Dynamic VAR Planning
Dynamic VAR Planning
Outline
Background Objective Load modeling for voltage stability studies Corrective measures for voltage stability Dynamic VAr Planning Study results Conclusions
Background
Power system stability- The ability of an electric power system, operating at a given initial condition, to regain a state of operating equilibrium after being subjected to a physical disturbance, with most of the system variables bounded, so that practically the entire system remains intact. Voltage stability - ability of a power system to maintain steady voltages at all the buses in the system after disturbance.
Background
Based on actual incidents, short term voltage stability has been an increasing concern in power industry The short term voltage stability problem may arise in two forms.
Slow voltage recovery Fast collapse
Several events that have occurred and recent industry work mainly deal with slow voltage recovery following short circuits with stalling and slow tripping of residential air conditioner compressor motors However, the fast voltage collapse has not been addressed in the literature VAr planning using static criteria are well established. The suitability of dynamic reactive power source is another subject which has drawn significant attention regarding the fast voltage collapse
4
Load characteristics
The accuracy of analytical results depends on proper modeling of power system components, devices, and controls Loads are most difficult to model
Complex in behavior varying with time and location Statistical in nature, and consists of a large number of continuous and discrete controls and protection systems
Dynamics of loads, especially, induction motors at low terminal voltage should be properly modeled
1.0
1.0
Air conditioners should be modeled to analyze the short term voltage stability problem Quite important for utilities in the Western interconnection
Load modeling
Old models
Loads are represented as lumped load at the distribution feeder The diversity in composition and dynamic behavior of various electrical loads is not modeled
Transmission Bus Bus 1
Variable reactive power source Can generate as well as absorb reactive power Maximum and minimum limits on reactive power output depends on limiting values of capacitive and inductive susceptances. Fixed capacitor with thyristor controlled reactor model is used. Droop characteristics of 2% over the control range is used.
Transformer
XSL
V XL
XC
Vref
11
Voltage source converter device Alternating voltage source behind a coupling reactance Can be operated at its full output current even at very low voltages Depending upon manufacturer's design, STATCOMs may have increased transient rating both in inductive as well as capacitive mode of operation. PI controller to regulate the voltage and a droop characteristics of 2% over the control range is used.
Transformer I X E
DC-AC switching converter
Cs Vdc
ICT
ICmax Cma
ILmax
ILT
Capacitive
Inductive
12
Trajectory sensitivity
Why? The influence of parameters on the non-linear, non-smooth behavior exhibited by a disturbed power system is difficult to explore Normal linearization techniques involving linearization of system model about an operating point are not very useful What? Based on linearizing the system around a trajectory rather than around an equilibrium point Change in trajectory due to small change in parameters is observed
13
f ( x, y , )
0 g ( x, y , )
The flows of x and y can be defined as,
x(t )
x
( x , t, )
o
x(t ) y (t )
x(t ) y (t )
x (t ) y (t )
(9)
(10)
14
x
y
( x , t,
o
)
)
( x , t, )
o
(11)
( x , t,
o
( x , t, )
o
(12)
These sensitivities are calculated along the trajectory, and are called trajectory sensitivities Sensitivities of the change in bus voltage magnitudes to the reactive power injection at a given bus are calculated, where V is one of the output variable represented by y, and reactive power Q is one of the parameters represented by
15
n i 1
bi
V Q
(13)
t tk
Wk is the weighting factor to designate the importance of the time instant k and Wbi is the weighting factor to represent the importance of bus i on the sensitivity calculation If the voltage collapse is local in nature, then there will only be a smaller number of buses with non-zero Wbi. The selection of the weights Wk depends upon the type of voltage instability based on time frame of interest The bus with the highest trajectory sensitivity index is selected as a candidate bus for dynamic VAr support
16
Load modeling
Composite load model consisting of static and motor loads is used. s T The percentage of motor load (both megawatts and MVAr) at each distribution substation is about 72% of the total load at that substation. The induction motors are classified as,
Small motors - Low inertia motors Large motors - High inertia motors Trip motors - Low inertia motors with the option of tripping under low voltage condition
69 kV Bus
Distribution Transformer
12.5 kV Bus
Static Load
SM ST
LM
The percentages of small, large, and trip motors at each bus are 63, 10, and 27 respectively.
