ATTMA TSL2 Issue 1 PDF
ATTMA TSL2 Issue 1 PDF
v bar
p p
3
Where:
( ) | |
)
`
+ |
.
|
\
|
+
=
15 . 273 ln 02802 . 5
15 . 273
4985 . 6790
484085 . 59 u
u
e p
v
and, can be taken as 0.5 (i.e. 50% relative humidity)
A.1.3 Correction for actual and observed airflow through the measuring device
The actual flow rate through the fan is a function of the measured values at the last fan
calibration and measured values during the air test.
m
c
c m
Q Q
= 4
Where Q
m
is the actual volumetric flow rate through the fan during the test, Q
c
is the
airflow rate from the last calibration of the fan,
m
is the density of air passing through
the fan (kg/m
3
) and
c
is the air density recorded during fan calibration.
A.1.4 Correction for internal/external air density differences
A correction is required for the internal/external density differences between air
passing through the airflow measuring device and air passing through the building
envelope. The correction to be applied depends on whether the building is being
pressurised or depressurised.
Technical Standard L2 Issue 1 Page 25 of 32 30/09/10
www.attma.org
A.1.4.1 Corrections to airflow rate for pressurisation tests:
Convert the measured airflow rate, Q
m
, to airflow through the building envelope,
Q
env(out)
, for pressurisation using equation 5:
i
e
m ) out ( env
Q Q
= 5
where Q
env(out)
is the actual air flow volume out through the envelope,
e
is the mean
external air density (kg.m
-3
) and
i
is the mean internal
air density (kg.m
-3
).
A.1.4.2 Corrections to airflow rate for depressurisation tests:
Convert the measured airflow rate, Q
m
, to airflow through the building envelope,
Q
env(in)
, for depressurisation using equation 6:
e
i
m ) in ( env
Q Q
= 6
where Q
env(in)
is the actual air flow volume in through the envelope,
e
is the mean
external air density (kg/m
3
) and
i
is the mean internal
air density (kg/m
3
).
A.1.5 Determination of constants C and n using a least squares technique
The results from a steady state building test will give a dataset comprising of building
differential pressures (Ap
env
) and corresponding fan flow rates (Q
m
). There are a
number of curve fitting approximations available to produce a best-fit line between
these points. The most straightforward of these is the least squares approximation.
Equation 1 is rearranged by taking the logarithm of each side to form an equation for a
straight line:
y = mx + b
where y = ln(Q
m
)
and x = ln(Ap
env
)
The points recorded are fitted through the points (x
1
, y
1
),.,(x
i
, y
i
) so that the sum of
the squares of the distances of those points from the straight line is minimum. The
airflow rates and corresponding pressure differences are plotted on a log-log graph for
pressurisation and depressurisation as required.
Technical Standard L2 Issue 1 Page 26 of 32 30/09/10
www.attma.org
The calculation of the factors m and b for a given (de)pressurisation test are as
follows:-
| | | | ( )
=
m env
Q ln p ln XY d A 7
| | | | ( )
=
env env
p ln p ln XX d A A 8
| | | |) ln (ln
m m
Q Q YY d =
9
| |
=
env
p ln X d A 10
| |
=
m
Q ln Y d 11
( ) ( )
( ) ( )
=
XX d i X d X d
XY d i Y d X d
m 12
where i = number of data points
( ) ( )
( ) ( )
=
XX d i X d X d
Y d XX d XY d X d
b 13
from this the air flow coefficient, C
env
, and air flow exponent, n, are obtained:
b
env
e C = 14
and
n m = 15
A.1.6 Correction of airflow rates through the building envelope to standard
temperature and pressure
The relationship is established between volumetric flow rate through the fan and the
induced building envelope pressure difference:
n
env env env
p C Q A = 16
where Q
env
is the air flow rate through the building envelope (m.h
-1
) and Ap
env
is the
induced pressure difference, in Pascals.
The air leakage coefficient, C
L
, is obtained by correcting the air flow coefficient, C
env
,
to standard conditions (i.e. 20 C and 101,325 Pa).
Technical Standard L2 Issue 1 Page 27 of 32 30/09/10
www.attma.org
For pressurisation use equation:
n
s
i
env L
C C
|
|
.
|
\
|
=
1
17
For depressurisation use equation:
n
s
e
env L
C C
|
|
.
|
\
|
=
1
18
where
i
is the internal air density (kg.m
-3
),
e
is the external air density (kg.m
-3
), and
s
is the air density at standard conditions (kg.m
-3
)
The air leakage rate,
env
p
Q
A
, for a given building differential pressure, Ap
env
, can be
calculated using equation:
( )
n
env L p
p C Q
env
A =
A
19
where C
L
is the air leakage coefficient, in m
3
.h
-1
.Pa
-n
, Ap
env
is the induced pressure
difference (Pa) and n is the air flow exponent.
