part 3, with transparent / opaque lids having quick fastening mechanism. (Applicable for Thermoplastic panels only) (d) The board shall be divided in to distinct vertical sections, each comprising of: o o o o A completely enclosed bus bar chamber running horizontally throughout the length of the switchboard. Individual feeder modules. Vertical busbar chamber at the side of feeder modules or back of the feeder module. Cable alley shall be with 250 mm width for double front execution.

(e) The switchboard shall be provided with degree of protection of not less than IP 42 as per IS 2147 for indoor application and all section pillar /sub-section pillar shall be of not less than IP-55 as per IS outdoor application. (f) Maximum height of the board including the height of the Base Channel shall be 2450 mm. Also, the minimum & maximum mounting height of the switches, relays & instruments etc. shall be 200 mm & 2000 mm respectively, above the bottom of the Base Channel. (g) Suitable sized thick neoprene gaskets shall be provided all round the perimeter of doors, covers etc for making the construction dust & vermin proof. (h) Power/control terminals in the cable alleys for each module & also the busbar chamber shall be covered with hinged & bolted type Hylam shrouds respectively to prevent accidental contact when the door/cover is withdrawn. In each feeder module, the phase barrier of Hylam sheet shall be provided between the adjacent phases. (i) Suitable lifting hooks shall be provided on each shipping section of the board. Each module shall be considered as separate shipping section. (j) In case of double front type design the vertical busbar chamber shall be common for the front sided feeders as well as for the rear sided feeders in each panel of the switchboard.

Sabarmati River Front Development Corporation Limited

Page 168

(k) Gland plate of 5 mm thickness shall be provided at the top or bottom of the board, and gland plate shall be of non -magnetic type. (Where ever required) (l) All the feeder modules & the cable alleys are provided with hinged type doors and cam lock with key lock chromium plated, whereas all the busbar chambers are provided with bolted type . (m) Main earth bus of aluminium flat shall be suitably placed running throughout the length of the switchboard. (n) All the hardwares used in the construction of the switchboard shall be chromium /zinc plated passivated type with spring washers to avoid loosening of the fixed parts. 8.4 METAL TREATMENT AND PAINT FINISH (Applicable for Metallic Panels only) : (a) PRE TREATMENT CHEMICAL PROCESS: All sheet steel work used in the construction of the switchboards shall be pretreated with 7-tank chemical process as specified in the specific requirement sheet before applying the two coats of zinc chromate primer followed by synthetic enamel/epoxy paint as follows : 71. TANK PROCESS:DEGREASING:In this process the M.S. Sheets shall be effectively cleaning by dipping in hot alkaline degreasing solution for the period of about 10-20 minutes. 2. WATER RINSING:After degreasing process the M.S. sheets shall be rinsed in to the water for the period of about 1-2 minutes to remove the loosened oil, grease and adhering alkali from the surface. 3. DERUSTING:In this process the M.S. sheets shall be pickled in dilute sulphuric acid to remove oxide scales and rust formation for the period of about 30 minutes. 4. WATER RINSING:After the de-rusting process the M.S. sheets shall be rinsed in to the water for the period of about 1-2 minutes to remove the traces of acidic solution from the surface. 5. PHOSPHATING:In this process the M.S. sheets shall be dipped in to the zinc phosphate solution for the period of about 30 minutes to facilitate durable coating of the paint on the metal surfaces.

Sabarmati River Front Development Corporation Limited

Page 169

6. WATER RINSING:After the phosphating process the M.S. sheets shall be rinsed in to the water for the period of about 1-2 minutes to remove the traces of phosphate solution from the surface. 7. PASSIVATION:In this process the M.S. sheets shall be dipped in to the de-oxalite solution for the period of about 1 minute to retain and augment the effects of phosphating on the surface. After completion of 3-tank/7-tank process a fine grained, smooth and compact coating of iron/zinc phosphate shall be produced, which is an excellent base for paint and provide under film protection against corrosion. The coating shall meet the Indian Standard Specification IS:3618-1966 class C. (b) DRYING: After the above pre treatment chemical process, the M.S. sheets shall be dried either by means of hot air circulation oven (stoving) or by means of blast of compressed air (air drying). (c) PRIMER COATING: Primer coating with two coats of highly corrosion resistant zinc chromate primer shall be done before applying the final paint finish. (d) PAINT FINISH: The final finishing of synthetic enamel/epoxy paint of RAL-7032 shall be matt finish powder coated. 8.5 (A) MATERIAL/COMPONENT SPECIFICATIONS : BUSBAR: (a) The busbar shall be air insulated with heat shrinkable coloured sleeves and made of high conductivity high strength Aluminium complying to the requirements of IS : 5082. (b) The busbar shall be suitably braced with non-hygroscopic epoxy resin cast/SMC supports at regular distance to provide a through fault withstand capacity of 50 KA RMS symmetrical for one second and a peak short circuit withstand of 150 KA minimum. Ridges shall be provided on the busbar supports to prevent tracking between adjacent busbars. (c) The main horizontal busbars shall be positioned at top portion running throughout the length of the switch board. The cross section of the busbar shall be uniform throughout the length of busbar. The busbars shall be insulated with coloured PVC heat shrinkable sleeves i.e. red coloured for R-phase, yellow coloured for Yphase, blue coloured for B-phase and black coloured for Neutral. Also the sequence of R, Y & B phase busbars shall be from top to bottom/left to right/front to back respectively and Neutral busbar shall be fixed near to R or B phase busbar.

