Tutorial 6
Tutorial 6
Q1
At what speed must an eight-pole synchronous generator rotate in order to generate a voltage with a frequency of 60 Hz?
Q.2 A dc motor is used as a prime mover for a synchronous generator in order to obtain a variable-frequency supply. If the speed range of the motor is 820 to 1960 r/min and the generator has four poles, what is the obtainable frequency range of the output voltage?
Q.3 A 250-kVA 1260-V Y-connected synchronous generator has its armature winding reconnected in delta. Determine the machine rating when Delta-connected (i.e., kVA, IL, and VL ).
Q.4 The phase voltage of a 60-Hz synchronous generator is 4600 V at a field current of 8 A. Determine the open-circuit voltage at 50 Hz if the field current is 6 A. Neglect saturation.