Basler DECS-200 Instruction Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 183
At a glance
Powered by AI
The instruction manual provides information about operating and installing the DECS-200 Digital Excitation Control System, including general information, controls, functional description, installation, and maintenance.

To provide information about the operation and installation of the DECS-200 Digital Excitation Control System, including general information, controls, functional description, installation, and maintenance.

Qualified personnel should perform procedures and the DECS-200 must be hard-wired to earth ground with at least 12 AWG copper wire for safety.

INSTRUCTION MANUAL

FOR

DIGITAL EXCITATION CONTROL SYSTEM DECS-200


Digital Excitation Control System DECS-200

Internal PreNull Balance Tracking Position

Limits Lower Upper

Edit

Reset

RS-232

COM 0

P0003-26 06/04/01

Publication: 9360100990 Revision: G 11/07

INTRODUCTION
This instruction manual provides information about the operation and installation of the DECS-200 Digital Excitation Control System. To accomplish this, the following information is provided: General Information and Specifications Controls and Indicators Functional Description Installation Maintenance

WARNING! To avoid personal injury or equipment damage, only qualified personnel should perform the procedures in this manual.

NOTE Be sure that the DECS-200 is hard-wired to earth ground with no smaller than 12 AWG copper wire attached to the ground terminal on the rear of the unit case. When the DECS-200 is configured in a system with other devices, it is recommended to use a separate lead to the ground bus from each unit.

9360100990 Rev G

DECS-200 Introduction

First Printing: January 2002 Printed in USA 2002, 2004-2007 Basler Electric, Highland Illinois 62249 USA All Rights Reserved November 2007

CONFIDENTIAL INFORMATION of Basler Electric, Highland Illinois, USA. It is loaned for confidential use, subject to return on request, and with the mutual understanding that it will not be used in any manner detrimental to the interest of Basler Electric.

It is not the intention of this manual to cover all details and variations in equipment, nor does this manual provide data for every possible contingency regarding installation or operation. The availability and design of all features and options are subject to modification without notice. Should further information be required, contact Basler Electric.

BASLER ELECTRIC ROUTE 143, BOX 269 HIGHLAND IL 62249 USA http://www.basler.com, [email protected] PHONE +1 618.654.2341 FAX +1 618.654.2351
ii DECS-200 Introduction 9360100990 Rev G

REVISION HISTORY
The following information provides a historical summary of the changes made to the DECS-200 hardware, firmware, and software. The corresponding revisions made to this instruction manual (9360100990) are also summarized. Revisions are listed in reverse chronological order. BESTCOMS Software Version and Date 1.05.00, 11/07 1.04.00, 06/04 1.03.05, 11/02 1.03.04, 06/02

Change Added Short output indicator to Metering, Alarm/Status screen. Added SCL Initial Delay to Settings, SCL screen. Added takeover-style OEL, SCL, and loss of field settings to interface. Added the EDM pole ratio calculator. Removed the Number of Poles parameter. Improved overall functionality. Allowed V/Hz Slope Setting adjustments to be made in increments of 0.01. The default value of the Analysis screen was changed from 10% steps to 2% steps. Updated BESTCOMS to add oscillography trigger to step response. Initial release

1.03.03, 05/02 1.03.00, 09/01

Application Firmware Version and Date 1.03.00, 10/07 1.01.03, 11/02 1.01.02, 05/02 1.01.01, 09/01

Change Added Short output indicator. Added SCL Initial Delay. Added primary/secondary active DECS indication (for redundant DECS applications). Modified firmware for compatibility with new LCD. Improved Auxiliary input measurement accuracy. Added takeover-style OEL. Added option of specifying on-line/off-line OEL activation via the 52J/K and 52L/M contact inputs. Added stator current limiting and loss of field protection. Added automatic alarm reset when generator frequency decreases below 10 Hz. Improved crosscurrent compensation. Added the EDM pole ratio calculator. Removed the Number of Poles parameter. Resolved field overcurrent indication problem when field overvoltage alarm was triggered. Improved var to AVR mode (online) tracking. Resolved nuisance EDM indication on secondary DECS in dual DECS applications. Resolved field overvoltage and field overcurrent alarm indication of secondary DECS during startup in dual DECS applications. Initial release.

1.02.03, 06/05 1.02.02, 04/05 1.02.00, 06/04

9360100990 Rev G

DECS-200 Introduction

iii

Hardware Version and Date R, S, 07/05 Q, R, 06/05 P, Q, 03/05

Change Updated packing material. (9360100100, 102 advanced to revision S, 9360100101, 103 advanced to revision R.) Released firmware version 1.02.03 (9360100100, 102 advanced to revision R, 9360100101, 103 advanced to revision Q. Improved mounting of front panel communication connector. (9360100100, 102 advanced to revision Q, 9360100101, 103 advanced to revision P.) Released firmware version 1.02.01 and BESTCOMS version 1.04.01. (9360100100, 102 advanced to revision P, 9360100101, 103 advanced to revision N. Revision level O not used.) Updated power supply circuit boards. (9360100100, 102 advanced to revision N, 9360100101, 103 advanced to revision M.) Released firmware version 1.02.00 (9360100100, 102 advanced to revision M, 9360100101, 103 advanced to revision L. Improved dielectric strength of C power supply (P/N 9360100100, 102 only). Began using new front panel LCD (display). Revised terminal numbering overlays. Revision level not used. Improved circuit board component labeling. Implemented BESTCOMS version 1.03.04 and updated production test. Implemented firmware version 1.01.02. Revised packing material. Revised engineering documents. Released hardware to production. Added CSA, UL, and CE logos to the part number labels. Pre-production manufacturing improvements and releases.

N, P, 07/04

M, N, 07/04 L, M, 06/04 L, 05/04 K, 01/03 J, 10/02 I H, 08/02 G, 06/02 F, 05/02 E, 05/02 D, 03/02 C, 01/02 A, B, 11/01

Manual Revision and Date G, 11/07 E, 12/05

Change Added manual part number and revision to footers. Corrected terminal numbering in Figure 4-6. Added SCL Initial Delay. Added Short Output Indicator. Added illustrations showing left-side terminals and typical connections to Section 4, Installation. (These figures were omitted in revision E of the manual.) Corrected minor errors in Section 2, Human-Machine Interface, Front Panel Operation. Removed expired patent information from Section 1. Added missing setting descriptions to Section 5. In Section 4, added caution box regarding the length of screws used to attach escutcheon plate to DECS-200. Made various minor corrections/changes throughout manual.

F, 08/06

iv

DECS-200 Introduction

9360100990 Rev G

Manual Revision and Date D, 06/04 C, 11/02

Change Section 1: Updated output contact ratings. Section 2: Modified tables and menu branch drawings to show added settings. Section 3: Added functional description of takeover OEL and SCL. Removed reference to A-phase and C-phase as acceptable sensing current source for crosscurrent compensation applications. Section 4: Added Crosscurrent Sensing sub-section with table listing crosscurrent sensing terminals. Section 5: Revised or added all applicable BESTCOMS screens and setting descriptions to accommodate new settings/features. Section 6: Added/changed BESTCOMS screens and DECS-200 settings to accommodate changed BESTCOMS screens and new DECS-200 settings. Section 7: Added/revised Modbus register tables to accommodate new DECS-200 settings. Changed Exciter Diode Monitor (EDM) Protection in Section 1 to reflect the pole ratio increment. Removed Gen Poles and added Pole Ratio to Figure 2-2. Made changes to Figures 2-6 and 2-8. Deleted reference to Generator Poles and Exciter Poles in Section 3, Exciter Diode Monitor (EDM) Function but added Pole Ratio. Updated the list of internal variable on page 3-14. Revised the Installation portion in Section 5 for using a CD-ROM disc. Added the Pole Ratio Calculator in Section 5 as well as updated the screen shots. Updated screen shots in Figures 6-1, 6-3, 6-7, and 6-14. Changed increment levels of register 47747-48, Table 7-17. Updated Table 7-25. Updated Figure 4-3 to correct error in terminal numbers. Updated terminal assignments in Section 1 to correct the error reflected from old Figure 4-3. Added Section 8, Troubleshooting. Corrected various minor errors. Changed introduction section to reflect the January first printing date. Repaginated the introduction so that the table of contents begins on an odd page. Edited the table of contents entries for section five and seven to reflect the appropriate names. Initial release

B, 10/02

A, 01/02

, 01/02

9360100990 Rev G

DECS-200 Introduction

This page intentionally left blank.

vi

DECS-200 Introduction

9360100990 Rev G

CONTENTS
SECTION 1 GENERAL INFORMATION ................................................................................................ 1-1 SECTION 2 HUMAN-MACHINE INTERFACE ....................................................................................... 2-1 SECTION 3 FUNCTIONAL DESCRIPTION ........................................................................................... 3-1 SECTION 4 INSTALLATION .................................................................................................................. 4-1 SECTION 5 BESTCOMS SOFTWARE .................................................................................................. 5-1 SECTION 6 SETUP ................................................................................................................................ 6-1 SECTION 7 MODBUS SOFTWARE.................................................................................................... 7-1 SECTION 8 MAINTENANCE.................................................................................................................. 8-1

9360100990 Rev G

DECS-200 Introduction

vii

This page intentionally left blank.

viii

DECS-200 Introduction

9360100990 Rev G

SECTION 1 GENERAL INFORMATION


TABLE OF CONTENTS
SECTION 1 GENERAL INFORMATION ................................................................................................ 1-1 INTRODUCTION.................................................................................................................................... 1-1 FEATURES ............................................................................................................................................ 1-1 Functions ............................................................................................................................................ 1-1 Inputs and Outputs ............................................................................................................................. 1-1 HMI Interface ...................................................................................................................................... 1-1 APPLICATION ....................................................................................................................................... 1-2 Introduction......................................................................................................................................... 1-2 Operating Power ................................................................................................................................ 1-2 Control Power..................................................................................................................................... 1-2 Sensing............................................................................................................................................... 1-3 Excitation Limiters .............................................................................................................................. 1-3 External Tracking and Transfer Between DECS-200 Units (Optional) .............................................. 1-3 Internal Tracking Between DECS-200 Operating Modes .................................................................. 1-3 Communication With a PC ................................................................................................................. 1-3 MODEL AND STYLE NUMBER DESCRIPTION................................................................................... 1-3 Sample Style Number ........................................................................................................................ 1-4 SPECIFICATIONS ................................................................................................................................. 1-4 Control Power..................................................................................................................................... 1-4 Operating Power ................................................................................................................................ 1-4 Generator Voltage Sensing ................................................................................................................ 1-4 Generator Current Sensing ................................................................................................................ 1-5 Bus Voltage Sensing .......................................................................................................................... 1-5 Accessory Inputs ................................................................................................................................ 1-5 Communication Ports ......................................................................................................................... 1-5 Contact Inputs .................................................................................................................................... 1-5 Contact Outputs ................................................................................................................................. 1-6 Field Output ........................................................................................................................................ 1-6 Regulation .......................................................................................................................................... 1-6 Parallel Compensation ....................................................................................................................... 1-7 Field Overvoltage Protection .............................................................................................................. 1-7 Field Overcurrent Protection .............................................................................................................. 1-7 Exciter Diode Monitor (EDM) Protection ............................................................................................ 1-7 Generator Undervoltage Protection ................................................................................................... 1-7 Generator Overvoltage Protection ..................................................................................................... 1-8 Loss of Sensing Protection................................................................................................................. 1-8 Loss of Field Protection...................................................................................................................... 1-8 Soft Start Function.............................................................................................................................. 1-8 Voltage Matching................................................................................................................................ 1-8 On-Line Overexcitation Limiting ......................................................................................................... 1-8 Off-Line Overexcitation Limiting ......................................................................................................... 1-9 Underexcitation Limiting ..................................................................................................................... 1-9 Manual Excitation Control .................................................................................................................. 1-9 Metering.............................................................................................................................................. 1-9 Sequence of Event Recording (SER)............................................................................................... 1-10 Data Logging (Oscillograpy)............................................................................................................. 1-10 Temperature Range ......................................................................................................................... 1-10 Type Tests........................................................................................................................................ 1-10 Physical ............................................................................................................................................ 1-10 UL Recognition ................................................................................................................................. 1-10 CSA Certification .............................................................................................................................. 1-10 CE Compliance ................................................................................................................................ 1-10

9360100990 Rev G

DECS-200 General Information

Figures Figure 1-1. Block Diagram of Typical DECS-200 Application ................................................................... 1-2 Figure 1-2. Style Number Identification Chart ........................................................................................... 1-3

ii

DECS-200 General Information

9360100990 Rev G

SECTION 1 GENERAL INFORMATION


INTRODUCTION
The Basler Digital Excitation Control System (DECS-200) is a microprocessor-based control device intended for generator power management. Programmability of system parameters and regulation settings enables the DECS-200 to be used in a wide range of applications and provides greater flexibility in excitation system optimization. The DECS-200 can accommodate generator exciter field requirements up to 15 Adc continuously in 32, 63 or 125 Vdc applications with one model.

FEATURES
DECS-200 units have the following features and capabilities. Functions Four control modes o Automatic voltage regulation (AVR) o Manual or field current regulation (FCR) o Power factor (PF) o Reactive power (var) Soft start buildup with an adjustable ramp in AVR and FCR control modes One adjustment range or pre-position setpoint for each control mode Overexcitation limiting (OEL) and underexcitation limiting (UEL) in AVR, var and PF control modes Twenty stability selections Underfrequency compensation or volts per hertz ratio limiter Autotracking between operating modes and between DECS-200 units (optional) Automatic transfer to a backup DECS-200 unit (optional) Eight generator protection features o Field overvoltage o Field overcurrent o Generator overvoltage o Generator undervoltage o Watchdog timer o Loss of sensing o Exciter diode monitor (EDM) o Loss of field Generator paralleling with reactive droop compensation and reactive differential compensation Data logging and event recording

Inputs and Outputs Single-phase rms bus voltage sensing Single-phase or three-phase rms generator voltage sensing Single-phase generator current sensing (1 or 5 amperes, nominal) Analog inputs (10 Vdc and 4 to 20 mAdc) provide proportional, remote control of the setpoint Eleven PLC-compatible contact sensing inputs for system interface Separate ac and dc power inputs accommodate redundant operating power sources Pulse-width modulated output power stage rated at a maximum of 15 amperes, continuous Five output relays for system control or annunciation o Three programmable output relays o Two fixed-function output relays

HMI Interface Front panel HMI includes pushbutton controls, LED indicators and a backlit, liquid crystal display (LCD) BESTCOMS Windows based software provides easy, fast and accurate setup and control

9360100990 Rev G

DECS-200 General Information

1-1

Three communication ports o Front RS-232 port for communication with a PC using BESTCOMS software o Right-side panel RS-232 port for dedicated communication with a redundant DECS-200 o RS-485 communication port for communication with a remote terminal Modbus protocol for the RS-485 port allows communication at distances of up to 1,200 meters (3,937 feet)

APPLICATION
Introduction In the typical application shown in Figure 1-1, the DECS-200 controls the exciter field of a synchronous generator. Front panel controls, indicators and serial communication ports using PC software make the system easy to operate locally or from remote locations. DECS-200 operation, settings and safety setup procedures in this manual should be studied before implementing your application. For detailed application assistance, contact Basler Electric or your local sales representative.

Figure 1-1. Block Diagram of Typical DECS-200 Application Operating Power Operating power for the pulse-width modulated (PWM) excitation output is typically obtained from the generator output through a power transformer. Alternately, operating power can be supplied from a permanent magnet generator (PMG). Control Power If power supply option C (120/125 Vac/Vdc) is selected, a redundant power source can be used with the DECS-200. (See Figure 1-1.) In this configuration, if one of the two sources fails, the other source will continue to supply DECS-200 operating power. If power supply option L (24/48 Vdc) is selected, no redundant power source is available. 1-2 DECS-200 General Information 9360100990 Rev G

Sensing The DECS-200 senses generator voltage and current through voltage and current transformers. Field voltage and field current values are sensed internally. Excitation Limiters Integrated overexcitation and underexcitation limiters (OEL and UEL) are available for both on-line and off-line protection. External Tracking and Transfer Between DECS-200 Units (Optional) For critical applications, a second DECS-200 can provide backup excitation control. The DECS-200 allows for excitation system redundancy by providing external tracking and transfer provisions between DECS-200 units. The secondary DECS-200 operating modes can be programmed to track the primary DECS-200 operating mode. Proper, redundant excitation system design allows for removal of the failed system. Periodic testing of the backup system must be performed to ensure that it is operational and can be put into service without warning. Internal Tracking Between DECS-200 Operating Modes In applications using a single DECS-200, the DECS-200 can be programmed so that the inactive operating modes track the active operating mode. Operating modes include AVR, FCR, PF and var. If the excitation system is normally operating on-line in Internal mode and a loss of sensing occurs, the DECS200 could be transferred to manual (FCR) mode where the loss of sensing has no impact on the exciter's ability to maintain proper excitation levels. While performing routine testing of the DECS-200 in backup mode, the internal tracking feature allows a transfer to an inactive mode that will result in no disturbance to the system. Communication With a PC Communication between the DECS-200 (front panel RS-232 port) and a PC is possible through BESTCOMS software. BESTCOMS enables fast and easy programming of setpoints and ranges and allows for step changes to facilitate proper stability settings. BESTCOMS also provides easy start and stop control and operator adjustment of the excitation system with real-time metering. The software catalog number is BESTCOMS-DECS200. BESTCOMS is provided with the DECS-200 as part of the software/manual package.

MODEL AND STYLE NUMBER DESCRIPTION


DECS-200 operating characteristics are defined by letters and numbers that make up the style number. The model number and style number describe the options included in the DECS-200 and appear on a label attached to the side of the case. Upon receipt of a DECS-200 unit, be sure to check the style number against the requisition and packing list to ensure that they agree.

