PLC - Pres
PLC - Pres
PRESENTATION
ON
PLC
5/40 OF M/S ALLEN BRADLEY : DMPLANT/ OHCU (RGC)/ CRU (RGC)/ FCCU (MAB&WGC).
984 OF M/S MODICON : HGU (PSA) S5-95U & S5115U OF M/S SIEMENS : FCCU (PALL FILTER & GAMBO LOADER) LM IPC620 OF M/S TATA HONEYWELL : TPS/ WWTP FSC OF M/S TATA HONEYWELL : GT/ HRSG
BASIC ARCHITECTURE
PROGRAMMING TERMINAL
PROCESSOR MODULE
MEMORY MODULE
DCS etc
I/O CARDS
FIELD
OUTPUT
TO FIELD
UPDA-TION
UPDA-TION
SCAN TIME
PROGRAMMING MODES
LADDER LOGIC A e.g.
LOGIC BLOCKS
A AND B
LOGIC STATEMENTS
IF A AND B THEN C
Interrogation
Voltage
Output Command
THE SYSTEM FAILS INVARIABLY EVERY TIME THE SAME PARTICULAR SET OF CONDITIONS OCCUR.MOST PLC TAKEN PTR, THESE PROBLEMS ARE FACED IN COMMISSIONING STAGES. RANDOM HARDWARE FAILURES HARDWARE FAILURES GENERALLY OCCUR RANDOMLY. REDUNDANCY IS VERY EFFECTIVE IN SUPPRESSING RANDOM FAILURES . POWER SUPPLY IS ONE MAJOR EXAMPLE.
SFU
M C B
M C B
24 V DC Power Supply
Fuse MCB BPS#1
MCB
Fuse
BPS#2
24 V DC DISTRIBUTION
BPS#1
BPS#2
HRC FUSE
HRC FUSE
FTB1(#2)
FTB2(#2)
DSSX-N203
UPS1BO - BATTERY OPERATIONS, BATTERY IS ON LOAD UPS1CF- COMMON FAULT UPS1EBC - EXTERNAL BYPASS CONTACTOR CSS6BPS#1 - CSS BPS FAIL MD23CVAR04BPS#2 - AMR BPS FAIL FCCUCSS6CCFA1 - FAN FAILURE ALARM
OUTPUT RELAY CONTACTS GETS OVERHEATING DUE HIGH CURRENT COIL USED IN BREAKER. OLD OUTPUT RELAY REPLACED WITH RE-400 RELAY HAVING HIGHER CURRENT CARRYING CAPACITY FOR STARING STOPING OF HT MOTORS.
ONLY THE I/O CARDS OR ONLY THE PROCESSOR RACK CARDS ARE REDUNDANT. ALL THE CARDS i.e. I/O & ALL PROCESSOR RACK CARDS ARE DUAL MODULAR REDUNDANT. ALL THE CARDS i.e. I/O & ALL PROCESSOR RACK CARDS ARE TRIPLE MODULAR REDUNDANT. ALL THE CARDS i.e. I/O & ALL PROCESSOR RACK CARDS ARE QUADRUPLAR MODULAR REDUNDANT.
I/P BOARD A
PROCESSOR A
O/P BOARD A
VOTER SYSTEM A
I/P
OUTPUT DRIVE
VOTER SYSTEM B
O/P
I/P BOARD B
PROCESSOR B
O/P BOARD B
Why Redundancy
For SAFETY- Example Furnace had to trip but PLC is not available For AVAILABLITY- Example All condition are healthy, but furnace
tripped due to PLC card Malfunction
The objective of any redundant system is to improve the amount of safe uptime of a machine or process by ensuring consistent availability of that machine to perform the safety shutdown on process demand , thereby reducing costs associated with equipment failure/shutdown. By using this backup system, one can design the system to take care of safe Availability of Equipments
PROGRAMMABLE LOGIC CONTROLLER The backup option is used where one must transfer the control of the process to a secondary system, without interrupting machine or process operationBumpless transfer Back up system also provide -Equipment with exceptional reliability. -Automatic fault isolation -No disturbance of the process when switching from primary to secondary system - Online Maintenance with Minimum/No disturbance to Plant.
O/P PATH A
2/3
OUTPUT
VO TI NG
SOME FEATURES
SOFTWARE IMPLEMENTED FAULT TOLERANCE. OPERATING MODE IS 3-2-0. SCAN RATES 30 MSEC TUV CERTIFICATION CLASS AK6 HIGHER AVAILABILITY BETTER EVENT HANDLING. SEEMLESS INTERFACE WITH DCS. 95% NEW PLC ARE TMR ONLY.
SIGNALS FROM PLC ARE NORMALLY ISOLATED FROM THE FIELD THROUGH INTERPOSING RELAYS.
INPUT TO PLC
(NO/ NC CONTACTS)
CMD TO FIELD
(NO/ NC CONTACTS)
INPUT RELAY
COIL
OUTPUT RELAY
COIL
SAFETY STANDARDS
SAFETY INTEGRITY LEVELS (SIL)
SIL LEVEL INDICATES AVAILABILITY OF THE SAFETY SYSTEM.
SIL LEVEL 4 3 2 1
90% AVAILABILITY MEANS FOR EVERY 10 TIMES A TRIP SITUATION OCCURS, THERE WILL BE ONE PREDICTED FAILURE TO TRIP.