0% found this document useful (0 votes)
392 views1 page

132 Testing - CT

This field test report summarizes test results for current transformers (CTs) in the 132/33 kV transformer bay at Lamki substation. Key details include: CT manufacturer is Mehru Electrical and Mechanical Engineers (P) Ltd. Accuracy class is 5P 20 and PS for protection, 0.5 for metering. General inspection found wiring, equipment structure, and earthing to be satisfactory with proper ratio selection and short circuited spare cores. Insulation resistance and current ratio tests were performed on the R, Y, and B phases and results were within acceptable limits.

Uploaded by

Santosh Gairhe
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
392 views1 page

132 Testing - CT

This field test report summarizes test results for current transformers (CTs) in the 132/33 kV transformer bay at Lamki substation. Key details include: CT manufacturer is Mehru Electrical and Mechanical Engineers (P) Ltd. Accuracy class is 5P 20 and PS for protection, 0.5 for metering. General inspection found wiring, equipment structure, and earthing to be satisfactory with proper ratio selection and short circuited spare cores. Insulation resistance and current ratio tests were performed on the R, Y, and B phases and results were within acceptable limits.

Uploaded by

Santosh Gairhe
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 1

132/33 kV Transformer Bay at Lamki S/S

FIELD TEST REPORT OF CURRENT TRANSFORMER Test Date:

1. Equipment Detail
Equipment Circuit Position Manufacturer Serial No. : : : R Phase : Y Phase : B Phase : : 132kV CT 132/33 kV Transformer Bay Mehru Electrical and Mechanical Engineers (P) Ltd

Accuracy Class

5P 20 and PS for Protection, 0.5 for Metering,

1.1 General check


SN 1 2 3 4 5 6 Test Items Inspection Secondary Wiring Tightness Equipment and Structure Earthing Results Remarks

Ratio Selection Spare Core


Polarity Oil leakage Oil Level

As per NEA requirement All spare core are short circuited

Between Min and Max position

1.2 Insulation Resistance Test


Phase Connection R Y B P E P E P E IR Value (5000V) M Result

1.3 Current Ratio Test Phase Ratio Primary Inject Current C1 600/1 800/1 50/1 100/1 200/1 C1 Y 600/1 800/1 50/1 100/1 200/1 C1 B 600/1 800/1 50/1 100/1 200/1 C2 C2 C2

Core C3 C4 C5

C3

C4

C5

C3

C4

C5

Field Test Report of 132 kV CT