Figure 1-2. Style Number Identification Chart

9360100990 Rev G

DECS-200 General Information

1-3

Sample Style Number The style number identification chart (Figure 1-2) defines the electrical characteristics and operational features included in the DECS-200. For example, if the style number were DECS-200-1L, the device would have the following characteristics and features. DECS-200 -- Digital Excitation Control System 1 --- Internal autotracking/transfer L --- 24/48 Vdc control power supply

SPECIFICATIONS
DECS-200 electrical and physical characteristics are listed in the following paragraphs. Control Power Input Voltage DC Input: AC Input: 16 to 60 Vdc (style XL) or 90 to 150 Vdc (style XC) 85 to 132 Vac, 50/60 Hz (style XC only) Note: Isolation transformer for ac input is required when dual control power sources are used. 30 W 50 VA B7 (+), B8 () B9 (L), B10 (N) (style XC only)

Burden DC Input: AC Input: Terminals DC Input: AC Input:

Operating Power To achieve the proper DECS-200 output voltage, the appropriate operating power input voltage must be provided. 32 Vdc PWM Output Nominal: Operating Range: Frequency Range: Configuration: Burden: 63 Vdc PWM Output Nominal: Operating Range: Frequency Range: Configuration: Burden: 125 Vdc PWM Output Nominal: Operating Range: Frequency Range: Configuration: Burden: Voltage Buildup From a minimum of 3 Vac Terminals C2 (A-phase), C3 (B-phase), C4 (C-phase) Generator Voltage Sensing Type: 1-4 60 Vac 56 to 70 Vac, 10% 50 to 500 Hz 1-phase or 3-phase 780 VA 120 Vac 100 to 139 Vac, 10% 50 to 500 Hz 1-phase or 3-phase 1,570 VA 240 Vac 190 to 277 Vac, 10% 50 to 500 Hz 1-phase or 3-phase 3,070 VA

1-phase/3-phase, 4 ranges DECS-200 General Information

9360100990 Rev G

Burden: Terminals: 50 Hertz Sensing Range 1: Range 2: Range 3: Range 4: 60 Hertz Sensing Range 1: Range 2: Range 3: Range 4: Generator Current Sensing Type: Frequency: Ranges: Burden: Terminals 1 A Sensing: 5 A Sensing:

<1 VA per phase A1, A2, A3 100 Vac (85 to 127 Vac) 200 Vac (170 to 254 Vac) 400 Vac (340 to 508 Vac) 500 Vac (425 to 625 Vac) 120 Vac (94 to 153 Vac) 240 Vac (187 to 305 Vac) 400 Vac (374 to 600 Vac) 600 Vac (510 to 660 Vac)

Two ranges, two channels 50/60 Hz 1 A or 5 A nominal, continuous <1 VA per phase B1, B3 (phase B, metering, var/PF, UEL) B4, B6 (phase B, crosscurrent compensation) B2, B3 (phase B, metering, var/PF, UEL) B5, B6 (phase B, crosscurrent compensation)

Bus Voltage Sensing Type: Burden: Sensing Ranges: Terminals: Accessory Inputs Current Input Range: Terminals: Voltage Input Range: Terminals: Communication Ports Interface RS-232: RS-485: Connections Com 0: Com 1: Com 2: Parameters Baud: Data Bits: Parity: Stop Bits: Contact Inputs Type: 9360100990 Rev G

1-phase, 4 ranges, <1 VA Identical to generator voltage sensing A4, A5

4 to 20 mAdc A6 (+), A7 () 10 to +10 Vdc A9 (+), A10 ()

Full duplex Half duplex Front panel DB-9 connector Right-side panel DB-9 connector Left-side panel screw terminals (A40, A41, A42) 1200 to 19200 8 None 1 (Com 0, Com 1) or 2 (Com 2)

Dry contact, accept PLC open-collector outputs DECS-200 General Information 1-5

Interrogation Voltage: Terminal Assignments Start: Stop: Auto (AVR): Manual (FCR): Raise: Lower: Pre-Position: Unit/Parallel (52L/M): Var/PF (52J/K): Secondary Enable: Alarm Reset: Contact Outputs Make and Break Ratings 24 Vdc: 48 Vdc: 125 Vdc: 120/240 Vac: Carry Ratings 24/48/125 Vdc: 120/240 Vac: Terminal Assignments Start/Stop (ON, OF): Watchdog (WTCHD): Relay 1 (RLY1): Relay 2 (RLY2): Relay 3 (RLY3): Field Output Continuous Output Rating 60 Vac Input: 120 Vac Input: 240 Vac Input:

12 Vdc A21, A22 A23, A24 A25, A26 A27, A28 A29, A30 A31, A32 A33, A34 A35, A36 A37, A38 A39, A40 A41, A42

8.0 A 0.7 A 0.2 A 10.0 A 8.0 A 10.0 A A11, A12 A13, A14 A15, A16 A17, A18 A19, A20

32 Vdc, 15 Adc 63 Vdc, 15 Adc 125 Vdc, 15 Adc

10 Second Forcing Output Rating 60 Vac Input: 50 Vdc, 30 Adc 120 Vac Input: 100 Vdc, 30 Adc 240 Vac Input: 200 Vdc, 30 Adc Minimum Field Resistance 32 Vdc Application: 63 Vdc Application: 125 Vdc Application: Regulation AVR Operating Mode Accuracy: Steady State Stability: Temperature Drift: V/Hz Characteristic: Response Time: 0.25% over load range at rated PF and constant generator frequency 0.1% at constant load and generator frequency 0.5% for a 0 to 50C change Slope from 0 to 3 PU is adjust-able in 0.1 PU increments. Voltage regulation error is within 2.0% of the nominal voltage. <1 cycle 2.13 4.2 8.3

1-6

DECS-200 General Information

9360100990 Rev G

Accuracy FCR Mode: Var Mode: Power Factor Mode: Internal Tracking: Parallel Compensation Modes: Burden: Adjustment Range Reactive Droop: Reactive Differential: Field Overvoltage Protection Pickup Range: Increment: Time Delay Range: Increment: Field Overcurrent Protection Pickup Range: Increment: Time Delay Characteristic:

1.0% of the nominal value for 10% of the bridge input voltage change or 20% of the field resistance change. Otherwise, 5.0%. 2.0% of the nominal VA rating at the rated frequency 0.02 PF of the PF setpoint for the real power between 10 and 100% at the rated frequency. 0.5%

Reactive Droop and Reactive Differential (cross-current) Can exceed 1 VA if external resistors are added to the CT circuit for crosscurrent compensation. 0 to 30% 30 to 0%

1.0 to 325 Vdc 1.0 Vdc 0.2 to 30 s 0.1 s

0 to 16 Adc 0.1 Adc Inverse per ANSI C50.13

Exciter Diode Monitor (EDM) Protection Pole Ratio Range: Increment: Ripple Threshold Open and Shorted Diode: Time Delay Open Diode Protection: Shorted Diode Protection: 1 to 10 (0 if unknown) 0.01 0 to 100% 10 to 60 s 5 to 30 s

Open and Shorted Diode Inhibit Levels Range: 0 to 100% or <1 Adc field current <45 Hz and >70 Hz generator frequency Generator Undervoltage Protection Pickup Range: Increment: Time Delay Range: Increment: 9360100990 Rev G 0 to 30 kVac 1.0 Vac 0.5 to 60 s 0.1 s DECS-200 General Information 1-7

Generator Overvoltage Protection Pickup Range: Increment: Time Delay Range: Increment: Loss of Sensing Protection Unbalance Generator Volts: Balanced Generator Volts: Time Delay Range: Increment: Loss of Field Protection Pickup Range: Increment: Time Delay Range: Increment: Soft Start Function Setting Range Soft Start Bias Level: Soft Start Bias Time Delay: Voltage Matching Accuracy: 0 to 90% in 1% increments 1 to 7,200 seconds in 1 second increments 0 to 3,000,000 kvar 1 kvar 0.0 to 9.9 s 0.1 s 0 to 30 kVac 1.0 Vac 0.1 to 60 s 0.1 s

0 to 100% 0 to 100% 0 to 30 s 0.1 s

Generator rms voltage is matched with the bus rms voltage to within 0.5% of the generator voltage

On-Line Overexcitation Limiting Response time: <3 cycles High Current Level Pickup Range: Pickup Increment: Time Range: Time Increment: Medium Current Level Pickup Range: Pickup Increment: Time Range: Time Increment: Low Current Level Pickup Range: Pickup Increment: Time Range: 0 to 30.0 Adc 0.1 Adc 0 to 10 s 1s 0 to 20.0 Adc 0.1 Adc 0 to 120 s 1s 0 to 15 Adc 0.1 Adc continuous

1-8

DECS-200 General Information

9360100990 Rev G

Off-Line Overexcitation Limiting High Current Level Pickup Range: Pickup Increment: Time Range: Time Increment: Low Current Level Pickup Range: Pickup Increment: Time Range: Time Increment: Underexcitation Limiting Adjustment Range: 0 to 30.0 Adc 0.1 Adc 0 to 10 s 1s 0 to 30.0 Adc 0.1 Adc 0 to 10 s 1s

0 to 100% of the generator rated apparent power (kvar) at 0 kW real power. Or customizable to generator curve capability.

Manual Excitation Control Range: Increment: Metering Generator Voltage Range: Accuracy: Generator Current Range: Accuracy: Generator Frequency Range: Accuracy: Bus Voltage Range: Accuracy: Bus Frequency Range: Accuracy: Phase Angle Range: Accuracy: Field Voltage Range: Accuracy: Field Current Range: Accuracy: Power Factor Range: Accuracy:

0 to 15.0 Adc 0.1 Adc

0 to 160% of nominal <1% (50/60 Hz) 0 to 200% of nominal <1% (50/60 Hz) 10 to 90 Hz 0.1 Hz 0 to 160% of nominal <1% (50/60 Hz) 10 to 90 Hz 0.1 Hz 90 to +90 1.0 0 to 375 Vdc 1.25 V or 1.0% (whichever is greater) 0 to 31 Adc 0.15 A or 1.0% (whichever is greater) 0.5 to +0.5 PF <0.02 PF

Real Power and Reactive Power Range: 0 to 200% of nominal Accuracy: <1.0% of nominal 9360100990 Rev G DECS-200 General Information 1-9

Sequence of Event Recording (SER) 127 event report, stored in volatile memory (retrievable via BESTCOMS) SER triggered by: Input/Output status changes, system operating status changes or alarm annunciations Data Logging (Oscillograpy) Stores 8 records in volatile memory. Up to 6 variables can be logged in a record. Sampling rate is 600 data points per log, up to 599 pre-trigger, 4 ms to 10 second intervals, (2.4 sec to 6,000 sec. total log duration). Temperature Range Operating: Storage: CD-ROM: Type Tests Shock 15 G in 3 perpendicular planes Vibration 5 to 26 Hz: 27 to 52 Hz: 53 to 500 Hz: 1.2 G 0.914 mm (0.036") double amplitude 5G 40 to +60C (40 to +140F) 40 to +85C (40 to +185F) 0 to +50C (32 to +122F)

Surge Withstand Capability and Fast Transient Tested per IEEE C37.90.1-1989 Dielectric Strength Tested per IEEE 421.3 Salt Fog Tested per MIL-STD-810E, Method 509.3 Physical Weight: Dimensions:

6.35 kg (14 lb) Refer to Section 4, Installation

UL Recognition UL recognized per standard 508, UL file number E90735. CSA Certification Certified per CSA Standard CAN/CSA-C22.2 Number 14, CSA File Number LR23131. CE Compliance The DECS-200 meets the criteria set forth by the following standards: EN 50081-2 Electromagnetic compatibility (EMC) emissions standard: EN 55011, Level A. EN 50082-2 Electromagnetic Compatibility (EMC) Immunity Electrostatic Discharge (ESD) EN 61000-4-2, Level B/IEC 1000-4-2 Radiated Susceptibility EN 61000-4-3, Level A/IEC 1000-4-3 Electrical Fast Transient EN 61000-4-4, Level B/IEC 1000-4-4 1-10 DECS-200 General Information 9360100990 Rev G

Radio Frequency Conducted EN 61000-4-6, Level A/IEC 1000-4-6 Power Frequency Magnetics EN 61000-4-8, Level A/IEC 1000-4-8

9360100990 Rev G

DECS-200 General Information

1-11

This page intentionally left blank.

1-12

DECS-200 General Information

9360100990 Rev G

SECTION 2 HUMAN-MACHINE INTERFACE


TABLE OF CONTENTS
SECTION 2 HUMAN-MACHINE INTERFACE ....................................................................................... 2-1 INTRODUCTION.................................................................................................................................... 2-1 FRONT PANEL controls and indicators................................................................................................. 2-1 Menu Navigation ................................................................................................................................ 2-2 Navigation Aids .................................................................................................................................. 2-2 Edit Sessions...................................................................................................................................... 2-2 Changing Settings .............................................................................................................................. 2-3 PASSWORD PROTECTION ................................................................................................................. 2-8 METERING SCREEN ............................................................................................................................ 2-9 Metering Fields ................................................................................................................................... 2-9 Setpoint Field.................................................................................................................................... 2-10 Percent-of-Range Field .................................................................................................................... 2-10 Mode Message Field ........................................................................................................................ 2-10 Alarm Annunciation Field ................................................................................................................. 2-10 Alarm Message Screen .................................................................................................................... 2-10 Screens with Special Editing Modes ................................................................................................ 2-11 Menu Tree ........................................................................................................................................ 2-11 FRONT PANEL OPERATION.............................................................................................................. 2-22 Operating Modes.............................................................................................................................. 2-22 Setpoints........................................................................................................................................... 2-22 Loop Gains ....................................................................................................................................... 2-23 Controller Gains ............................................................................................................................... 2-24 Metering............................................................................................................................................ 2-24 Protection ......................................................................................................................................... 2-24 Limiters ............................................................................................................................................. 2-25 System Parameters.......................................................................................................................... 2-26 General Settings............................................................................................................................... 2-29 Figures Figure 2-1. Front Panel Controls and Indicators ....................................................................................... 2-1 Figure 2-2.Operating Menu Branch ......................................................................................................... 2-12 Figure 2-3. Setpoint Menu Branch........................................................................................................... 2-13 Figure 2-4. Loop Gains Menu Branch ..................................................................................................... 2-14 Figure 2-5. Metering Menu Branch.......................................................................................................... 2-15 Figure 2-6. Protection Menu Branch........................................................................................................ 2-16 Figure 2-7. Limiters Menu Branch ........................................................................................................... 2-17 Figure 2-8. System Parameters Menu Branch (Part 1 of 3).................................................................... 2-18 Figure 2-9. System Parameters Menu Branch (Part 2 of 3).................................................................... 2-19 Figure 2-10. System Parameters Menu Branch (Part 3 of 3).................................................................. 2-20 Figure 2-11. General Settings Menu Branch........................................................................................... 2-21 Tables Table 2-1. DECS-200 HMI Component Descriptions ................................................................................ 2-2 Table 2-2. Front Panel Setting Parameters............................................................................................... 2-4 Table 2-3. Settings Accessible with Setpoint Access Level ...................................................................... 2-8 Table 2-4. User-Selectable Metering Quantities ....................................................................................... 2-9 Table 2-5. Setpoint Field as a Function of Operating Mode.................................................................... 2-10 Table 2-6. Annunciation Messages ......................................................................................................... 2-10 Table 2-7. Automatic Stability Range Gain Settings Index ..................................................................... 2-23

9360100990 Rev G

DECS-200 Human-Machine Interface

This page intentionally left blank.

ii

DECS-200 Human-Machine Interface

9360100990 Rev G

SECTION 2 HUMAN-MACHINE INTERFACE


INTRODUCTION
This section describes the DECS-200 human-machine interface (HMI), illustrates how to navigate through the menu screens, and explains how to use the front panel interface to view and change settings.

FRONT PANEL CONTROLS AND INDICATORS


The front panel HMI consists of a backlit liquid crystal display (LCD), six pushbutton switches, six LED indicators, and an RS-232 communication connector. The LCD displays DECS-200 settings and excitation system information through the use of a structured menu. Menu screens are viewed and settings are changed by operating the front panel pushbuttons. Active conditions are annunciated by the front panel LEDs. The RS-232 connector (Com 0) enables communication between the DECS-200 and a PC operating BESTCOMS software. Front panel HMI components are shown in Figure 2-1 and described in Table 2-1.

Figure 2-1. Front Panel Controls and Indicators

9360100990 Rev G

DECS-200 Human-Machine Interface

2-1

Table 2-1. DECS-200 HMI Component Descriptions Locator A description LCD. Backlit liquid crystal display is 64 by 128 pixels in size and serves as the primary source of information from the DECS-200. Displays operations, setpoints, loop gains, metering, protection functions, system parameters, and general settings. Pre-Position LED. Lights at the predefined, pre-position setpoint of the active mode. Lower Limit LED. Lights at the minimum setpoint value of the active mode. Upper Limit LED. Lights at the maximum setpoint value of the active mode. Scrolling Pushbuttons. Pushbutton switches are used to scroll up, down, left, and right through the menu structure. When operating in Edit mode, the Left and Right pushbuttons select the variable to change and the Up and Down pushbuttons change the variable value. Reset Pushbutton. Cancels editing sessions, resets alarm annunciations and latched alarm relays, and can be used for quick access to the metering screen. Serial Port (Com 0). This port is dedicated to RS-232 communication with a computer terminal or PC running a terminal emulation program such as BESTCOMS. See Section 1 and Section 3 for more information about the DECS-200 serial ports. Edit Pushbutton. Enables settings changes. When the Edit pushbutton is first pushed, an LED within the pushbutton lights to indicate that Edit mode is active. When settings changes are complete (using the scrolling pushbuttons) and the Edit pushbutton is pressed again, the LED turns off to indicate that the changes are saved. Null Balance LED. Lights when the inactive modes (AVR, FCR, var, or PF) match the active mode. Internal Tracking LED. Lights when any inactive mode (AVR, FCR, var, or PF) is tracking the active mode to accomplish a bumpless transfer when changing active modes.

B C D E

F G

I J

Menu Navigation The front panel scrolling pushbuttons are used to move through the menu structure displayed by the LCD. Pressing the Reset pushbutton (when an edit session is not in progress) gives quick access to the Metering screen. Metering values cannot be viewed during an edit session. Navigation Aids On-screen navigation assists the user in moving from screen to screen. These navigation aids are contained in the top and bottom lines of the LCD. The top line contains a menu path that is similar to the DOS prompt on a personal computer. When the menu path exceeds the width of the LCD, the first part of the menu path is replaced with two dots (..) so that the last part will be seen. Regardless of the menu path length, the current screen name is always shown. The bottom line displays the menu screens that can be accessed from the current screen with the Left, Down and Right pushbuttons on the front panel. The Left pushbutton listing consists of a <, followed by an abbreviated menu name. The Down pushbutton listing consists of the letter v, followed by an abbreviated menu name. The right-pushbutton listing consists of a >, followed by an abbreviated menu name. If the Left and Right pushbutton listings are blank, then the current screen is the only one on this level. If the Down pushbutton listing is blank, then there are no screens below the current screen. Edit Sessions Password access is required before entering an edit session. To initiate an edit session, press the Edit pushbutton. The Edit pushbutton lights to indicate that the front panel is in edit mode. If the appropriate access level is not active, then a prompt to enter a password appears. (Paragraphs titled Password Defaults and Password Protection in this section have more information about using passwords.)

2-2

DECS-200 Human-Machine Interface

9360100990 Rev G

Editing Settings Once the password is entered and security access is obtained, the first editable field of the current screen is underlined. The setting in this field can be modified by pressing the Up pushbutton to increase the setting or the Down pushbutton to decrease the setting. To edit another setting on the current screen, use the Left pushbutton to advance the underline upward or the Right pushbutton to advance the underline downward to the other editable fields. NOTE On most screen, setting changes are used immediately by the DECS-200. However, these changes are not saved in nonvolatile memory until the Edit pushbutton is pressed to terminate the edit session.

After all desired editing on the current screen is complete, the changes can be saved or the values that were in use prior to the edit session can be restored. Changes are saved by pressing the Edit pushbutton which terminates the edit session and saves the changes in nonvolatile memory. Changes are aborted by pressing the Reset pushbutton which terminates the edit session without saving the changes. The previous values are then restored by reading them from nonvolatile memory. In both cases, the Edit pushbutton LED turns off to indicate that the edit session is terminated. Security (password) access is not immediately lost when an edit session is terminated. Security access terminates after 10 minutes of pushbutton inactivity at the front panel. (Security access timeout is different from edit session timeout;. see Edit Session Timeout.) If this period of inactivity occurs during an edit session, any changes made are saved in nonvolatile memory and will be used or continue to be used by the DECS-200. At this time, both edit access and security access are terminated.

CAUTION Pressing the Reset pushbutton after changing the active mode setpoint will cause a step change in the operating setpoint that may have the potential to adversely affect the system.

In order to modify settings on another screen with the same access level, the user merely navigates to that screen and presses the Edit pushbutton to start a new edit session on the new screen. Edit Session Timeout If the front panel is left in the Edit mode after any setting changes are made, the changes will be saved and the edit session terminated after 10 minutes of pushbutton inactivity. Changing Settings All settings that are viewable at the front panel are password protected and require security access to change. Global access grants the right to change any viewable setting at the front panel. Setpoint access grants the right to change only a few settings. These include basic operating settings like Start/Stop, AVR/FCR, PF/var, control setpoints and pre-positions. See Table 2-2 for a complete setting list that shows the range, increments and default values. In Table 22, note that the Ref. column refers to numbers associated with the menu screens shown later in this section. These numbers should help you find the specific screen that contains the setpoint or parameter that you want to change. For a list of settings that are accessible with the Setpoint access level, see Table 2-3. All editable settings on a single menu screen are at the same access level.

