Isolux Ingeniería, S.A. Ministry of Electricity and Water: 6M. Mechanical Technical Data Sheet

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 2

MINISTRY OF ELECTRICITY ISOLUX INGENIERA, S.A.

AND WATER
6M. MECHANICAL TECHNICAL DATA SHEET
6M.2 GAS OIL SYSTEMS

6M.2 GAS OIL SYSTEMS Item Description No. 1. 1.1 1.2 Tariff metering (main pipeline supply) Number of and rating Type

Units

Particular

1 Positive displacement type( oval gear/ root type) or similar

1.3 1.4 1.5 2. 3. 3.1

Capacity Accuracy Turndown capability Gas oil storage tanks (Not used) Gas oil forwarding pumps: Number provided and rating (No. x %)

kg/s 46 Within +/-0.5% 5:1

3 x 50%

3.2 3.3

Type Manufacturer

Centrifugal KSB/Mather Platt/ Sulzer /Jyoti or similar

3.4 3.5

Capacity Net positive suction head at rated capacity

l/s 23 M Later

3.6 3.7 3.8

Maximum power absorbed by pump Discharge pressure at rated output Discharge pressure against closed valve

KW

Later

Bar 4.5 Bar 5.8

3.9 3.10 3.11 3.12 3.13 3.14 3.15 3.16 3.17 3.18

Speed Pump inlet connection diameter Pump discharge connection diameter Weight Type of coupling Casing material Impeller material Shaft material Shaft sleeves material Type of bearings

rev/s 24.16 Mm 65 NB Mm 50 NB Kg Later Direct, mechanical Cast Iron SS410 SS Later Later

This document contains proprietary information of ISOLUX INGENIERIA S.A. and is to be used solely for the Project and the purpose for which it is furnished. It may not be disclosed to others for a different use without the written permission of ISOLUX INGENIERIA S.A

MINISTRY OF ELECTRICITY ISOLUX INGENIERA, S.A. AND WATER


6M. MECHANICAL TECHNICAL DATA SHEET
6M.2 GAS OIL SYSTEMS

Item No. 3.19 3.19.1

Description

Units

Particular

Pump control panel Type Local control Panel with Remote/Local control selection

3.19.2 3.19.3 4. 4.1 4.2 4.3 4.4 4.5 5. 5.1 5.1.1 5.1.2 5.1.3 5.2 5.2.1 5.2.2 5.2.3

Make Type of enclosure Pressure accumulators Number provided Type Manufacturer Capacity Pressure rating Piping specialties Flow meters Make Type Range Strainers Make Type Number of

As per manufacturer standard Later

No 2 Bladder type with Nitrogen Gas. Later m3 Later Bar Later

Later Oval gear type No Later

Later Basket type with Self cleaning 6

This document contains proprietary information of ISOLUX INGENIERIA S.A. and is to be used solely for the Project and the purpose for which it is furnished. It may not be disclosed to others for a different use without the written permission of ISOLUX INGENIERIA S.A