A.1.7 Air permeability
The air permeability, AP
50
, is the air leakage rate at a pressure difference of 50 Pa,
divided by the building envelope area A
E
(m). Units are m.h
-1
per m of envelope
area. The air permeability is calculated using equation 20:
E
A
Q
AP
50
50
= 20
Where
n
L
C Q 50
50
= , from equation 19.
A.1.8 Air change rate
The air change rate, n
50
, is the air leakage rate at a pressure difference of 50 Pa,
divided by the building volume V (m). It defines the length of time required to
completely change the volume of air within the building, and has the units 1/h. The air
change is calculated using equation 21:
V
Q
n
50
50
= 21
Where
n
L
C Q 50
50
= , from equation 19.
Technical Standard L2 Issue 1 Page 28 of 32 30/09/10
www.attma.org
A.1.9 Correlation coefficient (r)
The correlation coefficient (r) is a measure of the strength of association between the
observed values of building differential pressure (A
env
) and corresponding fan flow
rates.
2
o
xy
S
r = 22
where
( ) ( ) | | ( ) ( ) | |
= Y d Y d YY d i X d X d XX d i
2
o
( ) ( )
= Y d X d XY d i S
xy
A.2.0 Essential parameters (r
2
and n)
Assessment of building airtightness using a steady state technique relies on the
premise that an equal pressure difference is maintained across the whole of the
building envelope. It is also paramount that no changes occur to the envelope, such as
removal of temporary sealing or opening an external door during the test. Two
parameters are used as indicators of the accuracy and validity of test results.
A.2.1 Correlation coefficient (r
2
)
The correlation coefficient, or r
2
, is indicative of the accuracy with which a curve fitting
equation can be applied to a set of results. For a building pressurisation test with a
minimum of seven building envelope readings typically taken in the range 20 to 100
Pa, an r value of greater than 0.980 must be obtained. Test results that do not attain
this minimum standard figure should be declared not valid and may be due to adverse
environmental conditions or substandard test and data collection techniques.
A.2.2 Air flow exponent (n)
The fortuitous air leakage paths through a building envelope under test will consist of a
number of cracks and holes of varying shapes and size. The constants C and n are
derived from the power law relationship. The air flow exponent, n, is used to describe
the airflow regime through this orifice. Values should range between 0.5 and 1.0. If the
value of n is not within these limits, then the test is not valid and should be repeated.
For information, n values which approach 0.5 will have fully developed turbulent flow
through the building elements and represents air flow through rather large apertures,
which tend to be indicative of rather leaky structures. For n values which approach 1.0,
will indicate a more laminar like flow through the building elements and generally
represent very tight structures, or those with a myriad of very tiny holes.
Technical Standard L2 Issue 1 Page 29 of 32 30/09/10
www.attma.org
A.3.0 Limiting factors
A.3.1 Static pressures within tall buildings
Buildings with large internal/external temperature differences are subject to stack
pressures. These may be more pronounced in tall buildings. If the product of the
temperature differential across the building envelope (T), multiplied by the building
height (m) is greater than 250 mC, it is likely that the stack pressure is too great to
maintain an equal pressure difference across the whole of the building envelope.
A.3.2 Uniform pressures across the building envelope
In multi cellular buildings all internal doors should be opened, so that a uniform
pressure is maintained across the whole of the building envelope. This may entail
using a number of fans strategically located in various doorways or other openings
around the envelope. Readings should be taken as outlined in section 3.5
A.3.3 Zero-flow pressure differences
Temporarily sealing is applied to the fan(s) at the start and end of the test. Readings
for building differential pressures are recorded at zero airflow rate through the fan(s). If
the average of the zero-flow pressure differences at the start or end of the test
exceeds 5 Pa the influence of wind and/or stack pressures are too great for a valid
set of readings to be obtained.
A.3.4 Minimum acceptable building differential pressures
The building differential pressures induced during an air test should be greater than
those occurring naturally to minimise the influence of wind and stack effects. A
maximum pressure of at least 50 Pa must be established across the envelope, with
readings typically taken up to between 60 and 100 Pascals. Higher building pressures
may result in more accurate data in some instances. However, differential pressures
above 100 Pa may result in the deformation of envelope components and must
therefore be avoided. No readings should be recorded below 10 Pa, or five times the
zero flow pressure difference, whichever is greater.