9360100990 Rev G

DECS-200 Human-Machine Interface

2-3

Table 2-2. Front Panel Setting Parameters


Ref. 1.1 Parameter Start/Stop Selection AVR/FCR Selection PF/Var Control Enable Load Comp. Selection Pre-Position Enable 1.2 Voltage Matching Internal Tracking Enable External Tracking Enable Underfrequency 2.1 AVR Setpoint FCR Setpoint Droop Compensation Var Setpoint PF Setpoint 2.1.1 Fine Voltage Band AVR Min. Setpoint AVR Max. Setpoint FCR Min. Setpoint FCR Max. Setpoint 2.1.2 Var Min. Setpoint Var Max. Setpoint Max Lag PF Max Lead PF Voltage Matching Band Volt. Matching Ref. 2.2 AVR Prep. Setpoint FCR Prep. Setpoint Var Prep. Setpoint PF Prep. Setpoint 3.1 Gain Table Index AVR/FCR Kp AVR/FCR Ki AVR/FCR Kd AVR/FCR Td 3.2 3.3 AVR Kg FCR Kg OEL Ki OEL Kg UEL Ki UEL Kg SCL Ki SCL Kg 3.4 PF Ki PF Kg Var Ki Var Kg Voltage Matching Kg Minimum Stop, Start AVR, FCR Off, PF Control, Var Control Off, Droop Off, On Off, On Off, On Off, On UF, V/Hz AVR min. setpoint FCR min. setpoint 30% nom. var min. setpoint PF min. setpoint 0% (nom.) 70% (nom.) 100% (nom.) 0.0% (nom.) 0.0% (nom.) 100% (of rated VA) 100% (of rated VA) 0.5 1.0 0% (nom.) 90.0% AVR min. setpoint FCR min. setpoint var min. setpoint PF min. setpoint 1 0.0 0.0 0.0 0.0 0 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 AVR max. setpoint FCR max setpoint 30% nom. var max. setpoint PF max. setpoint 30% (nom.) 100% (nom.) 110% (nom.) 100% (nom.) 120% (nom.) 100% (of rated VA) 100% (of rated VA) 1.0 0.5 20% (nom.) 120.0% AVR max. setpoint FCR max. setpoint var max. setpoint PF max. setpoint 21 1,000.0 1,000.0 1,000.0 1.0 1,000.0 1,000.0 1,000.0 1,000.0 1,000.0 1,000.0 1,000.0 1,000.0 1,000.0 1,000.0 1,000.0 1,000.0 1,000.0 Maximum Increment N/A N/A N/A N/A N/A N/A N/A N/A N/A 0.1 V 0.01 A 0.1% nom. 1 var 0.005 0.01% (nom.) 0.1% (nom.) 0.1% (nom.) 0.1% (nom.) 0.1% (nom.) 1% (of rated VA) 1% (of rated VA) 0.005 0.005 0.01% (nom.) 0.1% 0.1 VA 0.01 A 1 var 0.005 1 0.1 0.1 0.1 0.01 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.01 0.01 0.1 Default Stop AVR Off Droop On Off Off Off UF 120 V 0.1 A 5% nom. 0 var 1.00 20% (nom.) 70% (nom.) 110% (nom.) 0% (nom.) 120% (nom.) 0% 0% 0.8 0.8 10% (nom.) 100% 120.0 V 0.1 A 0 var 1.000 21 30.0 150.0 2.0 0.08 1.0 25.0 10.0 1.0 10.0 2.0 10.0 1.0 120.0 1.0 120.0 1.00 1.0

2-4

DECS-200 Human-Machine Interface

9360100990 Rev G

Ref. 4.1

Parameter 1 Metering Field


st

Minimum

Maximum

Increment

2nd Metering Field 3rd Metering Field 5.1 5.2 Corner Frequency Underfrequency Slope Field OV Enable Field OC Enable Stator OV Enable Stator UV Enable Loss of Sensing Enable Loss of Sensing Xfr to FCR Enable 5.3 Exciter Open Diode Enable Exciter Shorted Diode Enable Loss of Field Enable 5.4 Field OV Threshold Field OC Base Value Stator OV Threshold Stator UV Threshold EDM OD Ripple EDM SD Ripple 5.5 EDM Inhibit Level LOS Balanced Voltage LOS Unbalanced Voltage Loss of Field Level 5.6 Field OV Delay Exc OC Time Dial Mult. Stator OV Delay Stator UV Delay Loss of Voltage Sensing Open Exciter Diode Delay 5.7 Shorted Exciter Diode Delay Loss of Field TD 6.1 6.2 OEL Style OEL Option On-Line OEL Inst. Limit On-Line OEL Inst Time On-Line OEL Med. Limit On-Line OEL Med. Time On-Line OEL Cont. Limit 6.3 Off-Line OEL Hi Limit Off-Line OEL Hi Time Off-Line OEL Low Limit 6.4 Off-Line Takeover OEL Max. Current Off-Line Takeover OEL High Current

Va-b, Vb-c, Vc-a, V Avg, Line I, VA, watts, var, PF Gen Hz, Bus Hz, Bus V, Fld V, Fld I, V Aux, EDM OC, EDM SC 15.0 Hz 0.00 x V/Hz Off, On Of, On Off, On Off, On Off, On Off, On Off, On Off, On Off, On 1V 0.1 A 0V 0V 0% 0% 0% 0% 0% 0 0.2 s 0.1 0.1 s 0.5 s 0.0 s 10.0 s 5.0 s 0.0 325 V 16 A 30,000 V 30,000 V 100% 100% 100% 100% 100% 3,000,000 kvar 30.0 s 20.0 60.0 s 60.0 s 30.0 s 60.0 s 30.0 s 9.9 90.0 Hz 3.00 x V/Hz 0.1 Hz 0.01 V/Hz N/A N/A N/A N/A N/A N/A N/A N/A N/A 1V 0.1 A 1V 1V 0.1% 0.1% 0.1% 0.1% 0.1% 1 kvar 0.1 s 0.1 0.1 s 0.1 s 0.1 s 0.1 s 0.1 s 0.1 N/A N/A 0.1 A 1s 0.1 A 1s 0.1 A 0.1 A 1s 0.1 A 0.1 A 0.1 A

Default V Avg Vc-a Fld I 57.0 Hz 1.00 x V/Hz Off Off Off Off Off Off Off Off Off 20 V 0.1 A 150 V 90 V 5.0% 5.0% 10% 50% 20% 50.00 kvar 5.0 s 1.0 5.0 s 5.0 s 2.0 s 10.0 s 5.0 s 9.9 s Summing Pnt Option 1 3.0 A 10 s 2.0 A 120 s 1.0 A 3.0 A 10 s 1.0 A 0.0 A 0.0 A

Summing Point/Takeover Option 1/Option 2/Option 3 0.0A 0s 0.0 A 0s 0.0 A 0.0 A 0s 0.0 A 0.0 A 0.0 A 30.0 A 10 s 20.0 A 120 s 15.0 A 30 A 10 s 15 A 15.0 A 30.0 A

9360100990 Rev G

DECS-200 Human-Machine Interface

2-5

Ref.

Parameter Off-Line Takeover OEL Time Delay

Minimum 0.1 s 0.0 A 0.0 A 0.1 s 0 kW 0 kW 0 kW 0 kW 0 kW 0 kvar 0 kvar 0 kvar 0 kvar 0 kvar 0.0 A 0.0 s 0.0 A 85 V 10.0 A 50 Hz 1.0 V 0.1 A 0 1V 1V 1V 1V 1A 1A

Maximum 20.0 s 30.0 A 15.0 A 20.0 s 49 kW 49 kW 49 kW 49 kW 49 kW 49 kvar 49 kvar 49 kvar 49 kvar 49 kvar 66,000.0 A 60.0 s 66,000.0 A 30,000 V 60,000 A 60 Hz 180.0 V 15.0 A 10 30,000 V 600 V 500,000 V 600 V 60,000 A 5A

Increment 0.1 s 0.1 A 0.1 A 0.1 s 1 kW 1 kW 1 kW 1 kW 1 kW 1 kvar 1 kvar 1 kvar 1 kvar 1 kvar 1.0 A 1.0 s 1.0 A 1V 0.1 A 10 Hz 0.1 V 0.1 A 0.01 1V 1V 1V 1V 1A 4A N/A N/A 0.01 0.01 0.01 0.01 0.01 N/A N/A N/A 50 ms N/A N/A N/A N/A N/A N/A N/A N/A

Default 0.1 s 0.0 A 0.0 A 0.1 s 0 kW 0 kW 0 kW 0 kW 0 kW 0 kvar 0 kvar 0 kvar 0 kvar 0 kvar 0.0 A 0s 0A 120 V 200.0 A 60 Hz 32.0 V 5.0 A 0 120 V 120 V 120 V 120 V 200 A 5A 1-ph A-C voltage 0 1 1 1 1 Inner NO Maintained 0.10 s Off Off Off Off Off Off Off Off

6.5

On-Line Takeover OEL Max Current On-Line Takeover OEL Min Current On-Line Takeover TD

6.6

UEL Curve, Pnt 1 Watts UEL Curve, Pnt 2 Watts UEL Curve, Pnt 3 Watts UEL Curve, Pnt 4 Watts UEL Curve, Pnt 5 Watts

6.7

UEL Curve, Pnt 1 Vars UEL Curve, Pnt 2 Vars UEL Curve, Pnt 3 Vars UEL Curve, Pnt 4 Vars UEL Curve, Pnt 5 Vars

6.8

SCL High Limit SCL High Limit Time SCL Low Limit

7.1.1

Gen. Rated Output V Gen. Rated Output I Gen. Rated Frequency

7.2.1

Rated Field Voltage Rated Field Current Pole Ratio

7.3.1

Gen. Sensing PT Pri. Gen. Sensing PT Sec. Bus Sensing PT Pri. Bus Sensing PT Sec. Gen. CT Pri. Gen. CT Sec.

7.4.1

Sensing Configuration Auxiliary Input Type Cross Current Gain

1-phase A-C, 3-phase Voltage, Current 30.00 99.00 99.00 99.00 99.00 Inner, Outer NC, NO Momentary, Maintained, Latched 0.10 s On, Off On, Off On, Off On, Off On, Off On, Off On, Off On, Off 5.00 s 30 99 99 99 99

7.4.2

AVR Mode Aux. Gain FCR Mode Aux. Gain Var Mode Aux. Gain PF Mode Aux. Gain Inner or Outer Loop

7.5.1

Relay 1 Contact Sense Relay 1 Annunc. Type Relay 1 Moment Time Field Overvoltage Field Overcurrent Stator Undervoltage

7.5.2

Stator Overvoltage Underfrequency Overexcitation Limit Underexcitation Limit FCR Mode

2-6

DECS-200 Human-Machine Interface

9360100990 Rev G

Ref. 7.5.3

Parameter No Voltage Sensing Setpoint at Low Limit Setpoint at High Limit System Below 10 Hz Open Exciter Diode Shorted Exciter Diode

Minimum On, Off On, Off On, Off On, Off On, Off On, Off NC, NO

Maximum

Increment N/A N/A N/A N/A N/A N/A N/A N/A 50 ms N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 50 ms N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

Default Off Off Off Off Off Off NO Maintained 0.10 s Off Off Off Off Off Off Off Off Off Off Off Off Off NO Maintained 0.10 s Off Off Off Off Off Off Off Off Off Off Off Off Off Off 20 s 20 s 20 s 20 s Release Release Release Release 5% 5s 20.0 s

7.5.4

Relay 2 Contact Sense Relay 2 Annunc. Type Relay 2 Moment Time Field Overvoltage Stator Undervoltage 0.10 s

Momentary Maintained, Latched 5.00 s On, Off On, Off On, Off On, Off On, Off On, Off On, Off On, Off On, Off On, Off On, Off On, Off On, Off NC, NO Momentary, Maintained, Latched 0.10 s On, Off On, Off On, Off On, Off On, Off On, Off On, Off On, Off On, Off On, Off On, Off On, Off On, Off On, Off 10 s 10 s 10 s 10 s 200 s 200 s 200 s 200 s Maintain, Release Maintain, Release Maintain, Release Maintain, Release 0% 1s 1.0 s 90% 7,200 s 80 s 5.00 s

7.5.5

Stator Overvoltage Underfrequency Overexcitation Underexcitation FCR Mode No Voltage Sensing

7.5.6

Setpoint at Low Limit Setpoint at High Limit System Below 10 Hz Open Exciter Diode Shorted Exciter Diode

7.5.7

Relay 3 Contact Sense Relay 3 Annunc. Type Relay 3 Moment Time Field Overvoltage Field Overcurrent Stator Undervoltage

7.5.8

Stator Overvoltage Underfrequency Overexcitation Limit Underexcitation Limit FCR Mode No Voltage Sensing

7.5.9

Setpoint at Low Limit Setpoint at High Limit System Below 10 Hz Open Exciter Diode Shorted Exciter Diode

7.6.1

AVR Traverse Rate FCR Traverse Rate Var Traverse Rate PF Traverse Rate

1s 1s 1s 1s N/A N/A N/A N/A 1% 1s 0.1 s

7.7.1

AVR Prep Mode FCR Prep Mode Var Prep Mode PF Prep Mode

7.8.1 7.9.1

Soft Start Level Soft Start Time Internal Track rate

9360100990 Rev G

DECS-200 Human-Machine Interface

2-7

Ref.

Parameter Internal Track Delay External Track Rate External Track Delay

Minimum 0.0 s 1.0 s 0.0 s 1200 bps 1200 bps 1200 bps 0 0 ms 1 40 N/A N/A 12 hr, 24 hr

Maximum 8s 80 s 8s 19,200 bps 19,200 bps 19,200 bps 247 200 ms

Increment 0.1 s 0.1 s 01. s by x2 by x by x2 by x by x2 by x 1 10 ms N/A 1 1 1 1 N/A N/A N/A

Default 0.1 s 20.0 s 0.1 s 9600 bps 9600 bps 9600 bps 247 10 ms None 2 60 N/A 01-01-01 12 hr DS Off d-m-y

8.1.1

Com0 RS232 Baud Com1 RS232 Baud Com2 RS232 Baud

8.1.2

Com2 Address Com2 Delay Parity Stop Bits

None, Odd, Even 2 80

8.2 8.3

LCD Contrast Real-Time Clock Setting Real-Time Clock Date Setting

8.3.1

Time Format Daylight Saving Time Date Format

DS ON, DS OFF d-m-y, m/d/y

PASSWORD PROTECTION
All editable settings on the front panel are password protected. Passwords can be a maximum of six characters in length and may contain all letters, all numbers, or a mixture of both. Passwords are not case sensitive; the DECS-200 will accept a correct password consisting of uppercase or lowercase letters. There are two levels of access: global and setpoint. Global access grants the user the right to change any editable setting through the front panel. Setpoint access grants the user the right to change a limited number of settings. These settings include the basic operational settings like Start, Stop, AVR/FCR, PF/var, control setpoints and pre-position. For a complete list, refer to Table 2-3. All editable settings on a single menu screen are at the same access level. Table 2-3. Settings Accessible with Setpoint Access Level
Screen OPERATE_1 (1.1) OPERATE_1 (1.1) OPERATE_1 (1.1) OPERATE_1 (1.1) OPERATE_1 (1.1) OPERATE_2 (1.2) OPERATE_2 (1.2) OPERATE_2 (1.2) MODE_SET (2.1) MODE_SET (2.1) MODE_SET (2.1) MODE_SET (2.1) MODE_SET (2.1) PREP_SET (2.2) PREP_SET (2.2) MODE_SET (2.2) ADJUST (4.1) ADJUST (4.1) ADJUST (4.1) ADJUST (4.1) CONTRAST (8.2) AVR/FCR Mode PF/Var Mode Load Compensation Type Pre-Position Enable Voltage Matching Enable Autotracking Enable Autotransfer Enable AVR Mode Setpoint FCR Mode Setpoint Var Mode Setpoint PF Mode Setpoint Droop Setting AVR Mode Setpoint Pre-Position FCR Mode Setpoint Pre-Position Var Mode Setpoint Pre-Position 1ST Metering Field Display Quantity 2nd Metering Field Display Quantity 3rd Metering Field Display Quantity Active Setpoint LCD Contrast Setting Start/Stop Control

2-8

DECS-200 Human-Machine Interface

9360100990 Rev G

DECS-200 units are delivered with the global and setpoint passwords set at decs2. When a password is entered, software first checks for a match between the entered password and the global password. Because the two passwords are the same, global access is always granted. This means that in order to allow setpoint access only, the global and setpoint passwords must be changed so that they are not the same. Passwords may be changed using BESTCOMS software. It is suggested that the user change the passwords in order to provide security against unauthorized parameter changes. Once changed, the passwords should be stored in a secure location. CAUTION Pressing the Edit and Reset pushbuttons during DECS-200 power-up will cause all user-programmed settings to be replaced with the default settings. If the user-defined passwords are lost or forgotten, the default passwords may be restored by simultaneously pressing the Edit and Reset pushbuttons during power-up of the DECS-200. Restoring the passwords to the default values will also change all previously programmed settings to the default values. Before restoring the default passwords (and settings), all DECS-200 settings should be downloaded to a file by using BESTCOMS software. After the default settings are loaded, the user-programmed settings can be uploaded to the DECS-200 from the saved settings file. The user may also reprogram the passwords. A password is required the first time any DECS-200 setting is changed or when the password access expires (after 10 minutes with no additional entries). If a user with settings access attempts to begin an edit session on a screen requiring global access, the settings access is revoked and the user is prompted to enter a password to gain global access.