18
Study case
Fault on a 500 kV transmission line and the subsequent double line outage as follows, which causes voltage collapse in many zones. line connecting 500 kV Bus 9 and Bus 23 line connecting 500 kV Bus 1 and Bus 4
The lines are the major transmission corridors for importing power to the subsystem
19
A fault is applied at an artificial bus 90000 which is created at 40% of the 500 kV line 1-4 The fault is cleared after 5 cycles by removing the two lines
No serious voltage problems are observed when motor dynamics are not included The bus voltages restore almost to the pre-fault values
Time (sec)
20
BUS108 230 kV
0.66
0.44
0.00
2.00
8.00
10.00
Fig. 11 Bus voltages without motor dynamics and without corrective action 21
It is observed that the reactive power demand of the induction motor increases during the post contingency period This large increase in reactive power demand further reduces the voltage magnitudes in the system, thereby resulting in voltage collapse At such voltage levels, even the SM motor would stall, overload, and trip The typical tripping time for motors stalled at 50% voltage is 15-20 seconds
0.00
0.00
2.00
8.00
10.00
0.00
2.00
8.00
10.00
Generator response
T The outputs of the generators especially in zone 126 are e exceeding their maximum VAr capacity, thereby stressing the generating units This shows that there is a deficiency of dynamic reactive power in the zone. If appropriate actions are not taken, the zone could be subjected to severe voltage instability
340
258
12
23
Modal analysis
Modal Analysis is performed in two ways
Case A: By increasing the power
transfer with the power factor same as in the base case The zones associated with the critical modes do not represent the zones with very low post fault voltage magnitudes in time domain analysis
Case A: Critical modes at nose point S. No. Modes Participating zones 1 0.014904+j0 119/124/125 2 3 4 5 0.048814+j0 0.057995+j0 0.063687+j0 0.069565+j0 1657 1843 1657 1843/1844
S. No. 1 2 3 4 5 6 7 8 9 10
Modal analysis at point of collapse may not accurately pinpoint the buses or zones that require reactive power support when fast voltage collapse occurs
Case B: Bus participation factors Bus No. Zone No. Bus Participation Factor 397 128 0.53294 391 128 0.52416 378 126 0.50775 591 129 0.50457 396 128 0.50157 595 126 0.4993 379 126 0.49719 389 128 0.49445 333 380 126 128 0.49431 0.49396 24
25
STATCOMs with a rating of 350 MVAr each are placed at buses 108, 102, e 107, and 96 1 The 230 kV voltages recover to nearly 1 pu in about 4 seconds However, the voltages at the 69 kV buses and the distribution feeders (12.5 kV) take much longer time (about 7 seconds) to recover to pre-fault values Since the voltage collapse occurs at the low voltage level (69 kV, and 12.5 kV), it appears that the shunt compensation must be provided at 69 kV buses for effective voltage recovery
0.96
0.72
0.48
0.24
0.00
0.00
2.00
8.00
10.00
Fig. 16 230 kV bus voltages in the system with 900 MVAr STATCOMS at three buses
1.20
0.96
BUS591 69 kV
0.72
0.48
BUS817 12.5 kV
0.24
0.00
0.00
2.00
8.00
10.00
Fig. 17 Bus voltages (12.5-69 kV) in the system with 900 MVAr STATCOMS at three 230 kV buses
T The 69 kV buses that are connected to the 230 kV buses with high sensitivities are chosen as locations for STATCOMs The STATCOMs are removed from the 230 kV buses and then connected to 69 kV buses The maximum limit of the value of shunt compensation at a 69 kV bus is chosen to be 72 MVAr based on the physical constraints at the substation
S. NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 TOTAL
BUS NO. SIZE (MVAR) 17 72 102 72 170 72 322 72 328 44 342 72 343 72 344 72 357 72 373 72 375 72 381 72 477 72 535 72 550 72 551 72 554 72 584 72 591 72 1340 (MVAR)
27
The STATCOMs act quickly to increase their injected current and i thus provide the required reactive t power Voltages at all levels are restored to respective pre-fault values The STATCOMs are required to provide the reactive power to their full capacity only for a short period of time right after fault Power electronic based shunt compensation with high short term ratings may be an effective option to prevent voltage collapse caused by presence of significant induction motor loads
BUS18 500 kV
BUS108 230 kV
0.00
0.00
2.00
8.00
10.00
-0.12
-0.34
-0.56
-0.78
-1.00
0.00
2.00
6.00
8.00
10.00
0.96
0.72
0.48
0.24
Without VAr support 0.00 2.00 4.00 6.00 Time (sec) 8.00 10.00
0.00
29
Conclusions
Voltage collapse for the case under study is caused by short-term voltage instability initiated by a high reactive power demand of the induction motors during the disturbance period A fault on a high voltage transmission line might cause severe voltage dips at the distribution feeders, even though the voltage dips at high voltage level is not that severe Trajectory sensitivity analysis can be very useful in determining the location of dynamic VAr sources Power electronic based shunt compensation with high short term ratings may be an effective and attractive option STATCOMs provide a better option to improve short term voltage instability problems than SVCs Smaller modules of STATCOMs at 69 kV buses are found to be more effective than larger modules at 230 kV buses in order to obtain faster voltage recovery
30
31