Table of Contents ......................................................................................................... 2 Question ........................................................................................................................ 2 How do I create an S7 connection for the SIMATIC NET-OPC Server over MPI with the SIMATIC NET PC Software? .................................................. 2 Answer........................................................................................................................... 2 The instructions and notes listed in this document provide a detailed answer to this question. ............................................................................... 2 1 1.1 2 2.1 2.2
Copyright Siemens AG 2008 All rights reserved Guide_S7_MPI_e.doc
Assignment of tasks....................................................................................... 3 Condition........................................................................................................... 3 Configuration of the PC station..................................................................... 4 Download the configuration into PC station.................................................... 16 Start of the OPC Scout ................................................................................... 19 History ........................................................................................................... 26
This entry is from the Internet offer of Siemens AG, Automation and Drives, Service & Support. Clicking the link below directly displays the download page of this document. http://support.automation.siemens.com/WW/view/en/16518346
Question
How do I create an S7 connection for the SIMATIC NET-OPC Server over MPI with the SIMATIC NET PC Software?
Answer
The instructions and notes listed in this document provide a detailed answer to this question.
V1.0
15.02.2008
2/26
Assignment of tasks
In this example a CP 5611 is used that implements S7 communication over the OPC server with an S7 controller on the MPI bus.
NOTE
The method described in these instructions also applies to the communications processors. CP 5613, CP 5511, and CP 5512.
1.1
Condition
It is assumed that one of the two following configuration tools is installed: NCM PC NCM PC is supplied with the SIMATIC NET CD and allows you to create PC projects and open STEP 7 projects. It is, however, not possible to edit S7 blocks in the STEP 7 project with this software. STEP 7 STEP 7 is a separate software package with which you can create S7400, S7-300 and PC projects. S7 blocks can be edited with this software.
Only one of these tools can be installed. In chapter 2 Configuration of the PC station is described the configuration of PC station so that you can use the S7 communication via MPI to exchange data between PC station and S7 station.
V1.0
15.02.2008
3/26
New".
Confirm the project name you have entered (in the example: "PC_Station") with OK. An empty STEP 7 or NCM PC project is then created.
V1.0
15.02.2008
4/26
Station
V1.0
15.02.2008
5/26
entry ID: 16518346 Give the PC station you have just inserted the same name as your computer (in the example: "PC_Station"). Now open the hardware configuration of the PC station by selecting the PC station, then pressing the right mouse button and selecting "Open Project" (STEP 7: "Open Object").
Figure 2-4 hardware configuration of the PC station
You will see an empty rack. If you cannot see the hardware catalog, click on the button marked in red.
V1.0
15.02.2008
6/26
Platzieren Sie jetzt Ihr PC- Baugruppen in diesen Rack (z. B. per Drag & Drop). Now place your PC modules in this rack (for example by dragging them from the hardware catalog). If you use a CP5613 (or CP5512 or CP5511) you will select the CP5611 (or CP5512 or CP5511). The following dialog appears automatically after you insert the module in the PC station.
V1.0
15.02.2008
7/26
To configure the CP5611 on an MPI network, there must be no network assignment for PROFIBUS. Close the dialog with "OK".
Figure 2-7 hardware configuration projecting the CP5611
Double-click the module CP5611 in the PC station. So the property view of the CP5611 will open. Here you change the interface type of the CP5611 from PROFIBUS to MPI in the register General.
V1.0
15.02.2008
8/26
Select MPI for interface type. The following dialog will open.
Figure 2-9 decision dialog
Confirm the dialog with Yes. Following click the button Properties in the property view of the CP5611 (see Figure 2-8 configuring MPI network) to assign the CP5611 to the MPI network.
V1.0
15.02.2008
9/26
Connect the CP5611 to the MPI network by selecting the MPI subnet. Select the MPI address of the CP5611in the combo box. Confirm the dialog with OK.
V1.0
15.02.2008
10/26
Select the OPC server in the hardware catalog and then drag it to any slot.
V1.0
15.02.2008
11/26
Now open the NetPro program. Use the button marked red in the toolbar in Figure 2-13 button NetPro. In NetPro you -configure a S7 connection to exchange data between OPC server and S7 station.