METERING SCREEN
Information displayed by the metering screen is grouped into five field types: metering, setpoint, percent of range, mode message, and alarm annunciation. Metering Fields Three user-programmable fields display up to three different metering quantities at a given time. Table 24 lists the metering quantities that may be selected. Table 2-4. User-Selectable Metering Quantities Metering Labels Va-b Vb-c Vc-a Vavg Line I VA Watts Var PF Gen Hz Bus Hz Bus V Fld V Fld I V Aux EDM OD EDM SD 9360100990 Rev G Metering Quantities Generator A-B (L-L) rms voltage Generator B-C (L-L) rms voltage Generator C-A (L-L) rms voltage Average of three generator L-L voltages Generator line current Generator load VA Generator load watts Generator load var Generator load power factor Generator frequency Bus frequency Bus rms L-L voltage Field voltage Field current Voltage proportional to auxiliary input Open exciter diode ripple Shorted exciter diode ripple DECS-200 Human-Machine Interface 2-9

The values in all three metering fields are automatically scaled by an autoranging function to display up to four digits of resolution, a decimal point, and if needed, a multiplier such as k for 1,000 or M for 1,000,000. For negative values with magnitudes greater than 999.9, only three digits of resolution are displayed. Setpoint Field The setpoint field displays the setpoint for the present mode of operation. Table 2-5 lists the relationship between the operating mode and the setpoint field quantity. Table 2-5. Setpoint Field as a Function of Operating Mode Operating Mode Off Voltage Matching FCR (Manual) AVR (Auto) Droop Var Control PF Control Setpoint Field Quantity Setpoint from last mode AVR setpoint FCR setpoint AVR setpoint AVR setpoint Var setpoint PF setpoint Mode Message UNIT IS OFF VOLTAGE MATCHING FCR (MANUAL) AVR (AUTO) DROOP VAR CONTROL POWER FACTOR CONTROL

Percent-of-Range Field The percent-of-range field displays the setpoint expressed as a percentage of the available adjustment range. This relationship is linear. For example, a setpoint that is midway between minimum and maximum would be displayed as 50.0%. A setpoint that is at the maximum limit would be displayed as 100%. Mode Message Field The bottom of the metering screen contains the mode message field which displays a message indicating the DECS-200s current mode of operation. Alarm Annunciation Field The alarm annunciation field, located directly below the metering fields, remains blank during normal operating conditions. When an alarm condition occurs, the message ALARMS (PRESS < OR >) appears in the alarm annunciation field. The message appears as an inverse displaylight colored characters appear on a dark background. See Alarm Message Screen for information about how to identify which alarm condition was annunciated. Alarm Message Screen From the metering screen, pressing either the Left or Right scrolling pushbutton will cause the alarm message screen to appear. This screen displays up to six messages identifying the conditions that led to the most recent annunciations. Table 2-6 lists the messages that may appear as annunciations on the alarm message screen. When more than one message is listed, the newest annunciations are appended to the bottom of the list. Once the list contains six messages, any further annunciations will cause the oldest messages to be deleted from the top of the list. Table 2-6. Annunciation Messages Annunciation Message FIELD OVERVOLTAGE FIELD OVERCURRENT GEN. UNDERVOLTAGE GEN. OVERVOLTAGE UNDERFREQUENCY OVEREXCITATION LIMIT 2-10 Duration of Message Maintained until reset Maintained until reset Maintained until reset Maintained until reset Clears 2 s after end of event Clears 2 s after end of event 9360100990 Rev G

DECS-200 Human-Machine Interface

Annunciation Message UNDEREXCITATION LIMIT LOST VOLTAGE SENSING FAILED TO BUILD UP SYSTEM BELOW 10 HZ EXCITER DIODE OPEN EXCITER DIODE SHORT

Duration of Message Clears 2 s after end of event Maintained until reset Clears 2 s after end of event Maintained until reset Maintained until reset Maintained until reset

Once the list of annunciation messages has been viewed, it may be cleared by pressing the Reset pushbutton. If a condition that LED to an annunciation is still present when the alarm message screen is cleared, then a new annunciation message will be generated. Pressing the Reset pushbutton will also send the display back to the Metering screen. Furthermore, the alarms message on the Metering screen will also be cleared. However, if the user leaves the alarm message screen by pressing the Left, Right or Up scrolling pushbuttons, then the annunciation messages list remains intact. This allows the user to maintain a short history of annunciations. In addition, the alarms message on the Metering screen will also remain. The disadvantage of this is that the metering screen would no longer indicate that a new annunciation occurred because the alarms message would always be present. Screens with Special Editing Modes There are several screens that operate differently while in the edit mode. OPERATE_1 (1.1), BAUD_RATE (8.1.1), and MODBUS (8.1.2) are examples of such screens. In each case, any changes made to a setting are not used by the system (nor saved in nonvolatile memory) until the Edit pushbutton is pressed again. The programmable inputs for output relays 1 through 4 work in the same manner. These are on screens RELAY_1 (7.5.1) through RELAY_3B (7.5.9). The REG_GAIN (3.1) screen also operates in a different manner when in the Edit mode. The first four parameters on this screen represent a table containing twenty sets of predefined PID values and one set of user-definable values. The first of these, STAB SET #, which means stability settings number, is the index to the table. The second, third, and fourth parameters (AVR/FCR Kp, Ki, and Kd), are the actual entries in the table. Stability setting numbers 1 to 20 are the predefined values, and 21 is the set of userdefinable values. Editing these parameters works as follows: As long as STAB SET # is set to 21, then AVR/FCR Kp, Ki, and Kd may be individually edited and customized. The values displayed are not used by the system until they are saved by pressing the Edit pushbutton. This means that if a change is aborted by pressing the Reset pushbutton, the PID numbers currently being used by the system remain unchanged. If STAB SET # is 1 to 20, then AVR/FCR Kp, Ki and Kd may not be edited from the display (although the cursor can be moved to their display fields). If the STAB SET # is changed, the values shown in the display fields will not change until the selected STAB SET # is saved. When the STAB SET # is saved, the table entries are saved, used by the system and displayed on the LCD. If the DECS-200 is using the user-defined values previously set at STAB SET # 21 and a STAB SET # of 1 to 20 is saved, the user-defined values are lost. The next time that user-defined values for STAB SET # 21 are required, they must be manually entered and then saved. It is assumed that the table entries for STAB SET # 1 to 20 will be used as starting points from which users will arrive at their own customized values after the selected starting point has been saved (and thus copied into STAB SET # 21). Menu Tree The menu tree has eight branches: 1. OPERATING. Displays mode status and on or off status (AVR, FCR, var, PF, etc.) 2. SETPOINTS. Display and setting of mode values (AVR, FCR, var, PF, etc.) 3. LOOP GAINS. Loop gains for each element are set here (Kp, Ki, Kd, Kg) 4. METERING. Real-time metering of user-selected values and alarm messages. 5. PROTECTION. Display and setting of protective function parameters such as pickups. 6. LIMITERS. Display and setting of system limiters (OEL, UEL, etc.) 9360100990 Rev G DECS-200 Human-Machine Interface 2-11

7. SYSTEM PARAMETERS. Display and setting of system parameters. This menu item consists of nine sub-branches: Generator Data Field Data Transformers Configuration Output Contacts Traverse Rates Pre-position Modes Startup Tracking

8. GENERAL SETTINGS. Display and setting of communication setting parameters and LCD contrast. Figures 2-2 through 2-11 illustrate all branches in the menu tree. In Figures 2-2 through 2-11, the upper left corner of each screen displays a one, two or three digit number with decimal points between each digit. These numbers are reference numbers to the screens in the menu tree. A letter at the upper right corner (G, S, and N) indicates the security access level (global, setpoint and not applicable) required to edit that screen.

Figure 2-2.Operating Menu Branch

2-12

DECS-200 Human-Machine Interface

9360100990 Rev G

Figure 2-3. Setpoint Menu Branch

9360100990 Rev G

DECS-200 Human-Machine Interface

2-13

Figure 2-4. Loop Gains Menu Branch

2-14

DECS-200 Human-Machine Interface

9360100990 Rev G

Figure 2-5. Metering Menu Branch

9360100990 Rev G

DECS-200 Human-Machine Interface

2-15

Figure 2-6. Protection Menu Branch

2-16

DECS-200 Human-Machine Interface

9360100990 Rev G

Figure 2-7. Limiters Menu Branch

9360100990 Rev G

DECS-200 Human-Machine Interface

2-17

Figure 2-8. System Parameters Menu Branch (Part 1 of 3)

2-18

DECS-200 Human-Machine Interface

9360100990 Rev G

Figure 2-9. System Parameters Menu Branch (Part 2 of 3)

9360100990 Rev G

DECS-200 Human-Machine Interface

2-19

Figure 2-10. System Parameters Menu Branch (Part 3 of 3)

2-20

DECS-200 Human-Machine Interface

9360100990 Rev G

Figure 2-11. General Settings Menu Branch

9360100990 Rev G

DECS-200 Human-Machine Interface

2-21

FRONT PANEL OPERATION


The following paragraphs describe the settings and adjustments that are available via the DECS-200 front panel. They are grouped into eight main categories which include: operating modes, setpoints, loop gains, metering, protection, limiters, system parameters, and general settings. Front panel settings and adjustments are listed and described in the following paragraphs. Settings are organized by category and by screen. Operating Modes Screen: \OPER\OPERATE_1 (1.1) START/STOP - starts and stops the regulator AVR OR FCR - selects the regulator mode: AVR for automatic voltage regulator, FCR for field current regulator (also known as MANUAL mode) PF OR var - selects the controller mode: OFF for none, var for var control, PF for power factor control LOAD COMP - selects the load compensation type: OFF for none, DROOP for voltage droop. PRE-POSITION - enables/disables the pre-position function: OFF to disable, ON to enable Screen: \OPER\OPERATE_2 (1.2) VOLT MATCH - turns the voltage matching function on and off (Internal tracking between modes) INT TRACK - turns the internal tracking function on and off EXT TRACK - turns the external tracking function on and off UF OR V/HZ - selects either underfrequency or volts-per-hertz limiting Setpoints Screen: \SETPT\MODE_SET (2.1) AVR MODE - the automatic voltage regulation setpoint in actual generator voltage FCR MODE - the field current regulation setpoint in Amps DROOP - the amount of voltage droop as a % of rated generator voltage when the kvar load numerically equals the rated kW Var MODE - the var controller regulation setpoint in var PF MODE - the power factor controller regulation setpoint Screen: \SETPT\MODES\RANGE_1 (2.1.1) FINE V BD - the adjustable voltage band (var volt band) around the generator's output voltage as a % of rated generator voltage when var/PF mode is active AVR MIN - the minimum automatic voltage regulator setpoint as a % of rated generator voltage AVR MAX - the maximum automatic voltage regulator setpoint as a % of rated generator voltage FCR MIN - the minimum field current regulator setpoint as a % of rated field current FCR MAX - the maximum field current regulator setpoint as a % of rated field current Screen: \SETPT\MODES\RANGE_2 (2.1.2) MIN var OUT - the minimum generated var setpoint as a numerical % of rated generator kW (negative for absorbing) MAX var OUT - the maximum generated var setpoint as a numerical % of rated generator kW (negative for absorbing) MAX LAG PF - maximum lagging power factor setpoint MAX LEAD PF - maximum leading power factor setpoint V MATCH BD - the adjustable voltage band allows the voltage matching function to activate if the bus voltage is within this band. This setting is a numerical % of rated generator voltage. V MATCH REF - (Gen to Bus PT Match Level) the bus voltage setpoint for the voltage matching function as a numerical % of bus voltage 2-22 DECS-200 Human-Machine Interface 9360100990 Rev G

Screen: \SETPT\PREP_SET (2.2) The present control mode operating setpoint is driven to the pre-position value when the unit receives a pre-position command. AVR MODE - the automatic voltage regulator setpoint pre-position value FCR MODE - the field current regulator setpoint pre-position value Var MODE - the var controller setpoint pre-position value PF MODE - the power factor setpoint pre-position value Loop Gains Screen: \GAIN\REG_GAIN1 (3.1) STAB RANGE - the index into the internally defined PID table. Table 2-7 lists the automatic pre-defined stability gain settings for the exciter field and the 20 stability settings. AVR/FCR Kp - proportional gain coefficient used in the AVR/FCR loop AVR/FCR Ki - integral gain coefficient used in the AVR/FCR loop AVR/FCR Kd - derivative gain coefficient used in the AVR/FCR loop AVR/FCR Td - derivative time constant used in AVR/FCR loop Table 2-7. Automatic Stability Range Gain Settings Index Generator Open Circuit Time Constant (Tdo) 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 7.0 7.5 8.0 8.5 9.0 9.5 10.0 10.5 Generator Exciter Time Constant (Texc) 0.17 0.25 0.33 0.42 0.50 0.58 0.67 0.75 0.83 0.92 1.00 1.08 1.17 1.25 1.33 1.42 1.50 1.58 1.67 1.75

Excitation Mode

Setting 1 2 3 4 5 6 7 8

Kp 42.20 66.50 87.16 104.50 119.00 131.30 141.80 150.90 158.80 165.70 171.80 177.20 182.10 186.50 190.50 194.10 197.40 200.40 203.20 205.70

Ki 115.20 150.00 167.90 175.80 177.80 176.40 173.10 168.80 163.90 158.70 153.60 148.50 143.60 138.90 134.40 130.10 125.90 122.10 118.40 114.80

Kd 4.433 8.750 13.670 18.960 24.500 30.220 36.060 42.000 48.010 54.080 60.200 66.350 72.540 78.750 84.980 91.230 97.500 103.800 110.100 116.400

Exciter Field

9 10 11 12 13 14 15 16 17 18 19 20

Screen: \GAIN\REG GAIN2 (3.2) AVR Kg - loop gain used in AVR mode FCR Kg - loop gain used in FCR mode 9360100990 Rev G DECS-200 Human-Machine Interface 2-23

Screen: \GAIN\LIM_GAINS (3.3) OEL Ki - integral gain coefficient used in the overexcitation limiter loop OEL Kg - loop gain used in the overexcitation limiter UEL Ki - integral gain coefficient used in the underexcitation limiter loop UEL Kg - loop gain used in the underexcitation limiter SCL Ki - integral gain coefficient used in the stator current limiter SCL Kg - loop gain used in the stator current limiter Controller Gains Screen: \GAIN\CTL_GAINS (3.4) PF Ki - integral gain coefficient used in the power factor controller PF Kg - loop gain used for the power factor controller Var Ki - integral gain coefficient used in the var controller Var Kg - loop gain used for the var controller V MATCH Kg - loop gain used for the voltage matching function Metering Screen: \METER\ADJUST (4.1) 1st metering field - displays any one of several metering quantities 2nd metering field - displays any one of several metering quantities 3rd metering field - displays any one of several metering quantities SETPT - the present control mode operating setpoint Screen: \METER\ALARM_MSG (4.2) Reset Button - clears any displayed alarm messages (and returns to the ADJUST metering screen). Protection Screen: \PROT\UNDERFREQ (5.1) CORNR FREQ - the corner frequency for the underfrequency curve UF SLOPE - the slope of the underfrequency curve Screen: \PROT\PROT_ENABL1 (5.2) FIELD OV - field overvoltage detection enable FIELD OC - field overcurrent detection enable STATOR OV - generator output overvoltage detection enable STATOR UV - generator output undervoltage detection enable NO SENSING loss of voltage sensing detection enable NO SNSFCR transfer to FCR mode enable (when a loss of voltage sensing is detected). Loss of voltage sensing detection must also be enabled for this feature to work. Screen: \PROT\PROT_ENAB2 (5.3) EX DIOD OD - exciter open diode detection enable EX DIOD SD - exciter shorted diode detection enable LOSS FIELD - enables and disables loss of field protection Screen: \PROT\PROT_LEVL (5.4) FIELD OV - field overvoltage threshold FIELD OC - field overcurrent base value (100%) STATOR OV - generator output overvoltage threshold STATOR UV - generator output undervoltage threshold 2-24 DECS-200 Human-Machine Interface 9360100990 Rev G

EDM OD RIPL - open exciter diode ripple threshold EDM SD RIPL - shorted exciter diode ripple threshold Screen: \PROT\PROT_LEVL2 (5.5) EDM INH LVL - exciter diode detection inhibit level LOS BAL V - loss of balanced sensing voltage threshold LOS IMBAL V - loss of unbalanced sensing voltage threshold LOSS FIELD - loss of field time delay Screen: \PROT\PROT_TIMER (5.6) FIELD OV - field overvoltage time delay FIELD OC TD - field overcurrent time dial multiplier STATOR OV - generator output overvoltage time delay STATOR UV - generator output undervoltage time delay NO SENSING - lost sensing voltage time delay EX DIOD OD - exciter open diode time delay Screen: \PROT\PROT_TIMR2 (5.7) EX DIOD SD - exciter shorted diode time delay LOSS FIELD - loss of field time delay Limiters Screen: LIMITERS (6.0) ENABLED - selects which limiters are enabled: NONE, UEL, OEL, OEL/UEL, SCL, SCL/UEL, SCL/OEL, or SCL/OEL/UEL Screen: \LIMIT\OPTION (6.1) On-line overexcitation limiter style and options. OEL STYLE - selects Summing Point or Takeover style overexcitation limiter OEL OPTION - selects on-line and off-line overexcitation limiter control options: Option 1: On-line OEL settings are active when either the 52 J/K or 52 L/M contacts are open. Off-line OEL settings are active when either the 52 J/K or 52 L/M contacts are closed. Option 2: On-line OEL settings are active when the 52 J/K contact is open. Off-line OEL settings are active when the 52 J/K contact is closed. Option 3: On-line OEL settings are active at all times. Screen: \LIMIT\ONLINE (6.2) On-line overexcitation limiter (summing point) settings. INST LIMIT - on-line overexcitation limiter instantaneous limit threshold INST TIME - on-line overexcitation limiter instantaneous limit time delay MED LIMIT - on-line overexcitation limiter medium current threshold MED TIME - on-line overexcitation limiter medium current time delay CONT LIMIT - on-line overexcitation limiter continuous (low) current threshold Screen \LIMIT\OFFLINE (6.3) Off-line overexcitation limiter (summing point) settings. OEL HI LIM - off-line overexcitation limiter high current threshold HI LIM TIME - off-line overexcitation limiter high current time delay OEL LO LIM - off-line overexcitation limiter low current threshold

9360100990 Rev G

DECS-200 Human-Machine Interface

2-25

Screen \LIMIT\OFFTAKOVR (6.4) Off-line overexcitation limiter (takeover) settings. OEL MAX CUR - off-line takeover overexcitation limiter maximum current threshold OEL MIN CUR - off-line takeover overexcitation limiter minimum current threshold OEL TD - off-line takeover overexcitation limiter time delay Screen \LIMIT\ONTAKOVR (6.5) On-line overexcitation limiter (takeover) settings. OEL MAX CUR - on-line takeover overexcitation limiter maximum current threshold OEL MIN CUR - on-line takeover overexcitation limiter minimum current threshold OEL TD - on-line takeover overexcitation limiter time delay Screen \LIMIT\UEL_CRV_X (6.6) Underexcitation limiter real-power curve points. PNT 1 WATTS - underexcitation limiter real-power curve point 1 PNT 2 WATTS - underexcitation limiter real-power curve point 2 PNT 3 WATTS - underexcitation limiter real-power curve point 3 PNT 4 WATTS - underexcitation limiter real-power curve point 4 PNT 5 WATTS - underexcitation limiter real-power curve point 5 Screen \LIMIT\UEL_CRV_Y (6.7) Underexcitation limiter reactive-power curve points. PNT 1 vars - underexcitation limiter reactive-power curve point 1 PNT 2 vars - underexcitation limiter reactive-power curve point 2 PNT 3 vars - underexcitation limiter reactive-power curve point 3 PNT 4 vars - underexcitation limiter reactive-power curve point 4 PNT 5 vars - underexcitation limiter reactive-power curve point 5 Screen \LIMIT\SCLIM (6.8) Stator current limiter settings. SCL HI LIM - stator current limiter high current setpoint HI LIM TIME - stator current limiter time delay SCL LO LIM - stator current limiter low current setpoint System Parameters Screen: \GEN\GEN_DATA (7.1.1) RATED VOLT - generator rated output voltage RATED CURR - generator rated output current FREQUENCY - generator rated frequency Screen: \EXCTR\EXCTR_DATA (7.2.1) FIELD VOLT - rated field voltage FIELD CURR - rated field current POLE RATIO - ratio between exciter poles to the number of generator poles Screen: \XFMRS\XFMR_DATA (7.3.1) GEN PT PRI - generator sensing transformer primary voltage rating GEN PT SEC - generator sensing transformer secondary voltage rating BUS PT PRI - bus sensing transformer primary voltage rating BUS PT SEC - bus sensing transformer secondary voltage rating 2-26 DECS-200 Human-Machine Interface 9360100990 Rev G

