TheMaintGuide Fieldcomm
TheMaintGuide Fieldcomm
98
93
Field commuincation
Basics
HART is a point to point protocol (see fig.1): a PC talks to a single instrument (or to several instruments via a multiplexer). Conversely, Foudation Fieldbus and Profibus fit for the data exchange to a programmable logic controller (PLC) or a process control system (PCS). Since Foudation Fieldbus and Profibus use the same electric signal and encoding - only the
protocol differs -, the low level maintenance is identical in both networks. Profibus DP/PA typical architecture (Fig. 2) The process is controlled by a process control system or a programmable logic controller (PLC). The control system or PLC serves as a Class 1 master. It uses the cyclic services to acquire measurements and
output control commands. The asset management program, e.g. FieldCare, serves as a Class 2 master. It uses the acyclic services and serves to parametrize the bus participants during installation and normal operation. The PROFIBUS DP system is used to handle the communication at the control level. Drives, remote I/Os etc. may all be found upon the bus. It is also possible to connect externally powered field devices to this level, e.g. the flowmeters Promass and Promag. PROFIBUS DP ensures that data are quickly exchanged, whereby in mixed PROFIBUS DP/PA systems the baudrate supported by the segment coupler is often the limiting factor.
PROFIBUS PA is used at field level. The segment coupler serves both as interface to the PROFIBUS-DP system and as power supply for the PROFIBUS PA field devices. Depending upon the type of segment coupler, the PROFIBUS PA segment can be installed in safe or hazardous areas. Foundation Fieldbus typical architecture (Fig. 3) The Foundation Fieldbus system architecture has been designed to promote interoperability between and among devices of different manufacturers. Since Foundation Fieldbus supports both a high speed and low speed (H1) network, two architectures exist. These provide the same basic functionality but differ in
PLC
PLC
e.g. PROFIBUS DP e.g. PROFIBUS DP Remote I/O 420 mA HART PLC + HART interface 420 mA HART HART Multidrop (up to 15 devices) Ethernet
420 mA HART
420 mA HART
FOUNDATION Fieldbus H1
4x
4x
FOUNDATION Fieldbus H1
94
the communication stack. The H1 layer is IEC 61158-2 based and the high speed layer uses High Speed Ethernet (HSE). Installation instructions Cabling and termination are at the origin of most reported problems. Cabling When installing a PROFIBUS network, particular attention must be paid to the cabling. This covers both choice of cabling, and the way in which the cables are laid in the plant. Thus by careful routing, e.g. avoidance of potential sources of intense electromagnetic interference, use of metal trays or separation of power and bus cables in the cable tray, a significant contribution can sometimes be made to the faultfree running of the bus. Note: never use Profibus DP cables for cabling PA devices and vice versa. Termination The start and end of every PROFIBUS PA segment must be fitted with a bus terminator. For non- hazardous areas, some T-boxes have an integrated terminating element that can be switched in when required. If this is not the case, a separate terminator must be used. The segment coupler at the beginning of the segment has a built in terminator. The terminator in the T-box at the end of the segment must be switched in, or a separate terminator must be used.
T-boxes with switchable terminators may not be used in explosion hazardous areas. The terminator requires the corresponding FISCO approval and is a separate unit. For a segment with a tree architecture, the bus ends at the device that is the furthest from the segment coupler. If the bus is extended by the use of a repeater, then the extension must also be terminated at both ends. The beginning and end of the PROFIBUS DP segment must also be terminated. The terminating resistors are already built into most of the connectors on the market and must only be switched in. Note: branch lines are allowed in Profibus PA segments but not in Profibus DP segments. Set-up Device Parametrization using FieldCare Asset Management FieldCare is Endress+Hausers FDT based Plant Asset Management Tool. It can configure all intelligent field devices in your plant and supports you in managing them. By using status information, it also provides a simple but effective means of checking their health. FieldCare supports Ethernet, HART, PROFIBUS, and in future FOUNDATION Fieldbus etc. FieldCare ensures that devices can be integrated and configured quickly and easily, with the transparency demanded by good manufacturing practice.
