Example of Calculations For Open Conductor Fault in Power System

Two conductors of the line between buses 4 and 5 are open. The sequence impedance and voltage drop calculations are performed. The fault currents and bus voltages during the fault are determined. The phase currents in the faulted line are also calculated.

Uploaded by

bajrica
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
93 views6 pages

Example of Calculations For Open Conductor Fault in Power System

Two conductors of the line between buses 4 and 5 are open. The sequence impedance and voltage drop calculations are performed. The fault currents and bus voltages during the fault are determined. The phase currents in the faulted line are also calculated.

Uploaded by

bajrica
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

4.

14

Example of calculations for open conductor fault in


power system:

The power system described in Fig. 4.67 is considered again.


The prefault bus voltages for buses 3, 4 and 5 are :

V (0) 0.9165 8.7580

V4 (0) = 0.9152 10.0980 pu

V5 (0) 0.8858 12.9610

ONE CONDUCTOR OPEN


Let one conductor of line 7 between buses 4 and 5 be open. The pre-fault current in phase a of
(0)
(1)
the faulted line is I45 = (0.3821 j0.3779) pu. The sequence impedance matrices [Z
Bus ], [ZBus ]
(2)
and [Z
Bus ] are same as used in the example for calculation of short circuit faults on the power
system of Fig. 4.67.
The Thevenins impedance of the network as seen from buses 4 and 5 is calculated using equation
(4.145) with i=4 and i=5 as:
(1)
(1)
(1)
(1)
Zth,45
= Z44
+ Z55
2Z45
= j0.1397 + j0.1750 2 0.1250 = j0.0647 pu

(2)
(1)
Zth,45
= Zth,45
= j0.0647 pu

(0)
(0)
(0)
(0)
Zth,45
= Z44
+ Z55
2Z45
= j0.30 + j0.30 2 0.20 = j0.20 pu
(1)

(2)

(0)

, Z andZ are calculated from equation (4.147) and equation (4.148).


Next,Z
kk
kk
kk
(1) 2
(
z45
)
(j0.1)2
(1)

Zkk = (1)
=
= j0.2833 pu
(1)
j0.0647 j0.10
Zth,45 z45
(2)
(1)
Zkk
= Zkk = j0.2833 pu
(0) 2
(
z45
)
(j0.30)2
(0)

Zkk = (0)
=
= j0.90 pu
(0)
j0.20 j0.30
Zth,45 z45
(1)
The current Ia is calculated using equation (4.157)

Ia(1) = Iij

(1) (2)
(0)
Zkk
[Zkk + Zkk ]
Z (0) Z (1) + Z (1) Z (2) + Z (2) Z (0)
kk

Ia(1) = (0.3821 j0.3779)

kk

kk

kk

kk

kk

j0.2833(j0.2833 + j0.3)
= (0.2170 j0.2146) pu
j0.9 j0.2833 + j0.2833 j0.2833 + j0.2833 j0.9
220

(1)
(2)
(0)
The sequence voltage drops Vkk , Vkk and Vkk are then calculated using the equation:

(2) (0)
(1)
(1) Zkk Zkk

Vkk = Ia
(2)
(0)
Zkk
+ Zkk
j0.2833 j0.9
Vkk(1) = (0.2170 j0.2146)
= (0.0463 + j0.0468) pu
j0.2833 + j0.9
Vkk(2) = Vkk(0) = Vkk(1) = (0.0463 + j0.0468) pu
As a check calculate

Ia(2)

Vkk(2)
Z (2)

0.0463 + j0.0468
= (0.1651 + j0.1633) pu
j0.2833

Ia(0)

V (0)
= kk
Z (0)

0.0463 + j0.0468
= (0.052 + j0.0514) pu
j0.90

kk

kk

Ia = Ia(0) + Ia(1) + Ia(2) = (0.2170 j0.2146) + (0.1651 + j0.1633) + (0.052 + j0.0514)


=0

Q.E.D.

Then we calculate the changes in bus voltages using equation (4.146).


Bus 3
(0)
(0)
(Z34
Z35
)Vkk(0) j0.10 j0.10
(0)

V3 =
=
(0.0463 + j0.0468) = 0 pu
(0)
j0.30
z45

(1)
(1)
(Z34
Z35
)Vkk(1) j0.1103 j0.1250
(1)

(0.0463 + j0.0468) = (0.0068 j0.0069) pu


V3 =
=
(1)
j0.1
z45

V3(2) = V3(1) = (0.0068 j0.0069) pu


Hence,

V3 = V3(0) + V3(1) + V3(2) = (0.0136 j0.0138) pu


Bus 4

(0)
(0)
(Z44
Z45
)Vkk(0) j0.30 j0.20
(0)

V4 =
=
(0.0463 + j0.0468) = (0.0154 + j0.0156) pu
(0)
j0.3
z45

221

(1)
(1)
(Z44
Z45
)Vkk(1) j0.01397 j0.125
(1)

V4 =
=
(0.0463 + j0.0468) = (0.0068 + j0.0069) pu
(1)
j0.10
z45

V4(2) = V4(1) = (0.0068 + j0.0069) pu


V4 = V4(0) + V4(1) + V4(2) = (0.0290 j0.0293) pu
Bus 5

(0)
(0)
(Z54
Z55
)Vkk(0) j0.20 j0.30
(0)

V5 =
=
(0.0463 + j0.0468) = (0.0154 j0.0156) pu
(0)
j0.3
z45

(1)
(1)
(Z54
Z45
)Vkk(1) j0.1250 j0.1750
(1)