Sabarmati River Front Development Corporation Limited

Page 170

(d) The vertical busbars shall be provided in separate vertical busbar alley adjacent to individual feeder modules. Suitable barrier shall be provided in front of vertical busbar against accidental contact after the module has been withdrawn. (e) Pre-drilled holes shall be provided on the vertical risers so that modules can be changed at site, for vacant feeders also. (f) High tensile bolts and spring washers shall be provided at all busbar joints. Also, all busbar joints shall be protected by using hylum/plastic shrouds. (g) The minimum clearance in air between phase to phase busbars as well as between phase to earth shall be 25 & 20 mm respectively or as per fault level requirement. (h) Main busbars shall be adequately sized, so that, while carrying rated current continuously the maximum temperature of busbars, even at joints, does not exceed 85 degree centigrade. (i) Danger caution plates shall be provided on each busbar chamber cover. (j) For Aluminium bus bar, current shall be considered 400 Amps per 625 Sqmm cross-sections. (B) UNIT MODULE: (a) Each module shall be suitable for mounting drawout type air circuit breakers/MCCB/MCB power fuses, control fuses, contactors, relays, push buttons, indicating lamps, terminal blocks etc. as may be required. (b) Each module shall be provided with individual door and the door shall be mounted on the main structure. The doors shall be provided with concealed hinges. The module door with chromium plated locks / key operation. (c) Unit doors shall be interlocked mechanically with breaker/switch/fuse switch to prevent unintentional opening of the door while the units is in energized condition. However, provision should be made to open the door in energized condition i.e. defeat facility, for testing purpose. (d) Main HRC fuses shall be positioned before the isolator to eliminate any position hazards during a fault at the isolator terminals. The HRC fuses however, shall not be accessible when they are in live condition. (C) CIRCUIT BREAKERS:(a) The circuit breaker shall be air break type, FOUR pole, Drawout type and electrically operated type as specified in the schematic drawing complying to the requirements of IS : 13947(PART 2) (b) The circuit breaker shall be provided with shunt trip mechanism. (c) The circuit breaker shall be provided with inbuilt over current, short circuit and earth fault releases or separate protection relays as may be specified in the schematic drawing. All release shall be micro processor based. (d) The circuit breaker shall be provided with 6 NO + 6 NC auxiliary contacts rated 10 Amp, 240 Volt AC supply duly wired up to the terminal block for purchaser's use.

Sabarmati River Front Development Corporation Limited

Page 171

(e) The circuit breaker shall be provided with red, green, amber and white indicating lamps for indicating closed, open, auto trip and trip circuit healthy conditions of the breaker. all release shall be micro processor based. (f) Automatic safety shutters shall be provided to completely cover the female primary contacts when the breaker is withdrawn from service position. (g) Compartment door of breaker should not open unless the associated breaker is in open position. The interlock defeat also to be provided. (h) Closing action of the breaker shall charge the tripping spring ready for tripping. (i) Manually operated breaker shall be of the spring charging stored energy type. (j) Electrically operated breaker shall be provided with following:(i) 1 no 240 V, 1-ph, 50 Hz AC universal motor for charging the breaker closing spring along with HRC fuse link with base and carrier or SP MCB of appropriate rating and of approved make. Motors shall be sized such that maximum spring charging time is less than 15 seconds. (ii) Limit switches with 2 NO + 2 NC contacts for cutting off the power supply to spring charging motor when spring is under fully charged conditions. (iii) Closing of breaker shall automatically initiate ready for next closing. (D) (E) SWITCHES/FUSE SWITCHES: Not Applicable FUSES: (i). Fuses shall be of HRC cartridge link type having rupturing capacity of not less than 80 KA at 440 Volt. (ii). Fuses shall preferably be mounted in moulded plastic carriers and shall be complete with fuse bases. (iii). Fuses shall be suitably rated to prevent damage of the switchgears incorporated in the respective circuit of the particular module in case of overloading or any other fault occuring in the circuit. (F) CONTACTOR: (i). All the motor starter feeders shall be provided with electromagnetic type triple pole contactors suitably rated for uninterrupted AC-3 duty and shall comply with the requirements of IS : 13947 (PART 4 /SEC. 1) (ii). Main contacts of the contactors shall be of silver plated copper. (iii). Each contactor shall be provided with 2 NO + 2 NC auxiliary contacts. (iv). Operating coils of contactors shall be suitable supply of 420V/240V/110V AC. (G) TIMER WITH POWER RESERVE CAPACITY: (i). Power reserve capacity of timer shall be minimum up to 150 HRS. And timer with 24 HRS. Programmer. for operation from the control the recharging of closing spring

Sabarmati River Front Development Corporation Limited

Page 172

(ii). Timer shall be with High switching capacity and with inbuilt over-ride facility. (iii). Modular construction, Flush\Base\Din rail mounting (H) THERMAL OVERLOAD RELAYS : (i). All the motor starter feeders shall be provided with triple pole bimetal thermal overload relays with inbuilt single phasing protection to furnish protection against overload and single phasing and shall comply to all the requirements of IS : 13947 (PART 4 /SEC. 1) (ii). Thermal overload relays shall be provided with adjustable settings. The setting range shall be properly selected in accordance with the rating of the motor.