PLC FieldCare
Commubox FXA191/195
270
EX
A
Transmitter powersupply unit, e.g. RMA422 or RN221N (with communication resistor)
HELP
EX
Measured Value
64.50
352 mbar 0 C
SAVE
Page Up
Bksp
Delete
Page On
FXA191/195 or DXR375
PQRS
TUV
,()
_<>
+*/
375
FIELD COMMUNICATOR
Operations and Maintenance HART devices As the HART signal modulates the 4-20 mA current, if the latter operates, the former should also operate. You just need to check the presence of the current with a multimeter. By using a Commubox FXA191/195 (see fig. 4), you should see the instrument from FieldCare, otherwise there is a problem with the cabling. Profibus network See diagnosis on next page.
Re-engineering When adding fieldbus networks to an existing installation, consider exchanging basic remote I/O devices with smart I/O devices thus allowing centralized access to HART devices. Also consider using the FXA720 gateway to link Profibus networks to Ethernet networks. Take care of the maximum output current supplied by the segment coupler when adding a new device otherwise the segment might fail.
Our Solutions teams can help you from the start of your revamping project. Please contact us.
95
Field commuincation
Off
On
Field commuincation
Do I use the correct GSD* file? Enable Set unit to bus at the device to ensure correct scaling Is the decoding correct at the PLC?
* The PROFIBUS system requires a description of the device parameters, e.g. output data, input data, data format and supported transmission rate, so that it can integrate the field devices into the bus system. These data are contained in a PROFIBUS device description file (GSD file) which is placed at the disposal of the PROFIBUS-DP master when the communication system is being commissioned. Device bitmaps, which appear as symbols in the network tree, can also be integrated. See Chapter 7-2 of BA034S
96
No connection between the PLC and the PROFIBUS PA network. The bus parameters and baudrate were not set when the PLC was configured. The baudrate to be set depends upon the segment coupler used (Chapter 7-5 of BA034S). - Pepperl+Fuchs SK1: 93,75 kBit/s - Siemens: 45.45 kBit/s - PA-link (Siemens IM 153/157): freely selectable - Pepperl+Fuchs SK1: 93.75 kBit/s - Pepperl+Fuchs SK2 and SK3: freely selectable For Pepperl+Fuchs SK2 and SK3, the PROFIBUS PA GSD has not been converted The bus parameters require adjustment The polarity of the PROFIBUS-DP line is reversed (A and B)? PROFIBUS-DP bus not terminated? Both the beginning and the end of the bus must be terminated. Data transmission on Profibus networks How are data transferred to the PLC? The measured values are transmitted in 5 byte long data blocks. 4 bytes are used to transmit the measured value. The fifth byte contains standardised status information. Error codes for Endress+Hauser device faults, e.g. E 641, are not transmitted with the status. For limit switches, the information is transmitted in two bytes: Signal condition and status information. How can the PLC switch on the positive zero return of the Promag 53? Via the output word of the cyclic services. How can the totaliser of the Promag 53 / Promass 83 be reset? Via the output word of the cyclic services for the totaliser in question, see corresponding operating manual. How can I suppress a measured value in cyclic communication? By using the placeholder EMPTY_MODULE or FREE_PLACE during configuration. How can I write a value to the local display? By using the Display_Value model from the GSD (if supported). General note: You can refer to Chapters 7.2 and 7.3 of BA034S (Profibus) for more details.
