Per Unit Quantities
Per Unit Quantities
100 V
1 V /_00
SO ZPU=RPU+J(XLPU-XCPU)=0.15+J(0.4-0.2)=0.25 /_53.130
IPU=VPU/ZPU=1/0.25=4.0/_-53.130 SO ACTUAL CURRENT WILL BE IACT=IB*IPU=5 * 4.0/_-53.130 =20 /_-53.130
N1
N2
ZEQ1PU=ZEQ1 * MVAB/KVB2 ZEQ1= TOTAL IMPEDANCE OF THE TRANSFORMER REFERED TO PRIMARY SIDE IN OHMS MVAB=RATE DMVA OF TRANSFORMER KVB=RATED VOLTAGE OF TRANSFORMER ON PRIMARY SIDE IN KV
B
66KV LINE D/C DOG ,7.5 KM, 0.492 /KM
C
15MVA 66/11 TR 1, %Z =9.821 15MVA 66/11 TR 2, %Z =10.09
LINE
FAULT
11KV BUS
A
Zs=0.1972
ZTEQ=0.7193
C
ZTEQ=3.318
220KV BUS
66KV BUS
66KV BUS
FAULT
11KV BUS
NOW MVASC=MVAB/ZPU=1000/(0.1972+0.7193+0.4236+3.318)=214.68MVA SO 11KV BUS FAULT LEVEL IN MVA = 214.68MVA AND IN KA=214.68/(1.73*11)=11.27KA
132kv Bus
FL=2550 MVA,11.15 KA
132kv Bus C
262 A FL=1813.15 MVA,7.93KA
218.7 A
437.4 A
262 A
66kv Bus D
FL=739.65 MVA,6.47KA
66kv Bus E
FL=402.90 MVA,3.53KA 87.5 A
500 A
11kv Bus
FL=181.42 MVA,9.52KA
% Imp. Of 100 MVA 220/132kv Transformer = ZT1 = 9.21 (Base MVA is100) % Imp. Of 50 MVA 220/132kv Transformer = ZT2 (Base MVA is 100) = 100*10.50 / 50 =21 Equi. Impedance ZTeq = ZT1*ZT2 / (ZT1+ZT2) = 9.21*21 / (9.21+21) = 6.40 FL of 220kv Bus C = Base MVA *100 / (Zs+ ZTeq) = 100*100 /(2+6.40) = 1190.48 MVA.....................................(1)
Z of line = Base MVA * Z * Line Length *100/(KV*KV ) = 100*0.423*50*100/(132*132) = 12.14 FL of 132kv Bus C = Base MVA *100 / (Zs+ Zline) = 100*100 /(3.92+12.14) = 622.67 MVA .....................................(2) Total Fault Level of 132 kv Bus C =(1) + (2) =1190.48+622.67 =1813.15 MVA ,7.93 KA
% Imp. Of 50 MVA 132/66kv Transformer = ZT1 (Base MVA is 100) = 100*8 / 50 =16 ZT2 is also 16 Equi. Impedance ZTeq = ZT1*ZT2 / (ZT1+ZT2) = 16*16 / (16+16) =8 FL of 66kv Bus D = Base MVA *100 / (Zs+ ZTeq) = 100*100 /(5.52+8) = 739.65 MVA , 6.47 KA
1/ZTeq. =(1/ZT1 +1/ZT2+1/ZT3) =(1/90 +1/93+1/95) =0.033 ZTeq. = 1/0.033 =30.30 FL of 11 kv Bus E = Base MVA *100 / (Zs+ ZT eq.) = 100*100 / (24.82+30.30) = 181.42 MVA , 9.52 KA