GEN CT PRI - generator sensing transformer primary current rating GEN CT SEC - generator sensing transformer secondary current rating Screen: \CONFG\CNFG_DATA (7.4.1) SENSING - sensing configuration: single-phase or three-phase AUX IN TYPE - selects the auxiliary input type as voltage or current CRSS I GAIN - cross current compensation input gain Screen: \CNFG AUX Gains (7.4.2) The auxiliary input allows an analog signal to be externally applied to the DECS-200 to modify the operating setpoint. The amount of change that may be induced is proportional to the magnitude of the signal and the input gain. AVR MODE auxiliary input gain in AVR mode FCR MODE auxiliary input gain in FCR mode Var MODE auxiliary input gain in var mode PR MODE auxiliary input gain in PF mode INNER/OUTER control loop summing point location where the auxiliary input signal is to be injected. For AVR or FCR mode, select INNER. For var or PF mode, select outer. Once selected, the injection point remains fixed across all modes of operation. Screen: \CNTCT\RELAY_1 (7.5.1) There are three types of relay annunciation: momentary, maintained and latched. A relay that is programmed for momentary annunciation will do so for a (programmable) time interval and then cease. The momentary annunciation for an existing condition will not repeat. A relay that is programmed for maintained annunciation will do so for the duration of the condition that is being annunciated. A relay programmed for a latched annunciation will continue to annunciate the condition until an alarm reset command is given through the front panel, BESTCOMS software (via the front RS-232 port) or Modbus (via the rear RS-485 port). OUTPUT SENSE - relay 1 contact normal state: NO for normally open, NC for normally closed OUTPUT TYPE - type of contact annunciation: MOMENT for momentary, MAINTN for maintained, LATCHED for latched MOMENT TIME - the duration of a momentary annunciation FIELD O/V - assignment of field overvoltage annunciation to output relay 1 FIELD O/C - assignment of field overcurrent annunciation to output relay 1 STATOR U/V - assignment of stator undervoltage annunciation to output relay 1 Screen: \CNTCT\RELAY_1A (7.5.2) STATOR O/V - assignment of stator overvoltage annunciation to output relay 1 UNDER FREQ - assignment of underfrequency annunciation to output relay 1 IN OEL - assignment of overexcitation limit annunciation to output relay 1 IN UEL - assignment of underexcitation limit annunciation to output relay 1 IN FCR MODE - assignment of FCR mode (Manual) annunciation to output relay 1 NO V SENSE - assignment of lost voltage sensing annunciation to output relay 1 Screen: \CNTCT\RELAY_1B (7.5.3) AT LO LIMIT - assignment of setpoint at low limit annunciation to output relay 1 AT HI LIMIT - assignment of setpoint at high limit annunciation to output relay 1 BELOW 10 HZ - assignment of generator frequency below 10 hertz annunciation to output relay 1 EXC DIOD OD - assignment of open exciter diode to output relay 1 EXC DIOD SD - assignment of shorted exciter diode to output relay 1 LOSS FIELD - enables and disables annunciation of loss of field protection

9360100990 Rev G

DECS-200 Human-Machine Interface

2-27

Screen: \CNTCT\RELAY_1C (7.5.4) IN SCL - enables and disables stator current limiting annunciation Screen: \CNTCT\RELAY_2 (7.5.5) OUTPUT SENSE - relay 2 contact normal state: NO for normally open, NC for normally closed OUTPUT TYPE - duration of contact annunciation: MOMENT for momentary, MAINTN for maintained, LATCHED for latched MOMENT TIME - the duration of a momentary annunciation FIELD O/V - assignment of field overvoltage annunciation to output relay 2 FIELD O/C - assignment of field overcurrent annunciation to output relay 2 STATOR U/V - assignment of stator undervoltage annunciation to output relay 2 Screen: \CNTCT\RELAY_2A (7.5.6) STATOR O/V - assignment of stator overvoltage annunciation to output relay 2 UNDER FREQ - assignment of underfrequency annunciation to output relay 2 IN OEL - assignment of overexcitation limit annunciation to output relay 2 IN UEL - assignment of underexcitation limit annunciation to output relay 2 IN FCR MODE - assignment of FCR mode (manual) annunciation to output relay 2 NO V SENSE - assignment of lost voltage sensing annunciation to output relay 2 Screen: \CNTCT\RELAY_2B (7.5.7) AT LO LIMIT - assignment of setpoint at low limit annunciation to output relay 2 AT HI LIMIT - assignment of setpoint at high limit annunciation to output relay 2 BELOW 10 HZ assignment of generator frequency below 10 hertz annunciation to output relay 2 EXC DIOD OD - assignment of open exciter diode to output relay 2 EXC DIOD SD - assignment of shorted exciter diode to output relay 2 Screen: \CNTCT\RELAY_2C (7.5.8) IN SCL - enables and disables stator current limiting annunciation Screen: \CNTCT\RELAY_3 (7.5.9) OUTPUT SENSE - relay 3 contact normal state: NO for normally open, NC for normally closed OUTPUT TYPE - duration of contact annunciation: MOMENT for momentary, MAINTN for maintained, LATCHED for latched MOMENT TIME - the duration of a momentary annunciation FIELD O/V - assignment of field overvoltage annunciation to output relay 3 FIELD O/C - assignment of field overcurrent annunciation to output relay 3 STATOR U/V - assignment of stator undervoltage annunciation to output relay 3 Screen: \CNTCT\RELAY_3A (7.5.10) STATOR O/V - assignment of stator overvoltage annunciation to output relay 3 UNDER FREQ - assignment of underfrequency annunciation to output relay 3 IN OEL - assignment of overexcitation limit annunciation to output relay 3 IN UEL - assignment of underexcitation limit annunciation to output relay 3 IN FCR MODE - assignment of FCR mode (Manual) annunciation to output relay 3 NO V SENSE - assignment of lost voltage sensing annunciation to output relay 3 Screen: \CNTCT\RELAY_3B (7.5.11) AT LO LIMIT - assignment of setpoint at low limit annunciation to output relay 3 AT HI LIMIT - assignment of setpoint at high limit annunciation to output relay 3 BELOW 10 HZ assignment of generator frequency below 10 hertz annunciation to output relay 3

2-28

DECS-200 Human-Machine Interface

9360100990 Rev G

EXC DIOD OD - assignment of open exciter diode to output relay 3 EXC DIOD SD - assignment of shorted exciter diode to output relay 3 Screen: \CNTCT\RELAY_3C (7.5.12) IN SCL - enables and disables stator current limiting annunciation Screen: \TRVRS\TRVRS_RATE (7.6.1) The traverse rate is the time required to adjust the present control mode setpoint from one extreme of the programmed adjustment range to the other extreme. AVR MODE - the automatic voltage regulator mode traverse rate FCR MODE - the field current regulator mode traverse rate Var MODE - the var control mode traverse rate PF MODE - the power factor control mode traverse rate Screen: \PMODE\PREP_MODE (7.7.1) The pre-position mode for the present control mode determines whether or not the unit will respond to further setpoint change commands once the operating setpoint is driven to the pre-position value. If the pre-position mode is set for MAINTAIN, then further setpoint change commands are ignored. If the preposition mode is set for RELEASE, then subsequent setpoint change commands are followed. AVR MODE - automatic voltage regulator pre-position mode FCR MODE - field current regulator pre-position mode Var MODE - var controller pre-position mode PF MODE - power factor controller pre-position mode Screen: \START\START_UP (7.8.1) SS LEVEL - soft start level SS TIME - soft start time Screen: \TRACK\TRACK_DATA (7.9.1) Internal tracking (autotracking) and external tracking (auto-transfer) INT RATE - the traverse rate of internal tracking from minimum setpoints to maximum setpoints INT DELAY - the time delay before internal tracking begins after it is turned on EXT RATE - the traverse rate of external tracking from minimum setpoints to maximum setpoints EXT DELAY - the time delay before external tracking begins after it is turned on General Settings Screen: \COMMS\BAUD_RATE (8.1.1) COM0 RS232 - the front panel RS232 communications port baud rate COM1 RS232 - the rear panel RS232 autotracking communications port baud rate COM2 RS485 - the rear panel RS485 Modbus communications port baud rate Screen: \COMMS\MODBUS (8.1.2) Settings for the rear panel RS485 Modbus communications port COM2 ADDR - device address COM2 DELAY - response delay time PARITY - parity: NONE, ODD, or EVEN STOP BITS - number of stop bits: 1 or 2 Screen: \SETUP\CONTRAST (8.2) Front panel LCD contrast setting

9360100990 Rev G

DECS-200 Human-Machine Interface

2-29

Screen: \D200\SETUP\CLOCK (8.3) TIME - displays and sets the current time DATE - displays and sets the current date Screen: \RTC\CLK_FORMAT (8.3.1) TIME FORMAT - selects the format for displaying time on Screen 8.3 DST FORMAT - selects the DECS-200 RTC for day light savings time DATE FORMAT - selects the format for displaying the date on Screen 8.3

2-30

DECS-200 Human-Machine Interface

9360100990 Rev G

SECTION 3 FUNCTIONAL DESCRIPTION


TABLE OF CONTENTS
SECTION 3 FUNCTIONAL DESCRIPTION ........................................................................................... 3-1 INTRODUCTION.................................................................................................................................... 3-1 FUNCTION BLOCK DESCRIPTIONS ................................................................................................... 3-1 Contact Input Circuits ......................................................................................................................... 3-2 Analog Inputs...................................................................................................................................... 3-3 Operating Power ................................................................................................................................ 3-4 Control Power..................................................................................................................................... 3-5 Analog-to-Digital Converter (ADC) ..................................................................................................... 3-5 Microprocessor ................................................................................................................................... 3-5 Digital Signal Processor (DSP) .......................................................................................................... 3-5 Operational Settings........................................................................................................................... 3-5 Watchdog Timer ................................................................................................................................. 3-5 Real-Time Clock ................................................................................................................................. 3-5 Pulse-Width Modulated (PWM) Output .............................................................................................. 3-5 Relay Output Circuits ......................................................................................................................... 3-5 Communication................................................................................................................................... 3-6 Memory Circuits.................................................................................................................................. 3-7 Protection Functions........................................................................................................................... 3-7 SOFT START......................................................................................................................................... 3-9 LIMITER FUNCTIONS......................................................................................................................... 3-10 Underfrequency Limiter .................................................................................................................... 3-10 Volts per Hertz Ratio Limiter ............................................................................................................ 3-11 Overexcitation Limiter (OEL) ............................................................................................................ 3-11 Underexcitation Limiter..................................................................................................................... 3-13 Stator Current Limiting ..................................................................................................................... 3-13 DROOP AND LINE-DROP COMPENSATION .................................................................................... 3-14 DATA LOGGING AND REPORTING .................................................................................................. 3-14 Sequence of Events Reporting......................................................................................................... 3-14 Oscillography.................................................................................................................................... 3-15 Figures Figure 3-1. Simplified Block Diagram ........................................................................................................ 3-1 Figure 3-2. Field Overcurrent Timing Curves ............................................................................................ 3-7 Figure 3-3. Soft Start Voltage Reference ................................................................................................ 3-10 Figure 3-4. Typical Underfrequency Compensation Curve ..................................................................... 3-10 Figure 3-5. Typical 1.10 PU V/Hz Limiter Curve ..................................................................................... 3-11 Figure 3-6. Off-Line Overexcitation Limiting............................................................................................ 3-11 Figure 3-7. On-Line Overexcitation Limiting............................................................................................ 3-11 Figure 3-8. Inverse Time Characteristic for Takeover-Style OEL ........................................................... 3-12 Figure 3-9. Custom Five-Point Curve...................................................................................................... 3-13 Figure 3-10. Stator Current Limiting ........................................................................................................ 3-13 Figure 3-11. Data Record Example ......................................................................................................... 3-16 Tables Table 3-1. 52L/M and 52J/K Truth Table (Option 1, Default Settings) ...................................................... 3-3

9360100990 Rev G

DECS-200 Functional Description

This page intentionally left blank.

ii

DECS-200 Functional Description

9360100990 Rev G

SECTION 3 FUNCTIONAL DESCRIPTION


INTRODUCTION
This section illustrates and describes the functional capabilities of the DECS-200.

FUNCTION BLOCK DESCRIPTIONS


The function blocks of the DECS-200 are illustrated in Figure 3-1 and described in the following paragraphs.
FLASH MEMORY

START STOP SECEN 52L/M AUTO FCR PRE-P RAISE LOW ER 52J/K ALRST

RAM

EEPROM

W TCHD

CONTACT INPUT CIRCUITS

FRONT PANEL KEYPAD

COM0 RS-232 PORT

ON/OF

RELAY OUTPUT CONTACTS

RLY3

RLY2

RLY1

ZCD ZCD
VCA VCA VAB

FRONT PANEL LEDS MICRO PROCESSOR

BUS GEN GEN

LINE IB LINE IA/C ACC V/I

ANALOG INPUT CIRCUITS ADC

FRONT PANEL LCD

COM1 RS-232 PORT

+5 VAC

VDC

POW ER SUPPLY

+12 -12 +24

W ATCH-DOG TIMER

COM2 RS-485 PORT

F+

P0003-19.vsd 03-09-01

DIGITAL SIGNAL PROCESSOR

CHOPPER (PW M)

F-

POW ER INPUT

Figure 3-1. Simplified Block Diagram

9360100990 Rev G

DECS-200 Functional Description

3-1

Contact Input Circuits Eleven contact input circuits, powered by isolated 12 Vdc, provide operational input control for the DECS200. If the start and stop inputs should become active at the same time, the stop input has priority. If the AVR and FCR inputs should become active at the same time, the FCR input has priority. Each of the eleven inputs, their functions, and types of input required are defined in the following paragraphs. Start This input accepts a momentary contact closure and enables the DECS-200. Once the DECS-200 is enabled, this input has no effect. Stop This input accepts a momentary contact closure and disables the DECS-200. Once the DECS-200 is disabled, this input has no effect. The Stop input also takes precedence over the Start input. AVR (Automatic Voltage Regulation) This input accepts a momentary contact closure that places the DECS-200 in AVR mode. Once the DECS-200 is in AVR mode, this input has no effect. FCR (Field Current Regulation) This input accepts a momentary contact closure that places the DECS-200 in FCR mode. Once the unit is in FCR mode, this input has no effect. The FCR input takes precedence over the AVR input. Raise This input increases the active operating setpoint. This function is active as long as the contact is closed. The raise increment is a function of the setpoint range of adjustment and the active mode traverse rate. The increments are directly proportional to the adjustment range and inversely proportional to the traverse rate. This input has no effect when the active pre-position mode is Maintain. Lower This input decreases the active operating setpoint. This function is active as long as the contact is closed. The lower increment is a function of the setpoint range of adjustment and the active mode traverse rate. The increments are directly proportional to the adjustment range and inversely proportional to the traverse rate. This input has no effect when the active pre-position mode is Maintain. PRE-P (Pre-Position) This input accepts a continuous contact closure that causes all setpoints to be changed to the preposition (predefined) value. If the active pre-position mode is Maintain, then the pre-position input will override the raise and lower inputs to maintain the setpoint at the pre-position value while the contact is closed. If the active pre-position mode is Release, then the pre-position input will change the setpoint to the pre-position value and respond to raise and lower inputs. If the non-active pre-position mode is Maintain and internal tracking is enabled, the non-active mode will maintain the non-active setpoint at the pre-position value and override the tracking function. If the nonactive pre-position is Release and internal tracking is enabled, then the pre-position input will change the setpoint to the pre-position value and respond to the tracking function. Typically, this input is connected to a 52b auxiliary contact on the generator breaker. When the generator breaker opens, all setpoints are forced to the pre-position settings. This is especially helpful if FCR mode is active and the generator is under a load. Utilizing a 52b contact will force the FCR setpoint to its preposition setting which could be preset to the generators no-load, nominal voltage. 52L/M (Unit/Parallel) This input informs the DECS-200 that the system is operating in single-unit operation or paralleled to another generator or power grid in droop mode. It also switches between which overexcitation limiter (offline limiter or on-line limiter) is activated when excitation levels exceed the OEL settings. This input is typically connected to a 52b auxiliary contact of the generator breaker and requires a continuous contact closure to switch modes. Refer to the 52J/K (Var/PF Enable) paragraph for more information. If both the 52L/M and 52J/K contact inputs are closed, AVR mode is active while the off-line overexcitation limiter is enabled and will limit if the settings are exceeded. This mode is intended for stand-alone (single unit) generator operation. SCL and UEL are disabled when both 52L/M and 52J/K contact inputs are closed.

3-2

DECS-200 Functional Description

9360100990 Rev G

If the 52L/M contact input is open and 52J/K contact input is closed, droop mode is active while the online overexcitation limiter is enabled and will limit if the settings are exceeded. This mode is intended for two or more generators paralleled together on an isolated bus (islanded) or paralleled directly to the utility grid. Cross-current compensation (CCC) can also be utilized in this contact configuration. However, this mode (CCC) is not intended for paralleling to the utility grid. If both 52L/M is open and 52J/K are open, var/power factor mode is active while the on-line overexcitation limiter is enabled and will limit if the settings are exceeded. This mode is intended for applications requiring var or power factor regulation when paralleled to the utility grid. Table 3-1 describes 52 L/M and 52 J/K contact functionality for default OEL option 1. OEL options 2 and 3 are discussed in Overexcitation Limiter, On-Line/Off-Line OEL Options. Table 3-1. 52L/M and 52J/K Truth Table (Option 1, Default Settings) DECS-200 Operating Mode 52L/M 52J/K Generator Operating Mode AVR mode active, off-line OEL enabled, no droop, no var/PF, SCL and UEL disabled Droop mode active, on-line OEL enabled, no var/PF Var/PF mode active, on-line OEL enabled 52J/K (Var/Power Factor Enable) This input accepts a continuous contact closure that disables var/power factor operation. An open contact enables the DECS-200 to control the generator reactive power in either the var or power factor modes. These functions must be enabled via HMI, BESTCOMS, or Modbus before use. For more information, refer to the 52L/M (Unit/Parallel) paragraphs. If neither var nor power factor mode is desired, it is recommended that a jumper wire be placed across the 52J/K and common terminals, and switch the 52L/M input with the generator breaker auxiliary contact (52b). SECEN (Secondary Enable) This input accepts a continuous contact closure and enables the DECS-200 unit as the secondary unit to another excitation control system. ALRST (Alarm Reset) This input accepts a momentary contact closure to clear all latched relay annunciations and front panel alarm messages. Analog Inputs The following analog inputs are used to sense the following quantities: Generator voltage (three-phase/single-phase) Bus voltage (single-phase) Phase B (line) current Cross current loop input Accessory input (remote setpoint control) Field voltage (internal) Field current (internal) Closed Closed Single unit/stand-alone

Open

Closed

Paralleled to the utility grid (droop) or two or more generators islanded (droop or cross-current comp.) Paralleled to utility grid

Open

Open

Generator Voltage Sensing Ranges The ac voltage sensing range of the DECS-200 is split into four operating ranges: 120 volts nominal, 240 volts nominal, 480 volts nominal, and 600 volts nominal. The range selection is the same for generator and bus voltages and is based on the secondary VT voltage for the generator voltage sensing. The 120volt range is selected if the generator secondary VT voltage is between 85 and 153 Vac. The 240 volts range is selected if the generator secondary VT voltage is between 170 and 300 Vac. The 480-volt range is selected if the generator secondary VT voltage is between 340 and 528 Vac. The 600-volt range is selected if the generator VT voltage is between 540 and 690 Vac.