Figure 2-14 configuring the S7 connection in NetPro
Select the OPC server and click on the button marked red in the toolbar to insert a new connection or right-click the OPC server "Insert New connection".
V1.0
15.02.2008
12/26
It`s possible to select the communication peer, when it is configured in the same S7 project like the PC station. In this case the connection is created automatically. Ist he selected communication peer a S7 station, the connection must be downloaded into S7 station. If the communication peer isnt configured in the same S7 project like the PC station, as in this example, an unspecified S7 connection will ber configured. Select unspecified for communication peer in the dialog box. Click Apply. Now the property view of the S7 connection will open.
V1.0
15.02.2008
13/26
Here you set the IP address of the communication peer. Click the button Address Details". The following dialog will open.
Figure 2-17 dialog Address Details
V1.0
15.02.2008
14/26
entry ID: 16518346 Confirm the dialog with OK. Following confirm the property view of S7 connection with OK. So you come back to the dialog Insert New Connection. Confirm this dialog with OK. The S7 connection which you have just configured is shown in the connection table of the PC station.
Figure 2-18 connection table
Now the configuration of the S7 connection is finished. You have to save and compile S7 project. Therefore select the PC station in NetPro and click the button Save and Compile in the toolbar. This updates the information in the S7 project.
Figure 2-19 Save and Compile
V1.0
15.02.2008
15/26
Warning indications can be displayed while proceeding with the Save and Compile of a S7 project. Warnings serve as piece of information and have no functional effect. In case error warnings occur, search for possible divergences in the previous steps of the instructions.
2.1
Click the button "Import Station. A message about restarting the PC station will open.
V1.0
15.02.2008
16/26
Confirm the message about restarting the PC station with Yes. The following dialog to select the XDB file, which should be import, opens.
Copyright Siemens AG 2008 All rights reserved Guide_S7_MPI_e.doc
In this dialog you enter the path of the XDB file. The XDB file is always created in the project by NCM PC / STEP 7 (see Figure 2-1 giving the project a name). With the combo box Search in: you navigate in the path of the XDB file.
V1.0
15.02.2008
17/26
As information, you can see once again which modules and applications are configured in the XDB file.
V1.0
15.02.2008
18/26
Now the import of the XDB file is finished and the configuration is downloaded. In the column connection, which is marked red, you see that the connection is also been downloaded.
2.2
Double-click the OPC.SimaticNetfor connection with the SIMATIC NET OPC server. In the dialog that appears, enter a suitable group name and confirm this with OK.
V1.0
15.02.2008
19/26
Double-click the OPC group which you have created. The "OPC-Navigator" opens. You will now see your protocols in the OPC Navigator. Double-click on "S7". The connection name you configured in NetPro appears.
V1.0
15.02.2008
20/26
Double-click the connection name of your configured S7 connection. Under "Objects", the tree with the objects that can be accessed appears. If you have downloaded data blocks to the PLC of the S7 station, these will display.
V1.0
15.02.2008
21/26
Double-click on a DB to create a variable. If the DB is crossed through in red, this is OK. You will find a more detailed explanation of this behavior in SIMATIC Technical Support on the Internet under the following Entry: http://support.automation.siemens.com/WW/view/en/8763769 To create an OPC item, double-click on "New Definition". A new window appears in which you can define various variables and data types.
V1.0
15.02.2008
22/26
In this example, the 2nd byte in data block DB10 will be accessed. The syntax for DB is: S7:[<connectionname>]DB<no>,{<type>}<address>{,<quantity>} Now click "OK", the item is now in the central area of the window. If you press " ", you move the item to the right-hand column.
V1.0
15.02.2008
23/26
Confirm the dialog with "OK" to add the new defined OPC item in the OPC Scout. If the quality is good, your connection is established and it is possible to read and write respectively the OPC items.
Figure 2-31 OPC Scout
Double-click on the box of the value to write values into the PLC of the S7Station.
V1.0
15.02.2008
24/26
V1.0
15.02.2008
25/26
History
Version V 1.0 Date 15.02.2008 First issue Changes
V1.0
15.02.2008