In exceptional circumstances, e.g. when a building is unexpectedly leaky, it may not
be possible to achieve a pressure difference of 50 Pa. In these cases, the failure to
attain 50 Pa must be stated in the report, with an account of the reasons why.
Readings taken at low pressures will be more adversely affected by environmental
conditions and any conclusions drawn from such a report should be treated with
caution.
Technical Standard L2 Issue 1 Page 30 of 32 30/09/10
www.attma.org
Appendix B - Test Equipment Requirements
B.1.0 Introduction
The requirements of ATTMA for the accuracy of measurements are based primarily
around the BS EN Standard 13829:2001 - Thermal Performance of Buildings -
Determination of air permeability of buildings - Fan pressurisation method with
enhancements recommended by ATTMA.
All instrumentation, whatever the required tolerance, needs to satisfy the annual
calibration requirements of UKAS. UKAS Certification is a mandatory requirement for
all ATTMA members.
B.2.0 Accuracy
The following is a list of the required measurements and tolerances:
B.2.1 Pressure Differential Measurement (micromanometer)
An instrument capable of measuring pressure differentials with an accuracy of 2
Pascals in the range of 0 to 100 Pascals.
B.2.2 Air Flow Rate Measurement
The device must have a UKAS accredited calibration and measure the air flow rate to
within 7% of the reading. The reading of the air flow rate shall be corrected according
to air density. Care should be taken when choosing a measurement system that the
system is relatively unaffected by irregular air entry conditions (wind velocities and
local obstructions) and that there is stability in the measurement system. Where
multiple fans and measurement systems are to be used in unison then the calibration
of all individual units need to be verified and UKAS accredited.
B.2.3 Temperature Measurement devices
The accuracy of temperature measurement must have an accuracy of 1C within the
range of -20 C to + 40 C .
B.2.4 Barometric Pressure
A barometer should have an accuracy of 5 mbar in the range 950 - 1050 mbar. The
barometer is used for correcting air flow rates and has a small effect on the
measurement accuracy.
B.3.0 Calibration
Care will need to be taken in the choice of an air flow measurement system to avoid
inaccuracies induced by wind effects on the flow measurement device. The proximity
of local obstructions can cause inaccuracies but more particularly the proximity of two
flow measurement devices, as can be found with two or more blower door type fans.
Technical Standard L2 Issue 1 Page 31 of 32 30/09/10
www.attma.org
The flow measurement device will require to be calibrated against a recognised test
procedure. Such test procedures will have to satisfy UKAS requirements and two
standards are worthy of reference. The first is BS ISO 3966:2008 Measurement of
fluid flow in closed conduits. Velocity area method using Pitot static tubes and the
second is BS 848-1:2007 (BS EN ISO 5801:2008) Industrial fans. Performance
testing using standardized airways.
It will also be a UKAS requirement and by extension an ATTMA requirement to
calculate estimates of uncertainties for not only the individual parameters but also a
final uncertainty budget from the square root of the sum of the squares of the standard
deviation of each source of uncertainty.
Technical Standard L2 Issue 1 Page 32 of 32 30/09/10
www.attma.org
Appendix C - Equivalent Leakage Area (ELA)
It is often useful for the test engineer to translate the results of an air leakage test in to
a more readily understandable form such as an equivalent leakage area, A (m). Area
of holes left in the structure can be a useful guide, but it is only an aerodynamic
equivalent area based on a sharp edged orifice and should therefore be regarded as
approximate.
The flow rate of air can be expressed by:
n
s
env
d p
p
A C Q
env |
|
.
|
\
| A
=
A
2
23
Where:
The discharge coefficient, C
d
for a sharp edged orifice can be taken as 0.61, standard
air density
s
is taken as 1.20kg.m
-2
, n can be taken as 0.5, the test pressure is 50
Pascals, and
50
Q is in m/s, which allows equation to be simplified and rearranged to:
57 5
50
.
Q
A = 24
Most buildings do not exhibit a flow index (n) of 0.5 because the air leakage paths can
be long and convoluted, etc. and as such the above equation is only approximate.
The above should be treated with extreme caution since holes in buildings tend to
look considerably larger than they actually are, since the other side of the hole may
have a tortuous exit route or be occluded by a hidden membrane.
The equivalent leakage area should only be used as a guide for remedial measures
and not to determine the final air permeability value.