9360100990 Rev G

DECS-200 Functional Description

3-3

Generator Voltage (VCA) The GEN VCA input senses the generator voltage across phases A and C and is used to estimate the generator rms voltage and frequency. This input is not internally isolated. Generator Voltage (VAB) The GEN VAB input senses the generator voltage across phases A and B and is used to estimate the generator rms voltage and frequency. This input is not internally isolated. Generator Voltage (VBC) The GEN VBC input senses the generator voltage across phases B and C and is used to estimate the generator rms voltage and frequency. This input is not internally isolated. Bus Voltage (BUS VCA) The BUS VCA input senses the bus voltage across phases A and C. This voltage is used to estimate the bus rms voltage and frequency. The BUS VCA input is not internally isolated. Phase B Line Current This internally isolated input is developed from a current transformer (CT) and used to calculate the Bphase generator line current. Cross-Current Loop Input This input is developed from a current transformer (CT) connected to phase B of a generator and used when generators are operating in cross-current compensation mode. Accessory Input (Remote Setpoint Control) This internally isolated input may be either an analog voltage (10 to +10 Vdc) or current (4 to 20 milliamperes). Separate terminals provide convenient terminations but only one input may be used in any application. This input is typically supplied by a power system stabilizer or similar device. The accessory voltage input signal changes the setpoint of the selected operating mode. This input may be in the range of 10 to +10 Vdc or 4 to 20 milliamperes. The input signal is named a voltage signal even though one input mode may be 4 to 20 milliamperes. When the current input mode is selected, the input current (4 to 20 milliamperes) is converted by the DECS-200 to 5 to +5 Vdc voltage signal. The following equation is used when converting current signals to voltage signals.

V AUX = 0.625(I 12 )
Where: VAUX is the voltage signal I is the current in milliamperes

The accessory voltage input signal is multiplied by the accessory gain setting. The gain setting is in the range of 99 to +99. If the gain is set to zero, the accessory voltage input signal is made inactive. The accessory voltage input can be active in all four operating modes. In AVR mode, the accessory voltage input signal is multiplied by the voltage gain setting which defines the setpoint change as a percentage of the rated generator voltage. In FCR mode, the accessory voltage input signal is multiplied by the current gain setting which defines the setpoint change as a percentage of the rated field current. In var mode, the accessory voltage input signal is multiplied by the var gain setting which defines the setpoint change as a percentage of the rated apparent power of the generator. In power factor mode, the accessory voltage input signal is multiplied by the power factor gain setting and divided by 100, which defines the power factor setpoint change. Field Current and Field Voltage These signals are sensed internally. The field voltage signal is used for field overvoltage protection. The field current signal is used for: off-line and on-line overexcitation limiting, auto-tracking, and field overcurrent protection. Operating Power The DECS-200 operating power input accepts three-phase or single-phase voltage over the range of 50 to 277 Vac (depending on the nominal field voltage) at 50 to 500 hertz. The input is rectified and filtered by the inputs low-pass filter, which feeds the chopper stage. Depending on the operating power applied, three nominal output voltages are possible: 32, 63, or 125 Vdc. 3-4 DECS-200 Functional Description 9360100990 Rev G

Control Power Control power may be either of two types: nominal 24/48 Vdc or nominal 120 Vac/125 Vdc. For the 120 Vac/125 Vdc control power type, both ac and dc input power voltage might be applied for redundant power supply operation. Refer to Section 1, General Information, Specifications, for voltage ranges. The power supply provides +5 Vdc, 12 Vdc, and +24 Vdc for the DECS-200 internal circuitry. When dual power sources are used, an isolation transformer is required for the ac input. Analog-to-Digital Converter (ADC) All analog input signals are brought to the input of the 12-bit ADC. Each input signal is sampled at a rate that is controlled by the digital signal processor (DSP). Microprocessor The microprocessor is the heart of the DECS-200 and performs control, computation, self-testing, and communication functions. The main processor (labeled microprocessor in Figure 3-1) generally performs low speed tasks such as protective functions, frequency measurements, communication, watchdog alarm, and other system functions. The microprocessor generates the PWM (pulse width modulated) control signal needed for chopper control and monitors its status. Digital Signal Processor (DSP) The DSP supports measurement, control (output and converters), metering functions, and filtering. It controls both the ADC and the digital-to-analog converter (DAC). All eight analog input signals from the ADC are filtered by the finite impulse response (FIR) filters. AC signals are also filtered by the infinite impulse response (IIR) filters and dc signals (field voltage and current) are filtered by averaging filters. The DSP provides the microprocessor with the signal defining the chopper duty cycle/PWM control. Operational Settings Operational settings that affect the system are stored in nonvolatile memory. These settings may be changed through BESTCOMS or the front panel interface. Password access is required to change settings. Settings may be viewed without obtaining password access. Watchdog Timer If the microprocessor fails for any reason, output pulses to the watchdog timer stop and, after a brief interval, the watchdog timer takes the system off line and closes the watchdog output contacts. Real-Time Clock The real-time clock is used by the event and data logging functions to timestamp events. Time can be displayed in either 12- or 24-hour formats and can be selected to allow for daylight saving time. Two date formats are available: d-m-y or m/d/y. All formats may be selected either through the front panel HMI or BESTCOMS. Any cycling of power to the DECS-200 will reset the clock. Pulse-Width Modulated (PWM) Output The pulse-width modulated signal provided by the microprocessor controls the field voltage by modulating the duty cycle of the chopper (power module). Relay Output Circuits There are five output relays. These relay outputs are controlled by the microprocessor and sustain seven amperes at 240 Vac. Each output relay has 300-volt surge protectors across the contacts to protect against arcing from inductive loads. Relay outputs one through three are fully programmable via all interfaces. Two output relays (one form A and one form B) have predetermined functions. All output relays are described in the following paragraphs. Programmable Outputs Output relays RLY1, RLY2, and RLY3 may be programmed using the front panel HMI, BESTCOMS software (using the front RS-232 port (COM0)) or through the Modbus protocol (using the left RS-485 port (COM2)). The three output relays labeled RLY1, RLY2, and RLY3 have the following programmable features. Selection of contact functionality (normally open or normally closed) DECS-200 Functional Description 3-5 9360100990 Rev G

Selection of output type (momentary, maintained for as long as the condition is present, or latched until reset) Program duration of momentary annunciation (from 0.1 to 5 seconds in 50 millisecond steps) Selection of conditions to be annunciated, including: o Field overvoltage o Field overcurrent o Generator undervoltage o Generator overvoltage o Volts per hertz or underfrequency limit o Overexcitation limit o Underexcitation limit o FCR mode o Loss of sensing (LOS) voltage o Active setpoint at low limit o Active setpoint at high limit o Generator frequency below 10 hertz o Open exciter diode o Shorted exciter diode o Loss of field o Stator current limit NOTE If the contacts of a programmable output relay are configured as normally closed, the normally closed contact state is maintained only while the DECS-200 has control power applied. When power is removed from the DECS-200, these contacts will open.

Watchdog Output The Watchdog (WTCHD) output indicates a software execution problem within the DECS-200. The contact closes under the following circumstances: No control power is applied to the DECS-200 After application of power for approximately eight seconds Software in the DECS-200 stops executing normally

On/Off Output The On/Off (ON/OF) output indicates the enabled/disabled status of the DECS-200. The On/Off output closes when the DECS-200 is enabled and opens when the DECS-200 is disabled. Communication The RS-232 port (Com 0), located on the front panel, is dedicated for communication with a PC running BESTCOMS software. The RS-232 port (Com 1), located on the right side of the unit, is dedicated for communication with a second DECS-200. This port provides tracking between units in a redundant DECS-200 system. The RS-485 Port (Com 2), located on the left side of the unit, is dedicated for communication in remote terminal unit (RTU) mode using the Modbus protocol. NOTE Changing the baud rate or data format while that interface is in use will result in a loss of data and probably a complete loss of communication. All three ports have a default baud rate of 9600. However, the baud rate for each port can be set independently. Available baud rates are 1200, 2400, 4800, 9600, and 19200. Ports Com ) and Com 1 use a data format of 8N1 which stands for 8 data bits, no parity, and 1 stop bit. Port Com 2 has a default data format of 8N2 but the parity and number of stop bits are programmable. The choices for parity include none, Odd, and Even. The number of stop bits may be either 1 or 2. 3-6 DECS-200 Functional Description 9360100990 Rev G

Memory Circuits There are three types of memory circuits: flash memory, random access memory (RAM) and electrically erasable programmable read-only memory (EEPROM). Flash memory is nonvolatile and stores the operating software. RAM is volatile and serves as temporary storage for data. EEPROM is nonvolatile and stores the settings and configuration. Protection Functions Eight protection functions are available in the DECS-200: Field overvoltage Loss of sensing Field overcurrent Generator frequency below 10 hertz Generator undervoltage Loss of field Generator overvoltage Exciter diode monitor Each protection function can be indicated locally on the front panel display, remotely through communication port Com 0 or Com 2, and any of the three programmable output relays. Field Overvoltage When the field voltage increases above the Exciter Field Overvoltage Level setting for the duration of the Field Overvoltage Delay setting, a field overvoltage condition is annunciated. A field overvoltage condition is annunciated on the front panel metering screen and may be assigned to a programmable output relay for external annunciation. The Exciter Field Overvoltage Level setting is adjustable from 1 to 325 Vdc in 1 Vdc increments. The Exciter Field Overvoltage Delay setting is adjustable from 0.2 to 30.0 seconds in 0.1 second increments. If the field overvoltage timer is timing down and the field voltage drops below the Exciter Field Overvoltage Level setting, the field overvoltage timer is reset. The field overvoltage function may be disabled without changing the level or time delay settings. Field Overcurrent When the field current increases above the Exciter Field Overcurrent Level setting for the duration of the Exciter Field Overcurrent Delay setting, a field overcurrent condition is annunciated. Field overcurrent is annunciated on the front panel metering screen and may be assigned to a programmable output relay for external annunciation. The Exciter Field Overcurrent Level and Exciter Field Overcurrent Delay settings are related by an inverse function. This means that the higher the field current goes above the threshold, the shorter the time to an annunciation. The Exciter Field Overcurrent Delay setting is a linear multiplier for the time to an annunciation. The Exciter Field Overcurrent Level setting is adjustable from 0.1 to 20 Adc in 0.1 Adc increments. The Exciter Field Overcurrent Delay setting is adjustable from 0.1 to 20.0 in increments of 0.1. The field overcurrent protection function may be disabled without changing the level or time delay settings. Figure 3-2 shows a set of typical field overcurrent timing curves. Notice that field current levels below 103% of the field overcurrent setpoint value are unpredictable and may not cause an annunciation. Also, field current levels greater than 250% (field current multiple of 2.5 in Figure 3-2) of the setpoint value cause an annunciation in the same amount of time as the 250% level.

Figure 3-2. Field Overcurrent Timing Curves 9360100990 Rev G DECS-200 Functional Description 3-7

Generator Overvoltage When the generator voltage increases above the Generator Overvoltage Level setting for the duration of the Generator Overvoltage Delay setting, a generator overvoltage condition is annunciated. A generator overvoltage condition is annunciated on the front panel metering screen and may be assigned to a programmable output relay for external annunciation. The Generator Overvoltage Level setting is adjustable from 0 to 30,000 Vac in 1 Vac increments. The Generator Overvoltage Delay setting is adjustable from 0.1 to 60.0 seconds in 0.1 second increments. If the generator voltage drops below the Generator Overvoltage Level setting while the delay timer is timing down, the delay timer is reset. Generator overvoltage protection may be disabled without changing the level or time delay settings. Generator Undervoltage When the generator voltage decreases above the Generator Undervoltage Level setting for the duration of the Generator Undervoltage Delay setting, a generator undervoltage condition is annunciated. A generator undervoltage condition is annunciated on the front panel metering screen and may be assigned to a programmable output relay for external annunciation. The Generator Undervoltage Level setting is adjustable from 0 to 30,000 Vac in 1 Vac increments. The Generator Undervoltage Delay setting is adjustable from 0.5 to 60.0 seconds in 0.1 second increments. If the generator voltage increases above the Generator Undervoltage Level setting while the delay timer is timing down, the delay timer is reset. Generator undervoltage protection may be disabled without changing the level or time delay settings. Loss of Sensing A loss of sensing voltage is annunciated when either of two conditions exist: All three phases of generator voltage decrease below the Loss of Sensing VoltageBalanced Level setting for the duration of the Loss of Sensing Voltage Time Delay setting. Any individual phase of generator sensing voltage differs by more than the Loss of Sensing Voltage Unbalanced Level setting for the duration of the Loss of Sensing Voltage Time Delay setting.

A loss of sensing voltage is annunciated on the front panel Metering screen and may be assigned to a programmable output relay for external annunciation. The Balanced and Unbalanced Level settings are adjustable from 0 to 100% in 0.1% increments. The Time Delay setting is adjustable from 0 to 30.0 seconds in 0.1 second increments. Below 10 Hertz When the generator frequency decreases below 10 hertz, the condition is annunciated on the front panel display as SYSTEM BELOW 10 Hz. The programmable output relays may be configured to initiate additional annunciations or actions. A system below 10-hertz annunciation is reset automatically when the generator frequency increases above 10 hertz. Loss of Field When the reactive power absorbed by the generator exceeds the Loss of Field Level setting for the duration of the Loss of Field Delay setting, a loss of field condition is annunciated. A loss of field is annunciated on the front panel metering screen and may be assigned to a programmable output relay for external annunciation. The Loss of Field Level setting is adjustable from 0 to 3,000 Mvar in 1 kvar increments. The Loss of Field Delay setting is adjustable from 0 to 9.9 seconds in 0.1 second increments. If the absorbed reactive power decreases below the Loss of Field Level setting while the delay timer is timing down, the delay timer is reset. Loss of field protection can be disabled without changing the level or time delay settings. Exciter Diode Monitor (EDM) The DECS-200 monitors the output of the brushless exciter power semiconductors through the exciter field current and protects against both open and shorted diodes in the exciter bridge. When implementing the EDM, it is imperative that the user know and specify the number of poles for the exciter armature and the number of poles for the generator rotor. NOTE If the number of poles for the exciter armature and the generator rotor is unknown, the EDM function will still operate. However, only a shorted diode can be detected. If the number of poles is not known, it is best to select all parameters for the exciter open diode to off. In this situation, the generator and exciter pole parameters must be set at zero to prevent false tripping. 3-8 DECS-200 Functional Description 9360100990 Rev G

The EDM function estimates the fundamental harmonic of the exciter field current using discrete Fourier transforms (DFTs). The harmonic, expressed as a percentage of the field current, is then compared to the trip levels for open diode detection (OD ripple) and shorted diode detection (SD ripple). If the percentage of field current exceeds the OD Level or SD Level setting, then the appropriate delay will begin. After the programmable delay for the OD or SD event expires, and if the percentage of field current still exceeds the OD Level or SD Level setting, the event is annunciated. An exciter diode failure is annunciated on the front panel HMI and can be assigned to a programmable output relay for external annunciation. EDM inhibit parameters prevent nuisance annunciations due to low excitation current or out-of-range generator frequency. The following parameters are required for complete operation of the EDM function. Pole ratio Trip level of EDM OD ripple Trip level of EDM SD ripple Exciter Diode Monitor Settings Open exciter diode delay Shorted exciter diode delay EDM inhibit level

It is especially difficult to detect open diode conditions when the number of generator and exciter poles is unknown. For this reason, the ratio of the number of poles for the brushless exciter armature to the generator rotor is entered to ensure proper operation for both open and shorted diode protection. Setting the Trip Level To set the trip level of the EDM OD (open diode) ripple and EDM SD (shorted diode) ripple parameters, the maximum ripple current on the field must be known. This can be accomplished by running the generator unloaded and at rated speed. Vary the generator voltage from minimum to maximum voltage while monitoring the EDM OD and EDM SD % ripple on the DECS-200 HMI metering screen. Record the highest value for each. See Section 2, Human-Machine Interface for more details on displaying metering quantities. With Number of Generator Poles Known Multiply the highest EDM OD value, obtained under Setting the Trip Level , by 3. The result is the Exciter Open Diode % Ripple Level (EDM OD % Ripple). The multiplier can be varied between 2 and 5 to increase or decrease the trip margin. However, reducing the multiplier could result in nuisance EDM OD indications. A time delay is also adjustable from 10 to 60 seconds. Multiply the highest EDM SD value, obtained under Setting the Trip Level by 50. The result is the Exciter Shorted Diode % Ripple Level (EDM SD % Ripple). The multiplier can be varied between 40 and 70 to increase or decrease the trip margin. However, reducing the multiplier could result in nuisance EDM SD indications. A time delay is also adjustable from 5 to 30 seconds. The DECS-200 has fixed EDM inhibit levels to prevent nuisance EDM indications while the generator sensing voltage is less than 45 Hz, greater than 70 Hz, or when the field current is less than 1 Adc. Although the user can adjust the field current inhibit level from 0 to 100%, the fixed EDM inhibit levels take priority. Pole ratios must be in the range of 1 to 10 with 0 used if the ratio is unknown. With Number of Generator Poles Unknown The DECS-200 can detect shorted diode conditions when the number of generator poles is not known. To provide this protection, disable EDM OD protection and set the pole ratio to zero. Enable EDM SD protection. Multiply the maximum EDM SD % ripple value, obtained under Setting the Trip Level, by 30. The multiplier can be varied between 20 and 40 to increase or decrease the trip margin. Reducing the multiplier could result in nuisance EDM SD indication. Test the EDM Settings Start the generator from a dead stop condition and increase its speed and voltage to the rated value. Load the machine to its rating and confirm no EDM alarm indications occur. All of the EDM setup guidelines presented here assume the exciter diodes were not opened or shorted at the time of setup and testing.

SOFT START
DECS-200 soft start capability provides for an orderly buildup of terminal voltage from residual to the voltage setpoint in the desired time with minimal overshoot. When the system is in startup, the voltage reference is adjusted by the amount calculated based on two parameters. These parameters are level and time. Soft start bias level is adjustable from 0 to 90 percent of the active mode setpoint in increments of 1 percent with a default setting of 5 percent. Soft start time is adjustable from 1 to 7,200 seconds in increments of 1 second with a default setting of 5 seconds. Figure 3-3 illustrates a plot of the voltage 9360100990 Rev G DECS-200 Functional Description 3-9

reference showing soft-start bias at 30%, soft-start time at 8 seconds and a voltage setpoint of 100%. Soft start level is the same parameter as soft-start bias when accessed on the Startup tab of the BESTCOMS System Settings screen.

Figure 3-3. Soft Start Voltage Reference

LIMITER FUNCTIONS
DECS-200 limiter functions include an underfrequency limiter, V/Hz ratio limiter, overexcitation limiter, underexcitation limiter, and a stator current limiter. Underfrequency Limiter When the generator frequency drops below the corner frequency for the underfrequency slope (Figure 3-4), the voltage setpoint is automatically adjusted by the DECS-200 so that generator voltage will follow the underfrequency slope and an underfrequency annunciation occurs. The underfrequency slope can be tuned to have zero to three times the volts/hertz slope in 0.01 increments. The corner frequency can be set across a range of 45 to 65 hertz in 0.1 hertz increments. This adjustability enables the DECS200 to precisely match the operating characteristics of the prime mover and the loads being applied to the generator. The generator underfrequency function may be effectively disabled by setting the slope to zero. However, if the system frequency is below the corner frequency, underfrequency will be annunciated even if the slope is set at zero.
Corner Frequency 100 %
P0004-34.vsd 12-03-01

GENERATOR VOLTS
0% 10 Hz Nominal

GENERATOR FREQUENCY
Figure 3-4. Typical Underfrequency Compensation Curve

3-10

DECS-200 Functional Description

9360100990 Rev G

When the underfrequency function is active, an underfrequency annunciation occurs. Underfrequency is annunciated on the front panel Metering screen and may be assigned to a programmable output relay for external annunciation. Volts per Hertz Ratio Limiter The volts per hertz ratio limiter prevents the regulation setpoint from exceeding the volts per hertz ratio that is prescribed by the slope setting of the DECS-200 as stated in the previous paragraphs. This feature is also useful for other potentially damaging system conditions such as a change in system voltage and reduced frequency situations that could exceed the systems volts per hertz ratio limit. Figure 3-5 illustrates a typical 1.10 PU volts per hertz limiter curve. Overexcitation Limiter (OEL) Overexcitation limiting operates in all modes except FCR mode. The DECS-200 senses the field current output and limits the field current to prevent field overheating. In FCR mode, the DECS-200 announces that all conditions for OEL are fulfilled. The DECS-200 provides two types of overexcitation limiting: Summing Point and Takeover. Summing Point OEL

110 % 100 %

P0004-33.vsd 12-03-01

GENERATOR VOLTS

0% 0 Hz Nominal

GENERATOR FREQUENCY
Figure 3-5. Typical 1.10 PU V/Hz Limiter Curve

FIELD CURRENT

Vo lts /H er tz

Ra tio

High Current Time 0-10sec

CONTINUOUS

Low Current Level 0-15Adc

High Current Level 0-30Adc

Two OEL current levels are defined for off-line 04-03-01 TIME IN SECONDS operation: high and low (see Figure 3-6). The generator can operate continuously at the low Figure 3-6. Off-Line Overexcitation Limiting OEL current level and for a programmed time at the high OEL current level. Three OEL current levels are defined for on-line operation: high, medium, and low (see Figure 3-7). The high and medium current levels can be maintained only for a user-defined amount of time. The generator can operate continuously at the low OEL current level.