(iii). Thermal overload relays shall be provided with at least 1NO + 1 NC auxiliary contacts. (iv). Thermal overload relays shall be either self reset type or hand reset type. In case of hand reset type thermal overload relays, the reset push button shall be mounted flush on the compartment door separate from start/stop push button. (I) CURRENT TRANSFORMERS: Current transformers shall have adequate class of accuracy and VA burden to comply with all the requirements of IS : 2705.The design of current transformers shall be of ring tape wound type. Unless otherwise specified, the minimum performance requirements of current transformers are as follows: Measuring CT :- rated burden 15 VA, accuracy class 1.0 Protective CT :- rated burden 15 VA, accuracy class 5P10 All current transformers shall be earthed through a separate earth link on the terminal block to permit easy measurement of the current transformer insulation resistance. Secondary windings of current transformers shall be rated for 1 Amp as specified in the schematic diagram of the switchboard. (J) INDICATING INSTRUMENTS: (i). Ammeters and Voltmeters shall be of moving iron spring controlled (MISC) industrial type suitable for flush mounting of size 144x144/96x96 sq.mm. of suitable range as specified in the schematic drawing of the switchboard. (ii). Ammeters with suppressed scale current rating shall be provided for specific requirements. (iii). Energy meter (KWH meter) of direct reading 3-phase 4 wire unbalance type shall be provided wherever specified in the schematic drawing of the switchboard. It should be mounted inside the compartment but can be read through cut out on the compartment door. iv) Power factor meter (PF meter), frequency meter (Hz meter), Wattmeter (KW meter) etc. shall be provided if specified in the schematic drawing of the switchboard.

Sabarmati River Front Development Corporation Limited

Page 173

(K) INDICATING LAMPS : (i). Indicating lamps shall be of LED. The lamps shall have translucent lenses to diffuse light. (ii). Indicating lamps shall be provided in the respective colours i.e. Red, Yellow, Blue, Green, Amber, white etc. as required in the schematic drawing of the switchboard. (L) PUSH BUTTONS : (i). Push buttons shall be rated for 10 Amp at 240 Volt AC and provided with 1 NO + 1 NC auxiliary contacts. (ii). On/start push button actuator shall be of Green colour, off/stop push button actuator shall be of Red colour and O/L relay reset push button actuator shall be of Black colour. (M) INTERNAL WIRING: (i). All power/control wiring of the switchboard shall be made with 1100/660 Volt grade Black/Gray FRLS-PVC insulated flexible/stranded copper wires. (ii). The size of control wiring shall be 2.5 sq.mm. except for CT secondary circuit of 2.5 sq.mm. wire. (iii). Pin type crimping lugs shall be provided for flexible wire terminations. (iv). Power wiring shall be terminated preferably on stud/clamp type terminal blocks, whereas, control wiring shall be terminated on clip-on type terminal blocks. (v). All electrical connections are made vibration proof by proper tightening by using plain washers and spring washers etc. (N) TERMINAL BLOCK: (i). Terminal blocks for power circuits shall be of 660 V grade with contacts of rating not less than 10 Amps. They shall be of the stud type of Elmex/Connectwel make with insulated barriers between adjacent terminals. (ii). Terminal blocks for control circuits shall be of clip on type of Elmex/Connectwel make complete with mounting channel. (iii). The wire terminations to the blocks shall be screw type suitable for crimp type socket. (iv). Suitable provision shall be made to terminate power/control connections in the respective module. (O) SPACE HEATER: Space heater with thermostat and switch shall be provided in each cable alley of the cubical switchboard if specified in the specific requirement sheet.

Sabarmati River Front Development Corporation Limited

Page 174

(P)

LABLES: Labels shall be of anodized aluminium or acrylic sheets with white engraving on black back-ground. The engraving shall provided at the back side of label. They shall be properly secured by fasteners at convenient location on each feeder module, busbar chamber and cable alley of the cubical switchboard.

8.6.

TESTS: The switchboards shall be tested for all the following routine tests in accordance with IS:8623 of specification for Factory Built Assembly (FBA) of switchgear & control-gear for voltage up to and including 1000 V AC and 1200 V DC. a. Inspection of the switchboard including inspection of wiring and electrical operational test, where necessary. b. High voltage test c. Insulation resistance test (Meggar test)

8.7

DRAWINGS AND DOCUMENATION: (a) General Arrangement (GA) drawings indicating front, rear, side, sectional views, dimensions of the feeder modules and overall dimensions of the switchboards shall be furnished along with the offer. (b) After getting the order, the supplier should submit two sets of the following drawings and technical data to us for our review and approval. (i) General Arrangement (GA) drawings indicating front, rear, side, sectional views, dimensions of the feeder modules and overall dimensions of the switchboards. (ii) Single line diagrams of the switchboards. (iii) Control schematic drawings for various types of feeders. (iv) Bills of quantity sheet indicating details of components (make, cat no, rating, type etc.) in each feeder of the switchboards. (c) According to the changes/comments we have mentioned, the supplier should submit the final three sets of the above drawings/documents for our reference and record. One will remain with us, one with client and one will be return back to supplier duly signed & sealed.

Sabarmati River Front Development Corporation Limited

Page 175

E 9, 10 1.1

LT CABLING AND TERMINATION Scope: The scope consists of Supply, laying, testing and commissioning of L.T. XLPE Cable and its termination.

1.2

Standards: AS PER SCHEDULE OF INDIAN STANDARDS; ATTACHED IN THE DOCUMENT

1.3 A)

Cables: LV POWER CABLES will be 1100 Volts grade single / multicore standard aluminum conductor extruded XPLE insulated with extruded PVC inner sheath outer sheath made of FRLS PVC compound conforming to IS-7098 part-1. Single core will be used for DC application. Cables in buried insulation shall be armoured type. Armoured cable should be provided with galvanized steel wire or strip armouring. Control cables will be 1100 Volts grade multicore minimum 2.5 sqmm cross section standard copper conductor minimum 7 strands PVC insulated inner extruded sheathed and other sheath made of extruded FRLS PVC compound conforming to IS-1554 part-1. Cables in buried insulation shall be armoured type.