FieldCare cannot open connection to the PROFIBUS PA devices FieldCare is a Class 2 master that allows the transmission of acyclic values. The PROFIBUS-DP baudrate to be set depends upon the segment coupler used. The connection to the devices cannot be opened. If the PLC and FieldCare are used in parallel, the bus parameters must be mutually compatible. The bus parameters must be identical for all connected masters. If FieldCare is used, the Token Rotation Time (TTR) calculated by the PLC configuration tool must be increased by 20 000 bit times and the corresponding value entered in the FieldCare Profibus configuration and in the PLC. The HSA parameter (Highest Station Address) must permit the FieldCare address. The HSA specifies the highest address permitted for active participants (masters) on the bus. Slaves can have a higher address. Is the FieldCare address free or is it being used by another device? Is the correct baudrate set? Have the drivers and cards been correctly installed? Is the green LED on the TAP of the Proficard or Profiboard lit? Is the GAP update to high (the result is longer waiting times)? A device does not appear in the live list. Device is not connected to segment. Address used twice. Device cannot be fully operated. The device version is not supported by FieldCare. An appropiate DTM is necessary. The default parameters of the PROFIBUS-PA profile are offered. A change of unit at the device has no effect on the value on the bus. If the measured value at the device display is to be the same as that transmitted to the PLC, the parameters PV_SCALE and OUT_ SCALE must be matched. - OUT_SCALE_MIN = PV_SCALE_MIN - OUT_SCALE_MAX = PV_SCALE_MAX See the device operating instructions.
97
Field commuincation
FieldCare
Field commuincation
Commubox FXA191 is an intrinsically safe interface for Smart transmitters. It converts INTENSOR and HART protocols to RS-232 signals.
The Commubox FXA191 connects intrinsically safe Smart transmitters with INTENSOR or HART protocol to the serial port of a PC. This allows the transmitters to be remotely configured using for example the Endress+Hauser Commuwin II operating programme. The Commubox FXA 191 is powered over the serial port. If the computer, e.g. a notebook or laptop, is unable to supply enough power, the Commubox can be supplied with an external power pack.
The USB HART interface makes it possible to connect SMART transmitters with HART protocol to the USB port of a PC. The Commubox FXA193 connects all the Endress+Hauser transmitters with a service plug to the serial port of a PC. For example its easy to configure and service the PROline series flowmeters with the FieldTool software or the Micropilot M with ToF Tool / Fieldtool (see page 80). Main advantages: Simple connection of HART and INTENSOR transmitters to the serial port of a PC Intrinsically safe input (FXA191) Connection of HART transmitters to the USB port of a PC (USB HART interface) Connection of the Endress+Hauser transmitters to a PC by means of the Service plug in the connection housing of the instrument (FXA193)
Technical data Commubox FXA191 Power supply Either from RS232 port or external power pack (accessory) Electrical connection 9 pin DIN female connector for computer; 4 mm plug terminals for transmitter, polarity protected, supply (optional): clutch socket, 9VAC / VDC, polarity protected Intrinsic safety [EEX ia] IIC BVS 95.D.2060X for connection to intrinsically safe circuits EEx IIC with voltages up to 30V Operating range -20 C...+50 C Storage -40 C...85 C Humidity 0 %...95 % (no condensation) Dimensions Housing 143 x 60 x 30 mm with plastic housing for industrial use
How to order this tool: Refer to the price lists in the insert The Maintenance Store attached to this Maintenance Guide.
Typical application of Commubox FXA193: connection to the service plug in the connection housing of a Micropilot
98
Fieldgate FXA520 enables remote monitoring, diagnosis and configuration of connected HART field instruments (sensors/ actuators) by telephone lines (analogue), Ethernet TCP/IP or mobile communications (GSM). The measured data is webcompatible (http, html) and can therefore be displayed in your web browser without additional software. Fieldgate FXA520 has many possibilities from remote maintenance to inventory management (VMI).
Main advantages Worldwide access to measuring points with HART protocol via the Internet Simple configuration with web browsers without additional software Visualisation of all sensor data Remote monitoring, diagnosis and configuration Uses standard Internet protocols (http, html)
Event message via e-mail and SMS Efficient employment of standby and maintenance staff The Fieldgate FXA520 has standard two channels for HART devices and two channels for analogue inputs 4...20 mA (use of multiplexers is possible up to 30 channels) DAT module for configuration data backup
Avoid on-site service operations by using remote monitoring, diagnosis and configuration:
How to order this tool: Refer to the price lists in the insert The Maintenance Store attached to this Maintenance Guide.
99
Field commuincation