D2851-18.vsd

FIELD CURRENT

High Current Time 0-10sec

Medium Current Time 0-120sec

CONTINUOUS

Low Current Level 0.0 - 15 Adc

High Current Level Medium Current 0.0 - 30Adc Level 0.0 - 20 Adc

TIME IN SECONDS
Figure 3-7. On-Line Overexcitation Limiting

D2851-17.vsd 04-03-01

The 52L/M (unit/parallel) contact input status determines which limiter is active (on-line or off-line). When the 52L/M input is closed, the off-line limiter is active. When the 52L/M input is open, the on-Line limiter setting is active. 9360100990 Rev G DECS-200 Functional Description 3-11

In addition to the three current levels, the DECS-200 also uses embedded timers to prevent excessive heating of the exciter field that may be a result of repetitive overexcitation conditions. A duration timer monitors the accumulated time actually spent in an overexcitation condition and a reset timer is used to count backward from either the High OEL Current Time setting or the sum of the high plus the Medium OEL Current Time setting depending on the duration timer value. The reset timer countdown begins when the excitation current falls below the low OEL current limit level. In the event a subsequent overexcitation condition occurs before the reset timer reaches zero, the OEL limiter will resume from its state prior to the excitation current falling below the low OEL current limit level. A full OEL cycle cannot occur until the reset timer has counted down to zero after a previous OEL condition. When the system is limiting overexcitation, an OEL condition is annunciated on the front panel Metering screen and may be assigned to a programmable output relay for external annunciation. Takeover OEL When takeover-style overexcitation limiting is used, the level of field current at which limiting occurs is determined by an inverse time characteristic. This inverse time characteristic is similar to that shown in Figure 3-8. Two current levels and a time dial setting are defined for the takeover OEL. Separate curves may be selected for on-line operation. If the system enters an overexcitation condition, the field current is limited and forced to follow the selected curve.

Figure 3-8. Inverse Time Characteristic for Takeover-Style OEL On-Line/Off-Line OEL Options Selection of on-line or off-line OEL levels/curves is determined by an OEL option selection. The following options are available. Option 1 (default). When option 1 is selected, on-line overexcitation limiter settings are active when either the 52J/K contact input or 52L/M contact input are open. Off-line OEL settings are active when both the 52J/K contact input and 52L/M contact input are closed. The 52J/K contact input can be used to switch between on-line OEL and off-line OEL when the 52L/M contact input is jumpered. If var/power factor correction is disabled, Droop mode will be active when the 52J/K contact input is opened and AVR mode will be active when the 52J/K contact input is closed. Option 2. Option 2 allows the 52J/K contact input to define when the off-line and on-line limiters are active. When option 2 is selected, on-line overexcitation limiter settings are active when the 52J/K contact input is open. Off-line OEL settings are active when the 52J/K contact input is closed. Option 2 is intended for cross-compound generator applications where both machines are paralleled at low rpm. Therefore, Droop mode needs to be active (52L/M contact input opened) as the speed of the machines are increased. However, off-line OEL settings for both machines need to be active. Option 3. When option 3 is selected, on-line overexcitation limiting settings are active at all times. Option 3 allows the DECS-200 to operate in AVR mode (stand-alone application) without restriction from the offline OEL settings. In this case, the on-line OEL settings are active to limit excessive excitation current. This option also eliminates the need for the DECS-200 to operate in Droop mode when applied in a single unit application. Therefore, voltage should not droop as reactive load increases.

3-12

DECS-200 Functional Description

9360100990 Rev G

Underexcitation Limiter Underexcitation limiting (UEL) operates in all modes except FCR mode. UEL senses the leading var output of the generator and limits any further decrease in excitation to prevent loss of synchronization and end-iron heating during parallel operation. In FCR mode, the DECS-200 announces that all conditions for UEL are fulfilled. The reactive power level is selected at zero active power and the UEL limiting curve is calculated based on this value and the generator voltage and current rating. Typical leading kvar curves and a user-selected, five-point curve are shown in 3-9.

Real Power Generate (W) x 1000 0.0 0.0 7.5k 15.0k 22.5k 30.0k 37.5k 45.0k

Reactive Power Absorb (var) x 1000

7.5k

15.0k

22.5k

30.0k

37.5k
D2851-25 06-28-05

45.0k
Figure 3-9. Custom Five-Point Curve When the system is limiting underexcitation, a UEL annunciation occurs. Underexcitation is annunciated on the front panel Metering screen and may be assigned to a programmable output relay for external annunciation. Stator Current Limiting The stator current limiter (SCL) senses the level of stator current and limits it to prevent stator overheating. The SCL operates in all modes except FCR. In FCR mode, the DECS-200 only announces that a stator overcurrent condition exists; it does not provide current limiting. Two SCL current levels are provided: high and low (see Figure 3-10). The generator can operate continuously at the low SCL level and for a programmed time at the high SCL level. The SCL will not respond until the SCL Initial Delay setting has expired.

STATOR CURRENT

High Current Time 0-60 s

Continuous

High Current Level Low Current 0-66,000 Aac Level 0-66,000 Aac
P0013-19 11-10-04

TIME IN SECONDS

Figure 3-10. Stator Current Limiting 9360100990 Rev G DECS-200 Functional Description 3-13

DROOP AND LINE-DROP COMPENSATION


Droop and line-drop compensation are accomplished through the load compensation equation:

VC1 = VT + (RC + jX C )I T
Where:
VC1 is the compensated output voltage VT is the measured terminal-voltage vector (Rc + jX C ) are the compensation impedance values
I T is the measured terminal-current vector

When the droop percentage is a positive quantity, reactive droop compensation is performed. Droop is the product of the output voltage and the kvar that the generator is exporting. This is equivalent to the above compensation equation with RC equal to zero and neglecting the real part of the vector, I T . When the droop percentage is a negative quantity, line-drop compensation (LDC) is preformed. LDC takes into account the real part of the vector, I T . Since LDC is typically used to compensate for reactive impedance losses in transformers, RC is assumed zero. For LDC, the above equation becomes:

VC1 = VT + ( jX C )I T
DATA LOGGING AND REPORTING
DECS-200 data logging and reporting features include a sequence of events recorder that records up to eight oscillography records. Sequence of Events Reporting A sequence of events recorder monitors the internal and external status of the DECS-200. Events are scanned at 50 millisecond intervals with 127 events stored per record. All changes of state that occur during each scan are time tagged. Sequence of events reports are available through BESTCOMS. All monitored events are listed below. System Contact Input State Changes Alarm reset Start AVR mode enable Stop FCR mode enable Unit/Parallel (52 L/M) Pre-Position VAR/PF enable (52 J/K) Secondary enable The 52 contacts are reported as disabled when the input is jumpered to common and reported as enabled when the input is not jumpered. All other contacts are reported as enabled when the inputs are jumpered to common. Relay 3 output Watchdog relay output

System Output State Changes On/Off relay output Relay 1 output Relay 2 output System Alarm State Changes Exciter diode open Exciter diode shorted Field overcurrent Field overvoltage Generator overvoltage Generator undervoltage Changes in State of System Status Auto tracking mode Control mode Limiter mode Load compensation mode Operating mode

Loss of field Lost voltage sensing Overexcitation limit Stator current limit Underexcitation limit Underfrequency Soft-start mode Stop/Start Underfrequency mode Voltage matching mode 9360100990 Rev G

3-14

DECS-200 Functional Description

Oscillography The data recording function of the DECS-200 can record up to eight oscillography records. Oscillography records recorded by the DECS-200 use the IEEE Standard Common Format for Transient Data Exchange (COMTRADE). Each record is time and date stamped. After eight records have been recorded, the DECS-200 begins recording the next record over the oldest record. Because all oscillography records are stored in volatile memory, the records will be lost if power is lost. A record consists of six user selectable variables with 600 data points recorded for each variable. The sample rate or time between data point samples is user selectable from 4 milliseconds to 10 seconds. Therefore, the recording duration for a variable can range from 2.4 seconds to 6,000 seconds. Data points may be selected for pre-trigger operation in order to capture events prior to a fault. Up to 599 pre-trigger data points may be selected. Data points that are not designated for pre-trigger recording are assigned to the post-trigger portion of the fault record. This feature combined with the adjustable sample rate allows for flexible data sampling around the fault. The DECS-200 monitors six user-selectable internal variables. The following internal variables may be selected: Internal Variables Auto tracking output (for future use) Auxiliary input voltage AVR Error Signal Bus frequency Bus voltage Control output Crosscurrent input Exciter field current Ifd Exciter field voltage Vfd Generator average L-L voltage Generator frequency Generator Ib in amps Generator kVA Generator kvar Generator kW Generator power factor Generator Vab Generator Vbc Generator Vca Generator V-I phase angle Internal PID Integrator State Typically, these are used when commissioning or troubleshooting.

Data recording may be triggered manually using BESTCOMS, logic triggers, or level triggers. Logic triggers allow data recording to occur because of an internal or external status change of the DECS-200. Level triggering allows the user to select triggering of a data record based on the value of one of the internal variables. The value can be a minimum or maximum value and can be specified to trigger a record when the monitored variable crosses a minimum threshold from above or a maximum threshold from below. A minimum and maximum threshold may also be selected for the monitored variable causing the monitored value to trigger a record when it goes above its maximum or falls below its minimum. Figure 3-11 shows an example of a data record as it would look when viewed with BESTwave software. The example illustrates a voltage step change while monitoring average voltage, field voltage, and field current over a time of 2.75 seconds. For more information about selecting triggering types or levels, selecting internal variables for monitoring or viewing oscillography records, see Section 5, BESTCOMS Software.

9360100990 Rev G

DECS-200 Functional Description

3-15

Figure 3-11. Data Record Example

3-16

DECS-200 Functional Description

9360100990 Rev G

SECTION 4 INSTALLATION
TABLE OF CONTENTS
SECTION 4 INSTALLATION .................................................................................................................. 4-1 GENERAL .............................................................................................................................................. 4-1 PRODUCT REGISTRATION ................................................................................................................. 4-1 MOUNTING............................................................................................................................................ 4-1 CONNECTIONS .................................................................................................................................... 4-6 Right-Hand Panel Connections .......................................................................................................... 4-6 Front Panel Connections.................................................................................................................... 4-7 Left-Hand Panel Connections ............................................................................................................ 4-7 Typical Connections ......................................................................................................................... 4-13 Figures Figure 4-1. Overall Dimensions ................................................................................................................. 4-2 Figure 4-2. Panel Drilling Diagram, Projection Mount ............................................................................... 4-3 Figure 4-3. Escutcheon Plate Dimensions ................................................................................................ 4-4 Figure 4-4. Panel Cutting and Drilling Dimensions, Panel Mount ............................................................. 4-5 Figure 4-5. DECS-200 to DECS-200 Communication Connections ......................................................... 4-6 Figure 4-6. DECS-200 Left-Side Terminals............................................................................................... 4-7 Figure 4-7. Typical Cross-Current Compensation Connections.............................................................. 4-10 Figure 4-8. RS-485 DB-37 to DECS-200 ................................................................................................ 4-12 Figure 4-9. Typical Connections.............................................................................................................. 4-13 Tables Table 4-1. Com 1 Pin Functions ................................................................................................................ 4-6 Table 4-2. Left-Hand Panel Terminal Specifications ................................................................................. 4-8 Table 4-3. Control Power Terminals.......................................................................................................... 4-8 Table 4-4. Operating Power Terminals ..................................................................................................... 4-8 Table 4-5. Generator and Bus Voltage Sensing Terminals....................................................................... 4-9 Table 4-6. Generator Current Sensing Terminals ..................................................................................... 4-9 Table 4-7. Accessory Input Terminals ..................................................................................................... 4-10 Table 4-8. Contact Input Terminals ......................................................................................................... 4-10 Table 4-9. Output Contact Terminals ...................................................................................................... 4-11 Table 4-10. Field Output Terminals ......................................................................................................... 4-11 Table 4-11. Com 2 Terminals .................................................................................................................. 4-11

9360100990 Rev G

DECS-200 Installation

This page intentionally left blank.

ii

DECS-200 Installation

9360100990 Rev G

SECTION 4 INSTALLATION
GENERAL
DECS-200 Digital Excitation Control Systems are delivered in sturdy cartons to prevent shipping damage. Upon receipt of a system, check the part number against the requisition and packaging list for agreement. Inspect for damage, and if there is evidence of such immediately file a claim with the carrier and notify the Basler Electric Regional Sales Office, your sales representative or a sales representative at Basler Electric, Highland, Illinois. If the unit is not installed immediately, store it in the original shipping package in a moisture- and dust-free environment.

PRODUCT REGISTRATION
Registering with Basler Electric enables you to receive important information updates on your product plus new product announcements. Register your product by directing your web browser to http://www.basler.com/Register.

MOUNTING
The orientation of the DECS-200 heat sink requires vertical mounting for maximum cooling. Any other mounting angle will reduce the DECS-200s heat dissipation capability and possibly lead to premature failure of critical components. The DECS-200 may be mounted anywhere that the ambient temperature does not exceed the environmental conditions listed in Section 1, General Information, Specifications. Overall DECS-200 dimensions are shown in Figure 4-1. Two DECS-200 mounting configurations are possible: projection mounting and panel mounting. The panel drilling diagram for projection mounting of a DECS-200 is shown in Figure 4-2. Panel mounting of a DECS-200 is possible with the optional escutcheon plate (part number 9360107100). Escutcheon plate dimensions are shown in Figure 4-3. The panel cutting and drilling diagram for the escutcheon plate is illustrated in Figure 4-4.

CAUTION The hardware provided with the escutcheon plate should be used to attach the plate to the DECS-200. If other screws are used, ensure that the screw length is no greater than (0.25) and no less than 7/32 (0.219).

9360100990 Rev G

DECS-200 Installation

4-1

Figure 4-1. Overall Dimensions 4-2 DECS-200 Installation 9360100990 Rev G

Figure 4-2. Panel Drilling Diagram, Projection Mount

9360100990 Rev G

DECS-200 Installation

4-3

Figure 4-3. Escutcheon Plate Dimensions

4-4

DECS-200 Installation

9360100990 Rev G

Figure 4-4. Panel Cutting and Drilling Dimensions, Panel Mount 9360100990 Rev G DECS-200 Installation 4-5

CONNECTIONS
DECS-200 connections are dependent on the application and excitation scheme used. Observe the following guidelines when making DECS-200 connections: A given application may not require the use of all DECS-200 inputs and outputs. Incorrect wiring may result in damage to the unit. Applying incorrect control power, operating power, or sensing values may damage the unit. Compare the unit style number with the style chart (Figure 1-2) before applying control power. NOTE The DECS-200 must be hard-wired to earth ground with no smaller than 12 AWG copper wire attached to ground terminal C1. When the DECS-200 is configured in a system with other devices, a separate lead should be used to connect each device to the ground bus. Terminations for DECS-200 connections are located on the right-hand panel, the front panel, and the lefthand panel. Right-Hand Panel Connections Right-hand panel terminations consist of a nine-pin, female, D-type connector (Com 1) that is used for communication with a second DECS-200 unit when operating in a redundant system. A communication cable, part number 9310300032, is available for interconnecting two DECS-200 units. Table 4-1 lists the Com 1 pin numbers and functions. Figure 4-5 illustrates the communication connections between DECS200 units. Pin 1 2 3 4 5 6 7, 8, 9 XMIT RCV DTR GND DSR Name Table 4-1. Com 1 Pin Functions Description Function Not used Transmit Receive Data Terminal Ready Ground Data Set Ready Not used N/A Sends serial data from DECS-200 Receives serial data from DECS-200 Receives signal indicating that the sending unit is operational Provides the signal ground Sends a signal indicating that the DECS-200N is operational N/A

TO DECS-200 DB-9 FEMALE DB-9 MALE 1 XMIT RCV DTR GND DSR 2 3 4 5 6 7 8 9 NO CONNECTION NO CONNECTION NO CONNECTION NO CONNECTION DB-9 MALE 1 2 3 4 5 6 7 8 9 XMIT RCV DTR GND DSR

TO DECS-200 DB-9 FEMALE

P0007-07 03-13-01

Figure 4-5. DECS-200 to DECS-200 Communication Connections 4-6 DECS-200 Installation 9360100990 Rev G

Front Panel Connections Front panel terminations consist of a nine-pin, female, D-type connector (Com 0) that is intended for short-term, RS-232 serial communication with a PC operating BESTCOMS software. Refer to Section 5, BESTCOMS Software for information about using BESTCOMS to communicate with the DECS-200. Left-Hand Panel Connections Left-hand panel terminations consist of screw compression terminals. These terminals are illustrated in Figure 4-6. Table 4-2 lists the wire size capacity and maximum screw torque for each terminal on the lefthand panel.