B)

C)

All cables shall be new without any kind or visible damage. The manufacturers name, insulating material, conductor size and voltage class shall be marked on the surface of the cable at every 600 mm centres. Cable joints and termination: Connectors : Cable terminations shall be made with copper/Aluminium Heavy duty long neck copper crimping lugs only crimped type solder-less lugs for all aluminium cables and stud type terminals. For copper cables copper crimped solder-less lugs shall be used. Crimping shall be done with the help of hydraulically operated crimping tool. All cable lugs should be long neck type only.

1.4 A)

B)

Cable Glands : Cable glands shall be of heavy duty brass compression / whether proof type as specified. Generally single compression type cable glands shall be used for indoor protected locations and double compression type shall be used for outdoor locations. Glands for classified hazardous areas shall be CMRI approved.

C)

Ferrules : Ferrules shall be of self sticking type and shall be employed to designate the various cores of the control cable by the terminal numbers to which the cores are connected, for ease in identification and maintenance.

D)

Cable joints : Kit type joint shall be done and filled with insulating compound. The joint should be for 1.1 KV grade insulation.

Sabarmati River Front Development Corporation Limited

Page 176

E 14 1.0

EARTHING Scope of Work: The scope of work shall cover supply, laying, installation, connecting, testing and commissioning of:

1. 1.2 1.3 1.4 1.5 2.0 2.1

copper/galvanized/aluminium/chemical or Electrode type Earthing station. Earthing G.I./Aluminum/copper strips from earthing station to equi-potential bar. Earthing G.I./ Aluminum/ copper strips/ wires from equi-potential bar to lay feeder mains and circuit to connect power panels, DBs, switchboards etc. Bonding of Non-current carrying parts, and metallic parts of the electrical installation. Provide inter connection between all earth pits of same type. STANDARDS The following standards and rules shall be applicable: 1) IS: 3043 - 1966 Code of practice for Earthing. 2) Indian Electricity Act and Rules

2.2

All codes and standards mean the latest. Where not specified otherwise the installation shall generally follow the Indian Standard Code of Practice or the British Standard Codes of Practice in absence of Indian standard. GENERAL All the non-current carrying metal parts of the electrical installation and mechanical equipments shall be earthed properly. The metal conduits, trucking, cables armoured and sheath, electric panels boards, lighting fixtures, ceiling and exhaust fan and all other parts made of metal shall be bonded together and connected by means of specified earthing system. An earth continuity conductor shall be installed with all the feeders and circuits and shall be connected from the earth bar of the panel boards, to the conduit system, earth stud of the switch box, lighting fixture, earth pin of the socket outlets and to any metallic wall plates used. All the enclosures of motors shall be also connected to the earthing system.

3.0

4.0 4.1 4.1.1 4.1.2 4.1.3 4.1.4

TYPE OF EARTHING STATION PLATE EARTHING STATIONS The earthing station shall be as shown on the drawing IS:3043. The earth resistance shall be maintained with suitable soil treatment as shown in the drawing. The resistance of each earth station should not exceed the limit specified in IS : 3043. The earth lead shall be connected to the earth plate through copper/brass bolts in case of copper earth plate and shall be hot dip galvanized iron for G.I. plate earth plate as shown on the drawing.

Sabarmati River Front Development Corporation Limited

Page 177

4.1.5

The earthing grid and the earthing conductors shall be of copper strip in case of copper earth plate and hot dip galvanized iron strip in case of G.I. earth plate of size as mentioned on the drawing. G.I. pipe with funnel with filter of approved quality shall be used for watering the earthing electrodes \ stations. The block masonry chamber with Cast Iron hinged cover of 300 x 300 mm shall be provided for housing the funnel and the pipe for watering the earthing electrodes \ stations. PIPE EARTHING STATIONS The substation earthing shall be with GI Pipe earthing station and equipment earthing grid shall be with hot dip galvanized iron earthing station. The Pipe electrode shall 38mm dia GI pipe for earthing The earthing station shall be as shown on the drawing. The earth resistance shall be maintained with suitable soil treatment as shown in the drawing. The resistance of each earth station should not exceed 4 ohms. The earth lead shall be connected to the earth plate through copper/brass bolts in case of copper earth plate and shall be hot dip galvanized iron for G.I. Pipe earth as shown on the drawing. The earthing grid and the earthing conductors shall be of hot dip galvanized iron strip of size as mentioned on the drawing. The block masonry chamber with Cast Iron hinged cover of 300 x 300 mm shall be provided for housing the funnel and the pipe for watering the earthing electrodes \ stations. The hardware and other consumable for earthing installation shall be of copper/brass in case of copper earth plate and shall be hot dip galvanized iron material in case of G.I. Pipe , as per details shown in the drawing . ELECTRODE / CHEMICAL TYPE EARTHING STATIONS: The substation earthing and equipment earthing shall be with T-39 OR & T-19 as per earthing scheduled in BOQ & Drawing. The earthing station shall be as shown on the drawing. The earth resistance shall be maintained with suitable soil treatment as shown in the drawing. The resistance of each earth station should not exceed the limit specified in IS: 3043. The earthing grid and the earthing conductors shall be of copper strip of size as mentioned on the drawing. The block masonry chamber with Cast Iron hinged cover shall be provided for housing the termination block as shown in the drawing.