=
(0.0463 + j0.0468) = (0.0231 j0.0234) pu
V5 =
(1)
j0.3
z45

V5(2) = V5(1) = (0.0231 j0.0234) pu


V5 = V5(0) + V5(1) + V5(2) = (0.0617 j0.0624) pu
The bus voltages during fault are

V3 (F ) = V30 + V3 = (0.9058 j0.1395) + (0.0136 j0.138) = (0.8922 j0.1533) pu

V3 (F ) = 0.9053 9.750 pu

V4 (F ) = V40 + V4 = (0.9010 j0.1605) + (0.0290 + j0.0293) = (0.9300 j0.1311) pu

V4 (F ) = 0.9392 8.020 pu

V5 (F ) = V50 + V5 = (0.8632 j0.1987) + (0.0617 j0.0624) = (0.8016 j0.2610) pu


222

V5 (F ) = 0.8430 18.040 pu
The phase components of current in line 4-5 are:

I(a) 1 1 1 (0.052 + j0.0514)


0

45

(b)
I = 1 a2 a (0.2170 j0.2146) = 0.4782 147.840 pu

45

(c)
0
2
I45 1 a a (0.1651 + j0.1633) 0.478258.56


TWO CONDUCTORS OPEN
The sequence currents can be calculated with the help of equation (4.162) as:

Ia(1) = Iij

(1)
Zkk
(0.3821 j0.3779) j0.2833

=
(0)
(1)
(2)
j0.9 + j0.2833 + j0.2833
Zkk + Zkk + Zkk

Ia(1) = Ia(2) = Ia(0) = (0.0738 j0.073) pu


The sequence voltages of Thevenins equivalent sequence network is calculated using equation
(4.163)

(0)
(2)
Vkk(1) = Ia(1) (Zkk
+ Zkk ) = (0.0738 j0.073) (j0.9 + j0.2833) = (0.0864 + j0.0873) pu

(2)
Vkk(2) = Ia(2) Zkk
= (0.0738 j0.073)(j0.2833) = (0.0207 + j0.0209) pu

(0)
Vkk(0) = Ia(0) Zkk
= (0.0738 j0.073)(j0.9) = (0.0657 + j0.0664) pu

The changes in bus voltages are calculated using equation (4.146).


Bus 3
(0)
(0)
(Z34
Z35
)Vkk(0) j0.1 j0.10
(0)

V3 =
=
(0.0657 j0.0664) = 0 pu
(0)
j0.3
z45

(1)
(1)
(Z34
Z35
)Vkk(1) j0.1103 j0.1250
(1)

V3 =
=
(0.0864 + j0.0873) = (0.0127 j0.0128) pu
(1)
j0.1
z45

(2)
(2)
(Z34
Z35
)Vkk(2) j0.1103 j0.1250
(2)

V3 =
=
(0.0207 j0.0208) = (0.0030 + j0.0030) pu
(2)
j0.1
z45

V3 = V3(0) + V3(1) + V3(2) = (0.0097 j0.0098) pu


223

Hence, the voltage of bus 3 during fault is:

V3 (F ) = V30 + V3 = (0.9058 j0.1395) + (0.0097 j0.0098) = (0.8962 j0.1493) pu

V3 (F ) = 0.9085 9.460 pu
Bus 4

(0)
(0)
(Z44
Z45
)Vkk(0) j0.30 j0.20
(0)

=
(0.0657 j0.0664) = (0.0219 j0.0221) pu
V4 =
(0)
j0.30
z45

(1)
(1)
(Z44
Z45
)Vkk(1) j0.1397 j0.1250
(1)

=
(0.0864 + j0.0873) = (0.0127 + j0.0128) pu
V4 =
(1)
j0.1
z45

(2)
(2)
(Z44
Z45
)Vkk(1) j0.1397 j0.1250
(2)

V4 =
=
(0.0207 j0.0209) = (0.0030 j0.0031) pu
(2)
j0.1
z45

V4 = V4(0) + V4(1) + V4(2) = (0.0122 + j0.0124) pu


Hence, the voltage of bus 4 during fault is:

V4 (F ) = V40 + V4 = (0.9010 j0.1605) + (0.0122 j0.0124) = (0.8888 j0.1728) pu

V4 (F ) = 0.9054 11.00 pu
Bus 5

(0)
(0)
(Z54
Z55
)Vkk(0) j0.20 j0.30
(0)

=
(0.0657 j0.0664) = (0.0219 + j0.0221) pu
V5 =
(0)
j0.30
z45

(1)
(1)
(Z54
Z55
)Vkk(1) j0.1250 j0.1750
(1)

V5 =
=
(0.0864 + j0.0873) = (0.0432 j0.0437) pu
(1)
j0.10
z45

224

(2)
(2)
(Z54
Z55
)Vkk(2) j0.1250 j0.1750
(2)

V5 =
=
(0.0207 j0.0209) = (0.0103 + j0.0105) pu
(2)
j0.10
z45

V5 = V5(0) + V5(1) + V5(2) = (0.0111 + j0.01111) pu


Hence, the voltage of bus 5 during fault is:

V5 (F ) = V50 + V5 = (0.8632 j0.1987) + (0.0111 j0.01111) = (0.8523 j0.2097) pu


V5 (F ) = 0.8777 13.830 pu
The phase components of current in line 4-5 are:

I(a) 1 1 1 (0.0738 j0.073) 0.3114 44.690


45

(b)

I = 1 a2 a (0.0738 j0.073) =
pu
0
45

(c)

2
I45 1 a a (0.0738 j0.073)

225