0% found this document useful (0 votes)
624 views3 pages

NEC Cable Selection

1. Cable sizing must follow the 125% rule in the NEC, meaning cable capacity must be at least 125% of the continuous load current and MCCB ratings must be at least 125% of continuous loads. Some MCCBs are rated for continuous duty which changes this rule. 2. Cable temperature ratings must not exceed 75°C in panel boards according to the NEC. Cable capacity is based on the lower of its rating at 60/75°C or at 90°C with derating factors applied. 3. All power and control cables in NEC projects must include an insulated or bare copper conductor for grounding purposes.

Uploaded by

Calvert Wong
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
624 views3 pages

NEC Cable Selection

1. Cable sizing must follow the 125% rule in the NEC, meaning cable capacity must be at least 125% of the continuous load current and MCCB ratings must be at least 125% of continuous loads. Some MCCBs are rated for continuous duty which changes this rule. 2. Cable temperature ratings must not exceed 75°C in panel boards according to the NEC. Cable capacity is based on the lower of its rating at 60/75°C or at 90°C with derating factors applied. 3. All power and control cables in NEC projects must include an insulated or bare copper conductor for grounding purposes.

Uploaded by

Calvert Wong
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Cable selection in NEC project (for IEC practiced engineers) When you select a LV cable in a project which uses

NEC as the wiring code, the following must be observed. I referred NEC 2008 and IEE 1992. 1 125% rule ( or may be 80% rule) Your cable must have 125% current carrying capacity against continuous load. This is not a 25% design margin nor for future load, simply you can not use this 25% forever. In NEC and UL, MCCB, MCC and panel board rating is three hours rating, but not continuous. For continuous load, or load which is continuous for more than 3 hours, MCCB rating must be greater than 1.25 times the load current. For instance, continuous load of 100A requires 125AT MCCB at least. If you select 100A MCCB for 100A load, it may trip if the current of 100A continues more than three hours. The power cable connecting this load is protected by this 125A MCCB, thus the current carrying capacity of the cable is 125A minimum, which means you need a 125A cable for 100A load. Cable current carrying capacity >= MCCB rating >= 1.25 times continuous load current Refer to NEC 210.19(A)(1), 210.20(A), 240.4 IEE Note Cable current carrying capacity >= MCCB rating >= Continuous load current Refer to IEE 433-02-01 (1) and (2) 2 Many ACBs and some MCCBs are 100% continuous rating. If your ACB or MCCB together with the enclosure is 100% continuous rating, the item 1, above 125% rule does not apply. Such equipment or device has normally large rating current such as 500A or larger. Cable current carrying capacity >= MCCB rating >= Load current However, as far as I know, most of LV loads are fed from 3 hours rating panels. Practically, 100% continuous rating is only for ACB. Refer to NEC 210.19(A)(1) Exception No.1, 210.20(A) Exception

For cable protection, the next higher standard over-current device permitted. NEC permits a cable is protected with next higher OC device.

for instance cable with 100A current carrying capacity must be protected by 100A MCCB, however, 101A current carrying capacity cable can be protected by 110A MCCB which is next higher standard of 101A. The rule shown in item 1 above needs to change to this way. Cable current carrying capacity >= 1.25 times continuous load current And MCCB rating >= 1.25 times continuous load current. And Cable current carrying capacity >= next higher MCCB rating Refer to NEC 210.19 (A)(1), 210.20(A), 240.4 (B) For standard ampere rating, refer to NEC 240.6(A). 4 Conductor temperature in a panel board is 60 or 75 deg C. Your XLPE cable has maximum conductor temperature of 90 deg.C. However, you must keep the conductor temperature in the panel 60 or 75 deg C depending on the panel. If you can specify the conductor temperature of a panel, specify 75 deg C. There is no LV panel with 90 deg C available. In a panel, there is no need to apply group factor to reduce current carrying capacity. Current carrying capacity of a cable = Current carrying capacity of the cable at 60 or 75 deg. C without applying a group factor Or Current carrying capacity of the cable at 90 deg. C with applying a group factor. whatever smaller one. Refer to NEC 110.14(C)(1) Refer to IEE 512-02-01 5 2.5 mm2 16A, 4 mm2 20A, 6mm2 32A NEC requires small cables must be protected by the following OC protection. 14AWG (= 2.08mm2): 15A 12AWG (=3.31mm2): 20A 10AWG (=5.261mm2): 30A IEC interpretation. 2.5mm2: 16A 4mm2: 20A 6mm2: 30A You must apply 80% rule here.

Refer to NEC 240.4(D)(3), (5) and (7) 6 All power and control cables must include PE. Even though you can purchase IEC standard cables without PE, you should not do it. An NEC oriented client will never accept the explanation of IEC or interpretation of NEC with PE-less cables. Another important thing you should never forget is all HV, MV, LV power and control cable must have PE within each cable. Single core cables are the only exception to this rule. PE is called as EGC (Equipment Grounding Conductor) in NEC and the function is exactly same as PE. EGC insulation color is either green or green/yellow. Un-insulated EGC in a cable is also acceptable. Metal cable amour can be treated as EGC. Refer to NEC 250.134(B) and 300.3(B)

You might also like