4.1.6

4.1.7

4.2 4.2.1 4.2.2 4.2.3 4.2.4

4.2.5 4.2.6

4.2.7 4.2.8

4.2.9

4.3 4.3.1

4.3.2 4.3.3 4.3.4 4.3.5

4.3.6

Sabarmati River Front Development Corporation Limited

Page 178

4.3.7

The hardware and other consumable for earthing installation shall be of copper/brass, as per details shown in the drawing. INSTALLATION AND CONNECTION: The plate \ pipe electrode, as far as practicable, shall be buried below permanent moisture level but in no case not less than 2.5 M below finished ground level. The plate \pipe electrode shall be kept clear of the building foundation and in no case, it shall be nearer by less than 2 M from outer face of the respective building wall \ column. The plate electrode shall be installed vertically and shall be surrounded with 150 mm. thick layers of Charcoal dust and Salt mixture. G.I. pipe for watering shall run from top edge of the plate \ pipe electrode to the mid level of block masonry chamber. Top of the pipe shall be provided with G.I. funnel and screen for watering the earth \ ground through the pipe. The funnel with screen over the G.I. pipe for watering to the earth shall be housed in a block masonry chamber as shown in the drawing. The masonry chamber shall be provided with a Cast Iron hinged cover resting over the Cast Iron frame which shall be embedded in the block masonry. Construction of the earthing station shall in general be as shown in the drawing and shall conform to the requirement on earth electrodes mentioned in the latest edition of Indian Standard IS : 3043, Code of Practice for Earthing Installation. The earth conductors ( Strips / Wires copper/ Hot dip G.I.) inside the building shall properly be clamped / supported on the wall with Galvanized Iron clamps and Mild Steel Zinc Passivated screws \ bolts. The conductors outside the building shall be laid at least 600 mm. below the finished ground level. The earth conductors shall either terminate on earthing socket provided on the equipment or shall be fastened to the foundation bolt and / or on frames of the equipment. The earthing connection to equipment body shall be done after removing paint and other oily substances from the body and then properly be finished. Over lapping of earth conductors during straight through in joints, where required, shall be of minimum 75mm. long. The earth conductors shall be in one length between the earthing grid and the equipment to be earthed. EARTH LEADS AND CONNECTIONS: Earth lead shall be bare copper or galvanized steel as specified with sizes shown on drawings. Copper lead shall have a phosphor content of not over 0.15 %. Galvanized steel buried in the ground shall be protected with bitumen and Hessian wrap or polytene faced Hessian and bitumen coating. At road crossing necessary hume pipes shall be laid. Earth lead run on surface of wall or ceiling shall be fixed on saddles so that strip is at least 8 mm away from the wall surface. The complete earthing system shall be mechanically and electrically bonded to provide an independent return path to the earth source.

5.0 5.1 5.2

5.3 5.4

5.5 5.6

5.7 5.8

5.9

5.10

5.11

5.12 6.0 6.1

6.2

Sabarmati River Front Development Corporation Limited

Page 179

7.0

EQUIPMENT EARTHING: All apparatus and equipment transmitting or utilizing power shall be earthed in the following manner. Copper/G.I. earth strips/wires shall be used unless other wise indicated in the Schedule B.

8.0 8.1

POWER TRANSMISSION APPARATUS Metallic conduit shall not be accepted as an earth continuity conductor. A separate insulated / bare earth continuity conductor of size 50 % of the phase conductor subject to the minimum and maximum shall be provided. Copper Minimum (sqmm) Maximum (sqmm) 2.5 75 Aluminum 4.0 100 G.I. 6 200

The earth continuity conductor be drawn inside the conduit shall be insulated. 8.2 Non metallic conduit shall have an insulated earth continuity conductor of the same size as for metallic conduit. All metal junction and switch boxes shall have an inside earth stud to which the earth conductor shall be connected. The earth conduct or shall be distinctly coloured (Green or Green/Yellow) for easy identification. Armoured cable shall be earthed by two distinct earth connections to the armouring at both the ends and the size of connection being as for the metallic conduit. In the case of unarmoured cable, an earth continuity conductor shall either be run outside along with the cable or should form a separate insulated core of the cable. Three phase power panel and distribution boards shall have two distinct earth connections of the size correlated to the incoming cable size. In case of single phase DB's a single earth connection is adequate. UTILIZING EQUIPMENT: Three phase motors and other three phase apparatus shall have two distinct earth connections of the size equal to 50% of the connecting cable subject to the following: Copper Minimum (sqmm) Maximum (sqmm) 9.2 6.5 75 Aluminum 10 10 G.I. 20 200

8.3

8.4 8.5

9.0 9.1

For single phase motors and apparatus, the single earth connection shall be provided of the above size. For all light fittings and fans a single earth connection with 1.5 sqmm copper or equivalent size shall be provided. All street light poles shall have an earth stud and shall be connected to the cable armouring using 6.5 sqmm copper or equivalent unless shown otherwise. For street lighting poles planted in ground, 2.4 M long 10 SWG bare copper wire shall be coiled and buried with every fourth pole in addition to connection to cable armouring. An equipment earthing grid shall be established as shown in the drawing. All earth connections to all panels, DB's and equipment shall be connected to the nearest point of the earthing grid.

