Distribution & Power Transformer
Distribution & Power Transformer
Reference Standard: IS 1180 --1989 Types of Distribution Transformers a) Non-Sealed type b) Sealed type
IS 1180 (Part 1)
: 1989
This standard covers Ratings No load voltage ratios Winding connections and vectors Tapping ranges Fittings Terminal arrangement Losses and Impedance values Tolerances
3
IS 1180 (Part 1)
: 1989
Rating : KVA Rating 16, 25, 63 and 100 Frequency 50Hz System Voltage 3.3, 6.6 and 11KV Secondary Voltage 433 and 250
IS 1180 (Part 1)
Tapping
: 1989
+5%
Tappings at
IS 1180 (Part 1)
: 1989
Fittings Oil level indicator Lifting lugs Breather Drain cum sampling valve Rating and terminal marking plates
IS 1180 (Part 1)
: 1989
Clearances in mm
H.V Side
Phase to phase Phase to earth 255 140
L.V Side
75 40
IS 1180 (Part 1)
Limits
: 1989
of temperature rise : Winding 55C Top oil 45C Losses and Impedance values
Load loss (W) Rating (KVA) No load loss (W) at 75C 16 80 475 25 100 685 63 180 1235 100 260 1760
8
Tests
Measurement
of winding resistance Measurement Voltage ratio and check of voltage vector relationship Measurement of impedance voltage, short circuit impedance and load loss Measurement of no-load loss and current Measurement of insulation resistance
9
Tests
SSVW
test IOVW test Lightning impulse test Temperature rise test SC test Air pressure test (35KPa 30min)
10
16
25 63 100
8
7 6 5
11
Mounting arrangements
The
under-base of all the transformers shall be provided with two 75x40mm channels 460mm long.
415mm
4152mm
12
IS 1180 (Part 2)
No
: 1989
14
IS 1180 (Part 2)
: 1989
Clearances in mm
H.V Side L.V Side external
Phase to phase
Phase to earth
127 76
255 140
45 20
75 40
15
Power Transformers
Reference Standards IS 2026 Part I 1977 General IS 2026 Part II 1977 Temperature Rise IS 2026 Part III 1981 Insulation Levels and Dielectric Tests IS 2026 Part IV 1977 Terminal markings, Tappings and Connections IS 2026 Part V 1994 Transformer/ Reactor Bushings- Minimum external clearance in air
16
IS 2026 Part I
This standard covers Service conditions Rating Requirements to withstand Short Circuit Dimensions of Neutral Connection Tolerances Rating plates Fittings Tests
17
Rating
Rated
KVA Operation at other than rated voltage: The transformer can be operated at its rated KVA at any voltage with in 10% Rated frequency: 50Hz 1.5
18
TOLERANCES
Item Total Losses Component Losses Voltage ratio Impedance Voltage No-load current Tolerances +10% +15% 0.5% 10% +30
19
TESTS
Measurement
of winding resistance Measurement Voltage ratio and check of voltage vector relationship Measurement of impedance voltage, short circuit impedance and load loss Measurement of no-load loss and current Measurement of insulation resistance
20
TESTS
Dielectric tests Temperature rise Measurement of Zero Sequence impedance of three phase transformers Short-circuit test Measurement of acoustic Noise level Measurement of harmonics of no-load currents Measurement of power taken by fans and oil pumps
21
IS 2026 Part II
This
standard covers temperature rise requirements of Power Transformers Identification according to cooling methods. Ex. ONAN,OFAF Limits of temperature rise Procedure for temperature rise test.
22
23
IS 2026 Part IV
This
standard covers Terminal markings, Tappings and Connections for power transformers Identifying Terminal and tapping markings a) Character b) End points of phase winding c) Line and Neutral terminals d) Marking of Tappings
26
Connections
Connections
27
IS 2026 Part V
This
standard specifies clearances in air between live parts of bushings on oil immersed power transformer and to object at earth potential.
28
Bushing clearance
Voltage class (KV) < 1.1 3.6 7.2 12 17.5 24 36 52 72.5 Minimum clearance (mm) --60 90 125 170 275 450 630
29