ICM 175 Bypass Timer

This document provides information about a bypass timer that can be used for low pressure switch bypass and low ambient startups. The timer has an adjustable delay period from 10 to 1,000 seconds. When power is applied, the load is energized for the set time delay period regardless of the state of the pressure switch. After the delay, the pressure switch controls the load. Power must be removed during or after the delay to reset the timer.

Uploaded by

Ray Ravel
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
966 views

ICM 175 Bypass Timer

This document provides information about a bypass timer that can be used for low pressure switch bypass and low ambient startups. The timer has an adjustable delay period from 10 to 1,000 seconds. When power is applied, the load is energized for the set time delay period regardless of the state of the pressure switch. After the delay, the pressure switch controls the load. Power must be removed during or after the delay to reset the timer.

Uploaded by

Ray Ravel
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Low Pressure Switch Bypass, Low Ambient Startups, 18-240 VAC

Knob adjustable from 10-1,000 seconds Ideal for winterstart kits MODE OF OPERATION
When power is applied to the input, regardless of the state of the pressure switch, the load is energized and timing begins. After the timing delay is complete, the pressure switch will control the load. The control is reset by removing power during or after the time delay.

BYPASS TIMER

ICM 175

INSTALLATION
1. Disconnect power. 2. Connect terminals as shown in the wiring diagram below. 3. Select the desired time delay. 4. Reapply power, check operation.

SPECIFICATIONS
Input Voltage: 18-240 VAC Frequency: 50-60 Hz Output Output Ratings: Maximum: 1 amp Minimum: 40 mA Inrush: 10 amps Time Delay 10-1,000 seconds

TIMING DIAGRAM
Input Voltage

0V
Load Voltage

Time

Time Delay Load Energized


Time

WIRING DIAGRAM
Input 18-240 VAC

Load

ICM CONTROLS
www.icmcontrols.com

7313 William Barry Blvd. North Syracuse, NY 13212

800.365.5525
LII271-1