9.3

9.4

Sabarmati River Front Development Corporation Limited

Page 180

10.0 10.1

TEST: The entire earthing installation shall be tested as per requirements of Indian Standard Specification IS: 3043. The following earth resistance values shall be measured with an approved earth meggar and recorded. 1) Each earthing station 2) Earthing system as a whole 3) Earth continuity conductors

10.2

10.3

Earth conductor resistance for each earthed equipment shall be measured which shall not exceed 1 Ohm in each case. This is responsibility of contractor to get the final value for resistance. Measurements of earth resistance shall be carried out before earth connections are made between the earth and the object to be earthed. All tests shall be carried out in presence of the consultant.. METHOD OF MEASUREMENT: Provision of earthing station complete with excavation, plate, earth lead up to chamber, earth link in the chamber, electrode, GI watering pipe, Salt, Charcoal, soil treatment to achieve the earth resistance less than 4 ohm, masonry chamber with cast iron cover etc. shall be treated as one unit of measurement. The following items of work shall be measured and paid per unit length covering the cost of the earth wires/strips, clamps, labour etc. a) b) Main equipment earthing grid and connection to the earthing stations. Connection to the power panels, DB etc.

10.4

10.5 11.0 11.1

11.2

11.3

The cost of earthing the following items shall become part of the cost of the item itself and no separate payment for earthing shall be made. a) Light fittings - form part of installation of the light fitting. b) Conduit wiring, cabling - should form part of the wiring or cabling. c) Street lighting - should form part of the street light poles.

Sabarmati River Front Development Corporation Limited

Page 181

E-17 1.0 1.1

External Lighting Scope: The scope of work covers the supply, installation and testing of lighting poles with required foundation as per drawing complete in all respect, weather proof light fixtures, wiring to the fixtures, cable laying, earthing as specified and shown on drawings. Standards: As per Applicable standard.

2.0

3.0 3.1

Light Fixtures: The light fixture construction shall be of IP 65 die cast aluminium with a separate compartment for integral ballast equipment. The reflector shall be anodized polished aluminium. The glass refractor shall be heat resistant. Lamp holder shall be of porcelain and shall comprise of a terminal block of no hygroscopic material. The luminaries shall have integral ballast housed in water tight and dust tight metal cases. Ballast shall be pre-wired to the Lamp socket and terminal block, requiring only power supply leads to the ballast primary terminals. The Lamp & Laminar shall generally follow the specification under section `LIGHT FIXTURES'. Lighting Poles: Lighting Poles for street lights /flood lights shall be swaged type GI pole construction / GRP Poles as specified below The lighting poles shall be fabricated from heavy duty cold rolled steel tubes to IS:1239-1958 and hot dip galvanized or painted as specified. The pole shall have a base plate, a large access panel, and necessary fixture mounting bracket at top. The access panel shall provide easy access to a multi-way porcelain connector and fuse board, to be mounted inside the pole. The access shall be specially fabricated with adequate reinforcement and weather gasket to prevent ingress of moisture and vandal proof. Poles shall have large diameter entries for incoming and outgoing cable and two earth studs. The pole fabrication shall conform to the drawings and where such drawing is not available; the contractor shall make such drawing and have it approved before fabrication. It will be fixed with the foundation as shown in the drawing. The pole shall house a multi-way integral type terminal block and MCB as shown on the drawings. Pole shall have a concrete coping. Detail specifications of GLASS REINFORCED POLYMER (GRP) COMPOSITE POLE Design: The GRP Poles shall be designed to withstand the maximum wind speed as per IS 875. The Pole shall withstand top load up to 300 Kgs. Pole Shaft: The pole shaft shall be in continuously conical shape. It should be in a single piece construction.

3.2

3.3 4.0

4.1

4.2

4.3

Sabarmati River Front Development Corporation Limited

Page 182

Door opening: The GRP Poles shall have appropriate door opening fitted with integral junction box at the elevation as shown in the drawing. The door shall be vandal resistance and shall be weather proof to ensure safety of inside connections. The pole shall be adequately strengthened at the location of the door to compensate for the loss in section. Material: It should be a combination of FABRIC GLASS REINFORCED POLYMER COMPOSITES (mats, technical fabric & unsaturated polyester resins) & various RESIN matrixes. Exterior Finish: The poles shall be Externally PU treated & coated for UV stabilization. Fixing Type: The GRP Poles shall be embedded type & it will be fixed with the foundation as shown in the drawing. Physical Dimensions: Should be followed as shown in the drawing. (However the tenderer shall also specify his consideration in a separate sheet for all the physical parameters along with the tender) Standards: The GRP Poles design should comply with BSEN407:2002. Manufacturing: The GRP pole manufacturing unit shall be ISO 90012002 certified to ensure consistent quality & environmental protection. The manufacturing process should be Filament Winding & Taper Ground to absolute smooth finish with UV retarded Higloss Polyurethane Paint. 5.0 5.1 5.2 5.3 Cable laying: Cabling shall be generally as specified in the section `CABLING'. Cables shall be terminated in a 4-way terminal block inside the pole or attached therewith as shown on drawings. Cable route shall be as shown on the drawings or the contractor shall mark out the route and lay the cables only upon approval of the route. Earthing: All street lights fixtures and poles shall be earthed as specified under section `EARTHING'.

6.0 6.1

Sabarmati River Front Development Corporation Limited

Page 183

7.0 7.1

Mode of Measurement: Each light fitting with lamp, control gear, earthing etc. shall be considered as one unit for measurement and payment. Each lighting pole, concrete coping, base plate earthing etc. shall be considered as one unit for measurement and payment. All cabling work shall be measured on the basis of unit length and the cost shall include, cost of cable, cable termination in junction boxes or pole terminal box etc.

7.2 7.3

Sabarmati River Front Development Corporation Limited

Page 184

SPECIAL CONDITION FOR TESTING (CONTRACTOR TO READ THIS CAREFULLY) 1.0 SCOPE : If required contractor should have to take all necessary testing/ random testing of equipments and component prior to supply as per the guidelines / rules / sampling method etc. of IS at manufacturing works or other standard lab in presence of Clients representative & consultant as witness testing. Any deviation in parameters which is not as per IS is not accepted and client reserve the rights to reject the same at any stage of the project.

Sabarmati River Front Development Corporation Limited

Page 185

APPLICABLE STANDARDS Sr. No. 1) IS No. IS: 2026-1977 &1981 -1994 IS 3639-1966 IS10028-Part III 1981 IS: 13118-1991 : Description Power transformers fittings.

2) 3) 4)

: : :

Fittings and acc. For P.T. Installation of Transformer. Specification for High voltage AC circuit breakers. Insulating oil for Transformers & switch gear. CT for measuring and protection. Voltage (Potential) Transformers. Voltage Transformer. Bus-bar arrangement and marking Bushing Large Hollow Porcelains Insulator Insulators greater than 1000V Hot Dip Galvanizing

5) 6) 7) 8) 9) 10) 11) 12) 13)

IS: 335-1993 IS: 2705-1992 IS: 3156-1992 IS: 3156-1992 IS: 8623-Part II IS: 2099-1986 IS: 5621-1980 IS: 2544-1973 IS: 2629-1985 IS: 2633-1986 IS: 3842-1967 IS: 1248-2003 IS: 10118-1982 IS: 692-1994

: : : : : : : : :

14) 15) 16) 17)

: : : :

Relays for AC system Meters (measuring). Installation of Switch gears. HV Cable Paper Insulated Lead Sheathed Cables for Rated Voltage up to and Including 33 kV Specification. Installation of HV cables and jointing. Code of practice for earthing. HD Air breaker, Switch gears and fuses for Voltage not exceeding 1000 Volts. Selection, installation and maintenance of fuses up to 650 Volts.

18) 19) 20)

IS: 1255 -1983 IS: 3043-198 IS: 13947-Part III -1993

: : :

21)

IS: 13703-Part IV 1993

Sabarmati River Front Development Corporation Limited

Page 186

22)

IS: 13947-Part I -1993 IS: 13947-Part III -1993 IS:8623-1993

General requirements for switch gear and control gear for voltage not exceeding 1000 Volts. Air-break isolators for Voltage not exceeding 1000 Volts. Factory built assemblies of switch gears and control gears for voltage up to and including 1000 Volts A.C. and 1200 Volts D.C. Marking and arrangement of switch gear bus bars main connectors and auxiliary wiring. Cubical Boards. Insulated Bus bar rating. Enclosed distribution fuse boards and cut-outs for Voltage not exceeding 1000 Volts. Miniature Circuit Breaker. Fuse wire used in rewirable type electric fuses up to 650 Volts. PVC insulated electric cables Heavy duty. Recommended current rating for cables. Copper conductor in insulated cables and cores. Conductor for insulated electric cables and flexible cords. Low Carbon Galvanized Steel Wires, Formed Wires and Tapes for Armouring of Cables - Specification PVC insulation and sheath of electric cables. Aluminum conductor for insulated cables. Recommended current rating for Cable. Code of practice for electrical wiring installation system Voltage not exceeding 650 Volts.

23)

24)

25)

IS: 11353-1985

26) 27) 28)

IS: 13947 PART-1 IS: 8084-1976 IS: 2675-1983

: : :

29) 30)

IS: 8828-1995 IS: 9926-1981

: :

31) 32)

IS: 1554-Part I -1988 IS: 3961-Part II & IV -1967 IS: 8130-1984 IS: 8130-1984

: :

33) 34)

: :

35)

IS: 3975-1999

36) 37) 38) 39)

IS: 5831-1984 IS: 8130-1984 IS: 11955-1987 IS: 732-1989

: : : :

Sabarmati River Front Development Corporation Limited

Page 187

40)

IS: 1646-1997

Code of practice for fire safety of Buildings (general) electrical installation. Rigid steel conduits for electrical wiring. Fittings for rigid electrical wiring. steel conduits for

41) 42) 43) 44)

IS: 9537-1981 IS: 2667-1988 IS: 3480-1966 IS: 3837-1976

: : : :

Flexible steel conduit for electrical wiring. Accessories for rigid steel conduits for electrical wiring. PVC insulated cables (wires). Installation of Rigid non-metallic conduits for electrical wiring. Flexible (playable) non-metallic conduits for electrical installation. Plugs and sockets up to 250V. Conductors for insulated electrical cables and flexible codes. Specification for conduit for electrical installation. Accessories for non-metallic conduits for electrical wiring. Switches. Plugs. Shunt Capacitors for power systems up to 650V. Low voltage fuse and links up to 1000 volts. General and safety lighting fittings. requirement for

45) 46) 47)

IS: 694-1990 IS: 9537-Part III -1983 IS: 6946-1973

: : :

48) 49) 50)

IS: 1293-2005 IS: 8130-1984 IS: 9537-1980

: : :

51) 52) 53) 54)

IS: 3419-1988 IS: 3854-1997 IS: 6538-1971 IS: 13585-Part I -1998 IS: 1370 IS: 1913-1978

: : : :

55) 56)

: :

57) 58) 59) 60)

IS: 1944-1981 IS: 3528-1966 IS: 3553-1966 IS: 1239-Part I -2004 IS: 10322-Part V -1987

: : : :

Code of practice for lighting public thorough fares. Waterproof electric lighting fittings. Water tight electric lighting fitting. Mild Steel tubular and other wrought steel pipe fitting. Luminaries for street light.

61)

Sabarmati River Front Development Corporation Limited

Page 188

62) 63) 64) 65)

IS: 13703-Part III -1993 IS: 2312-1967 IS: 374-1979 IS: 7098 (Part I, II, III) -1988

: : : :

HRC fuses having rupturing capacity voltage up to 1000V. Exhaust Fan. Class I Ceiling Fan. XLPE armoured Cables up to 1000V.

NOTE:

All codes and standards means the latest where not specified otherwise the installation shall generally follow the Indian Standard codes of practice or relevant British Standard Codes of Practice in the absence of corresponding Indian Standards.

PLEASE FOLLOW: a. Indian Electricity Act of 1910 and rules issued there under revised up to date. b. Regulations for electrical equipment in building issued by The Bombay Regional Council of insurance Association of India.

Sabarmati River Front Development Corporation Limited

Page 189

LIST OF APPROVED MAKE / MANUFACTURER 1) Rigid PVC Conduit : ISI & FIA approved & manufactured from virgin material. Precision, Nihir, Polycab. Same make as of pipe FRLS type: Finolex, Polycab, Primecab. MK India (Logic), MK (Bleez), Legrand (Mosaic), Crabtree (Emerald), Toyama (Accura Plus) Cast Iron type only L&T, Siemens, Schneider

2) Accessories for conduit 3) Flexible Copper Wires 4) Switches & its accessories

: : :

5) Fan Box 6) Switch fuse Units 60 Amps - AC 23 duty 7) HRC Fuses

: :

Schneider MG, Siemens, L&T. Legrand (Lexic),Schneider MG, L&T. Legrand (lexic), Schneider MG (Multi 9), L&T. Delton, Finolex, Polycab, Primecab Steel grip, Anchor Finolex, Primecab, CCI, Avo cab Finolex, Primecab, CCI, Avo cab

8) MCCB/MCB/ELMCB/Iso & Acc : 9) Distribution Boards :

10) Telephone wires/Cable 11) PVC tape 12) LT Cables 13) Branched Cable downstream From 35 sqmm. 14) Glands

: : : :

Compression type, Heavy duty and deep threading with rubber ring and double washers. (Sample to be approved) HMI, Comet Dowels, 3-D Legrand, Indoasian Elmex, Connectwel Anchor, CPL

15) Cable Lugs 16) Industrial Plug-socket 17) Connectors 18) Button holder, Angle holder, ceiling rose

: : : :

Sabarmati River Front Development Corporation Limited

Page 190

19) M.S. Conduit ISI 20) A.C.B 21) Telephone tag block 22) Capacitor 23) Relay(Numerical) 24) Relay(Auxiliary) 25) APFC Relay 26) Meter (DIGITAL ENERGY METERS) 27) Light Fixture

: : : : : : :

BEC, Steel Craft, AKG Schneider MG, L&T Krone L&T Mehar, EPCOS, Conzerv Areva, Siemens, ABB, Schneider ABB, AREVA, Schneider Conzerv, L&T, ElMeasure, HPL

: :

Secure, L&T, ElMeasure, HPL Phillips, Keselec, Bajaj, Crompton, Wipro / equi. (Sample to be approved) Crompton, Usha Crompton, Usha, Almonard Anchor Ding Dong type. Voltamp, Crompton Indiana, Power Control Finolex, Polycab, RPG, Universal

28) Ceiling Fans 29) Exhaust Fan 30) Call bell 31) Dry type transformer 32) Cable Tray 33) TV Cable 34) Panel Fabricators (Metallic) :

: : : : :

CPRI approved vendors only Hensel, Schneider, Spelsberg.

34a) Panel Fabricators (Thermoplastic): 35) Load Manager Power meter/MFM 36) Anchor Fasters 37) On Load Changeover 38) Fire Extinguisher : : :

Conzerv, L&T, ElMeasure, HPL Hilti or equivalent Havells, L&T, Schneider, HPL Should be of Safex, Firex, Safeline ISI approved

39) Meters (V, A, PF etc)

IMP, AE, RISHABH, ElMeasure, HPL

Sabarmati River Front Development Corporation Limited

Page 191

40) Timer 41) Raceway 42) Data Wire / Cable, I/O

: : :

Theban (Indoasian), Legrand, Schneider MK (Ega), Legrand Systemex, Avya

43) High Mast High Mast Shaft & Accessories : Luminaries :

Bajaj, Crompton, BPP Bajaj, Phillips, Crompton, Schreder Bajaj, Sumip, Wipro, / equi. KAPPA/ AE / Pragati Rex, Dutron, equi Ashlok, Universal, Errico, LPI CMS, Nucleonics, Swarco, Bajaj. Finolex, Primecab, Lapp Cables

Keselec-

44) GRP Poles 45) LT CT

: : : : : :

46) DWC Pipes 47) Electrode type Earthing 48) Traffic Signal System 49) Control Cables

Special Notes : The successful tenderer will have to supply the makes from above in consultation with the Client / Architect / Consultant without any extra cost. The tenderer should have to submit considered makes from the above list along with the tender with covering letter of separate letter enclosure. However, the final decision for accepting make specified by tenderer would be of client / Architect / Consultants. As far as possible, the successful tenderer will have to place order directly to the manufacturer OR its authorized dealer. The Client/Architect/Consultants have right to check the challans of supplier. The MCB and MCB DBs must be of same make. Make of components required to be used by contractor to complete the installation, if not mentioned any where, shall be required to GOT IT APPROVED by Client/Architect/Consultant before installation in writing manner. Within a week of work order, the contractor shall submit the sample of each item / component of above mentioned approved make for the approval of the Client/Architect/Consultant.

You might also like