Figure 4-6. DECS-200 Left-Side Terminals 9360100990 Rev G DECS-200 Installation 4-7

Table 4-2. Left-Hand Panel Terminal Specifications Terminals Wire Size Capacity Maximum Screw Torque A1 A45 B7 B10 B1 B6 C1 C6 14 AWG 10 AWG 0.4 Nm (3.5 in-lb) 0.5 Nm (4.4 in-lb)

In the following paragraphs, DECS-200 terminal functions are described and the terminal assignments for each function are listed. Control Power DECS-200 units have two sets of power terminals. One set receives dc control power and the other set receives ac control power. A DECS-200 with a style number of XL accepts nominal dc control power of 24 or 48 Vdc. The ac control power input of a style XL DECS-200 is not used. A DECS-200 with a style number of XC accepts nominal dc control power of 125 Vdc and nominal ac control power of 120 Vac. One source (either dc or ac) is sufficient for operation, but two sources can be used to provide redundancy. The dc input has internal protection against reversed polarity connections. When dual control power sources are used, an isolation transformer (part number BE31449001) is required for the ac input. Control power terminal functions are listed in Table 4-3. Terminal B7 (BAT+) B8 (BAT) B9 (L) B10 (N) Operating Power Operating power for the pulse-width modulated (PWM) excitation output is usually derived from the generator output. This input can also be developed by any suitable source that delivers voltage within the limits specified in Section 1, General Information, Specifications. Operating power may be either three-phase or single-phase. For single phase connections, any terminal combination can be used. The operating power applied must be of sufficient magnitude to support the required level of excitation voltage. For 32 Vdc field voltage, the operating power voltage should be in the range of 56 to 70 Vac (60 Vac nominal). For 63 Vdc field voltage, the operating power voltage should be in the range of 100 to 139 Vac (120 Vac nominal). For 125 Vdc field voltage, the operating power voltage should be in the range of 190 to 277 Vac (240 Vac nominal). The operating power frequency can be within the range of 50 to 500 hertz. Terminal C2 (A) C3 (B) C4 (C) Chassis Ground Terminal C1 (GND) serves as the DECS-200 chassis ground connection. Generator and Bus Voltage Sensing The DECS-200 accommodates either three-phase or single-phase generator sensing voltage with four automatically selected ranges: 120, 240, 400, or 600 Vac for 60 hertz systems or 100, 200, 400, or 500 Vac for 50 hertz systems. When single-phase generator sensing voltage is used, use terminals A1 and A3 for the sensing connections. 4-8 DECS-200 Installation 9360100990 Rev G Table 4-4. Operating Power Terminals Description A-phase operating power input B-phase operating power input C-phase operating power input Table 4-3. Control Power Terminals Description Positive side of dc input Negative side of dc input Line side of ac input Return or neutral side of ac input

A single bus sensing voltage input connects from phase A to phase C. The bus voltage sensing input has four automatically selected ranges which are identical to the generator sensing voltage ranges. Generator and bus voltage sensing terminals are listed in Table 4-5. Table 4-5. Generator and Bus Voltage Sensing Terminals Terminal Description A1 (E1) A2 (E2) A3 (E3) A4 (B1) A5 (B3) Generator Current Sensing A single current sensing input connects to a CT monitoring generator current on phase B. Two terminals are provided to accommodate 1 Aac or 5 Aac CTs. An input is also provided for sensing the current in a cross-current (reactive differential) compensation loop. Two or more paralleled generators can operate in cross-current compensation mode. Figure 4-7 illustrates a typical connection diagram for two paralleled generators using the 5 Aac sensing range on the DECS-200 cross-current input. The 1 resistor is a typical value that can be used to set the burden. (Ensure that the resistor power rating is adequate for the installation.) Like the generator current sensing input, the cross-current input has two terminals to accommodate 1 Aac or 5 Aac CTs. Generator current sensing terminals are listed in Table 4-6. Terminal B1 (CTB 1 AMP) B2 (CTB 5 AMP) B3 (CTB COM) B4 (CT CC 1A) B5 (CT CC 5A) Table 4-6. Generator Current Sensing Terminals Description B-phase generator current input for 1 Aac sensing B-phase generator current input for 1 Aac sensing B-phase generator sensing current common terminal Cross-current input for 1 Aac sensing Cross-current input for 5 Aac sensing A-phase generator sensing voltage input B-phase generator sensing voltage input C-phase generator sensing voltage input A-phase bus sensing voltage input C-phase bus sensing voltage input

B6 Cross-current common terminal (CT CC COM)

9360100990 Rev G

DECS-200 Installation

4-9

GEN 1

Phase B

CT

1.0
CT CC 5A

CT CC COM

DECS-200 DECS-200
CT CC 5A

1.0

CCC ENABLE CONTACT

LOAD

CT CC COM

GEN 2

P0005-02 05-28-04

Phase B CT

Figure 4-7. Typical Cross-Current Compensation Connections Accessory Input DECS-200 units accept analog accessory signals from other controllers (e.g., power system stabilizers) for remote control of the setpoint. Two types of accessory inputs are provided: voltage and current. Only one accessory input (voltage or current) may be used at one time. The voltage input accepts a signal over the range of 10 Vdc to +10 Vdc. The current input accepts a signal over the range of 4 mAdc to 20 mAdc. Shielded cable is recommended for the accessory signal. Terminal A8 is provided for the shield connection. Accessory input terminal assignments are listed in Table 4-7. Terminal A6 (I+) A7 (I) A8 (GND) A9 (V+) A10 (V) Contact Inputs The DECS-200 has 11 fixed-function contact inputs. Each contact input supplies an interrogation voltage of 12 Vdc and accepts dry switch/relay contacts or open-collector PLC outputs. Open-collector devices connected to the contact inputs must be compatible with the 12 Vdc interrogation voltage, be capable of conducting a minimum of 5 mAdc, and have off-state leakage current no greater than 100 Adc. Table 48 lists the contact input terminals. Function Start Stop AVR Mode Enable 4-10 Table 4-8. Contact Input Terminals Terminal Common Terminal A21 (START) A23 (STOP) A25 (AUTO) A22 (COM) A24 (COM A26 (COM) Input Type Momentary Momentary Momentary 9360100990 Rev G Table 4-7. Accessory Input Terminals Description Positive side of current accessory input Negative side of current accessory input Shield connection for accessory input Positive side of voltage accessory input Negative side of voltage accessory input

DECS-200 Installation

Function FCR Mode Enable Raise Command Lower Command Pre-Position Unit/Parallel Var/PF Enable Secondary Enable Alarm Reset Output Contacts

Terminal A27 (FCR) A29 (RAISE) A31 (LOWER) A33 (PRE-P) A35 (52L/M) A37 (52J/K) A39 (SECEN) A41 (ALRST)

Common Terminal A28 (COM) A30 (COM) A32 (COM) A34 (COM) A36 (COM) A38 (COM) A40 (COM) A42 (COM)

Input Type Momentary Momentary Momentary Continuous Continuous Continuous Continuous Momentary

The DECS-200 has two fixed-function contact outputs and three user-programmable contact outputs. All output contacts are normally open (NO) except for the Watchdog output which is normally closed (NC). Output contact terminal assignments are listed in Table 4-9. For additional information about relay output specifications, refer to Section 1, General Information. For information about configuring the userprogrammable outputs, refer to Section 3, Functional Description. Terminal A11 (ON/OF) A12 (ON/OF) A13 (WTCHD) A14 (WTCHD) A15 (RLY1) A16 (RLY1) A17 (RLY2) A18 (RLY2) A19 (RLY3) A20 (RLY3) Field Output The DECS-200 output is capable of supplying 15 Adc of continuous excitation current to a field with no less than 2.13 ohms of resistance (at 32 Vdc), 4.2 ohms of resistance (at 63 Vdc), or 8.3 ohms of resistance (at 125 Vdc). Field output terminals are listed in Table 4-10. Terminal C5 (F+) C6 (F) Com 2 Connections Communication port Com 2 is intended for polled communication over a Modbus network. Twisted-pair cable is recommended for Com 2 connections. Com 2 terminals are listed in Table 4-11. Figure 4-8 illustrates the Com 2 connections used for multiple DECS-200 units communicating over a Modbus network. Table 4-11. Com 2 Terminals
Terminal A43 (A) A44 (B) A45 (C) Description RS-485 send/receive A terminal RS-485 send/receive B terminal RS-485 signal ground terminal

Table 4-9. Output Contact Terminals Description On/Off contact terminals Watchdog contact terminals (normally closed) Programmable relay #1 terminals Programmable relay #2 terminals Programmable relay #3 terminals

Table 4-10. Field Output Terminals Description Field output positive terminal Field output negative terminal

9360100990 Rev G

DECS-200 Installation

4-11

T0 RS-422/RS-485 DB-37 Female 4 6 22 24 19 Rt

To DECS-200 Terminal Block

A B C

A43 A44 A45 DECS-200 Com 2

A B C 4000' MAX.

A43 A44 A45 DECS-200 Com 2

P0007-08 11-21-05

Rt

A B C

A43 A44 A45 DECS-200 Com 2

Rt = Optional terminating resistor (120 O typical)

Figure 4-8. RS-485 DB-37 to DECS-200

4-12

DECS-200 Installation

9360100990 Rev G

Typical Connections Connections for a typical DECS-200 application are illustrated in Figure 4-9.

Figure 4-9. Typical Connections

9360100990 Rev G

DECS-200 Installation

4-13

This page intentionally left blank.

4-14

DECS-200 Installation

9360100990 Rev G

SECTION 5 BESTCOMS SOFTWARE


TABLE OF CONTENTS
SECTION 5 BESTCOMS SOFTWARE .................................................................................................. 5-1 INTRODUCTION.................................................................................................................................... 5-1 INSTALLATION...................................................................................................................................... 5-1 Operating Requirements .................................................................................................................... 5-1 Installing BESTCOMS ........................................................................................................................ 5-1 Connecting the DECS-200 and PC.................................................................................................... 5-1 STARTING BESTCOMS........................................................................................................................ 5-1 Establishing Communication .............................................................................................................. 5-1 Configuring the Communication Ports ............................................................................................... 5-2 Configuring the Real-Time Clock ....................................................................................................... 5-2 Assigning Identification Labels ........................................................................................................... 5-3 Creating a Password .......................................................................................................................... 5-3 CHANGING SETTINGS......................................................................................................................... 5-3 Sending Settings to the DECS-200.................................................................................................... 5-3 Retrieving DECS-200 Settings ........................................................................................................... 5-3 Saving Settings in DECS-200 Memory .............................................................................................. 5-3 SYSTEM SETTINGS ............................................................................................................................. 5-4 System Configuration ......................................................................................................................... 5-4 Setting Adjustments ........................................................................................................................... 5-8 Control Gain ..................................................................................................................................... 5-15 Analysis ............................................................................................................................................ 5-17 Protection/Relay ............................................................................................................................... 5-21 Data Log ........................................................................................................................................... 5-25 Metering............................................................................................................................................ 5-30 SAVING, PRINTING, AND OPENING FILES...................................................................................... 5-32 Saving Files ...................................................................................................................................... 5-32 Printing Files..................................................................................................................................... 5-33 Opening/Uploading Files .................................................................................................................. 5-33 PID WINDOW ...................................................................................................................................... 5-33 PID Calculations Based On Input Values......................................................................................... 5-34 Adding To PID List ........................................................................................................................... 5-35 Removing A PID List Record............................................................................................................ 5-35 Retrieving Existing Data From PID List............................................................................................ 5-35 TERMINATING COMMUNICATION .................................................................................................... 5-35 Figures Figure 5-1. Wait Dialog Box Figure 5-2. Communication Port Settings ................................................................................................. 5-2 Figure 5-3. Password Dialog Box .............................................................................................................. 5-2 Figure 5-4. Set Real Time Clock Screen................................................................................................... 5-2 Figure 5-5. Device ID Screen .................................................................................................................... 5-3 Figure 5-6. Change DECS Password Screen ........................................................................................... 5-3 Figure 5-7. System Configuration Screen, System Options Tab .............................................................. 5-4 Figure 5-8. System Configuration Screen, System Data Tab ................................................................... 5-5 Figure 5-9. System Configuration Screen, Rated Data Tab...................................................................... 5-6 Figure 5-10. Pole Ratio Calculator ............................................................................................................ 5-7 Tables Table 5-1. Predefined Stability Setting Groups ....................................................................................... 5-16 Table 5-2. Data Log Report Parameter Triggers..................................................................................... 5-30 Table 5-3. 52J/K and 52L/M Logic........................................................................................................... 5-31

9360100990 Rev G

DECS-200 BESTCOMS Software

This page intentionally left blank.

ii

DECS-200 BESTCOMS Software

9360100990 Rev G

SECTION 5 BESTCOMS SOFTWARE


INTRODUCTION
BESTCOMS is a Windows-based application that provides a user-friendly environment for programming and customizing the DECS-200. In addition to screens for configuring DECS-200 settings, BESTCOMS has metering screens for viewing machine and system parameters and control screens for remote control of the excitation system. An integrated PID calculator simplifies the selection of stability settings.

INSTALLATION
BESTCOMS-DECS200 software contains a setup utility that installs the program on your PC. When it installs the program, an uninstall icon is created that you may use to uninstall (remove) the program from your PC. The minimum recommended operating requirements are listed in the following paragraph. Operating Requirements IBM compatible PC, 486 DX2 or faster (100 MHz or higher speed microprocessor recommended), with a minimum 20 megabytes of RAM Microsoft Windows Vista, XP, or 2000 CD-ROM drive One available serial port Installing BESTCOMS 1. Insert the DECS-200 CD-ROM into the PC CD-ROM drive. 2. When the DECS-200 Setup and Documentation CD Menu appears, click the Install button for BESTCOMS-DECS200. The BESTCOMS setup utility automatically installs BESTCOMS. When BESTCOMS is installed, a Basler Electric folder is added to the Windows program menu. This folder is accessed by clicking the Start button and pointing to Programs. The Basler Electric folder contains an icon for BESTCOMS-DECS200. Connecting the DECS-200 and PC Connect a communication cable between the DECS-200 front panel RS-232 connector (Com 0) and the appropriate communication port of the PC.

STARTING BESTCOMS
BESTCOMS is started by clicking the Windows Start button, pointing to Programs, the Basler Electric folder, and then clicking the BESTCOMS-DECS200 icon. At startup, a dialog box with the program title and version number is displayed briefly. After this dialog box is displayed, the System Configuration Screen is displayed (Figure 5-7). Establishing Communication Communication between BESTCOMS and the DECS-200 must be established before viewing metering values or reading or changing settings. BESTCOMS screen settings are updated only after communication is opened or the communication settings have been changed. Open the DECS-200 communication port by clicking Communications on the menu bar, hovering the mouse pointer over Open Comm Port and clicking Front Port - RS-232 (Figure 5-2). When the Comm Port dialog box appears, select the appropriate PC communication port and click the Initialize button. BESTCOMS initiates communication by retrieving the configuration settings from the DECS-200. NOTE BESTCOMS may display the dialog box of Figure 5-1 when initiating DECS-200 communication, obtaining DECS-200 configuration settings or performing other tasks. It's important to wait until the box disappears before trying to execute communication commands. Issuing commands while the Reading from DECS-200 dialog box is present may disrupt communication between BESTCOMS and the DECS-200. 9360100990 Rev G DECS-200 BESTCOMS Software

Figure 5-1. Wait Dialog Box

5-1

Configuring the Communication Ports DECS-200 communication settings are changed through the Communication Port Settings screen. To access this screen, click Communications on the menu bar and click Port Configuration. Communication port settings are illustrated in Figure 5-2 and described in the following paragraphs. Serial Port. To modify the settings of a communication port, the serial port must first be selected. Each port has a corresponding setting selection. Front-panel communication port settings are adjusted by selecting COM0 RS-232. Righthand panel communication port settings are adjusted by selecting COM1 RS-232. Left-hand panel communication port settings are adjusted by selecting COM2 RS-485. Baud Rate. A baud rate of 1200, 2400, 4800, 9600, or 19200 may be selected for each serial port. Parity. This setting can be adjusted only for port Com 2. A setting of N (no parity) O (odd parity), or E (even parity) may be selected. Data Bits. The number of data bits is not adjustable and fixed at 8. Stop Bits. This setting can be adjusted only for port Com 2. One (1) stop bit or two (2) stop bits may be selected. Modbus Settings, Address. This setting is enabled only for port Com 2. A device address of 1 through 247 may be selected. Modbus Settings, Response Time Delay. This setting is enabled only for port Com 2. A response time delay of 10 to 200 milliseconds may be entered in 10 millisecond increments. Once changes are made to the communication settings and the OK button is clicked, the Password dialog box of Figure 5-3 appears and prompts you to enter a password. Each DECS-200 is delivered with "decs2" as the default password. See Creating a Password for information about changing the password. After the correct password is entered, the communication setting changes are made active. Configuring the Real-Time Clock DECS-200 timekeeping is set and configured through the Set Real Time Clock screen (Figure 54). To access the Set Real Time Clock screen, click Configure on the menu bar and click Real Time Clock. The DECS-200 date and time are set by altering the date and time fields or by retrieving the PC date and time and then sending the values to the DECS-200. The date format can be selected as MM/DD/YY or DD-MM-YY. Timekeeping can use the 12-hour or 24-hour format. Daylight saving time compensation can be enabled or disabled. 5-2 Figure 5-3. Password Dialog Box Figure 5-2. Communication Port Settings

Figure 5-4. Set Real Time Clock Screen

DECS-200 BESTCOMS Software

9360100990 Rev G

Assigning Identification Labels Identification labels can be assigned to the DECS200 through the Device ID screen (Figure 5-5). The information entered on the Device ID screen identifies the DECS-200 unit and associates it with a location and one or two operators. The Device ID screen is accessed by clicking Configure on the menu bar and clicking Device ID Information. Information entered on the Device ID screen is used in sequence-of-events reporting and settings printouts. Each field of the Device ID screen accepts a maximum of 30 alphanumeric characters. Figure 5-5. Device ID Screen Creating a Password Password protection guards against unauthorized changing or viewing of DECS-200 settings. A single password protects all DECS-200 settings. The DECS-200 is delivered with a default password of decs2. The password can be changed only after communication between BESTCOMS and the DECS-200 is established. Once the password is changed, it should be stored in a secure location. If the user-defined password is lost or forgotten, BESTCOMS must be reloaded to restore the default password. A user password is entered on the Change DECS Password screen. This screen, illustrated in Figure 5-6, is accessed by clicking Communications on the menu bar and clicking Password Change. A password containing up to six alphanumeric characters may be entered.

Figure 5-6. Change DECS Password Screen

CHANGING SETTINGS
A setting is changed by clicking within the setting field and typing the new setting value. When the cursor is placed within a setting field, the range limits and increments for the setting are displayed on the status bar. If a value outside the range limits is entered, an Input Error dialog box will appear and display the acceptable range limits for the setting. Sending Settings to the DECS-200 Once all desired setting changes have been made on a setting group screen, the settings must be sent to the DECS-200 before viewing other screens. Otherwise, the setting changes will be lost. Setting changes can be sent to the DECS-200 by clicking the SendToDECS button or by clicking Communications on the menu bar and then clicking Send To DECS. A single setting change can be sent to the DECS-200 by pressing the keyboard Enter key. Functions controlled by option buttons or checkboxes are immediately sent to the DECS-200 when the option button or checkbox is selected. Retrieving DECS-200 Settings Settings are retrieved from the DECS-200 by clicking the GetFromDECS button. This causes the current DECS-200 settings to be displayed on the BESTCOMS setting screens. DECS-200 settings can also be retrieved by clicking Communications on the menu bar and clicking Get From DECS. Saving Settings in DECS-200 Memory DECS-200 settings are saved in nonvolatile memory (EEPROM). In the event of a control power loss, these are the settings that are active at power-up. When setting changes are made and sent to the DECS-200, they are automatically saved to EEPROM (if the correct password is entered). When you close communication or exit BESTCOMS, you may be asked for a password. Enter the correct password to ensure that all setting changes are saved. 9360100990 Rev G DECS-200 BESTCOMS Software 5-3

SYSTEM SETTINGS
DECS-200 settings, metering values, and data records are arranged into seven groups within BESTCOMS: System Configuration Protection/Relay Setting Adjustments Data Log Control Gain Metering/Operation Analysis Each group is contained on a BESTCOMS screen. A screens settings and parameters are further organized by labeled tabs within the screen. In the following paragraphs, settings, metering values, and data records are arranged and defined according to the organization of the BESTCOMS screen and tabs. System Configuration The System Configuration screen consists of four tabs labeled System Options, System Data, Rated Data, and Auxiliary Input. To view the System Configuration screen, click the Configure button on the toolbar or click Screens on the menu bar and click System Configuration. System Options System Options tab functions are shown in Figure 5-7 and described in the following paragraphs.

Figure 5-7. System Configuration Screen, System Options Tab Limiter Mode. This setting disables all limiters or enables the underexcitation limiter (UEL), overexcitation limiter (OEL), or stator current limiter (SCL). Selection of the following limiter combinations is also possible: OEL/UEL, SCL/UEL, SCL/OEL, and SCL/OEL/UEL. Sensing Configuration. Configures the generator sensing voltage as either single-phase or three-phase. Underfrequency Mode. Configures underfrequency limiting for V/Hz or underfrequency operation. Generator Frequency. Selects either 50 hertz or 60 hertz as the nominal system frequency. Voltage Matching. Enables or disables voltage matching. For voltage matching to be enabled, the DECS200 must be operating in AVR mode, var/power factor correction must be disabled, and the system must be off line. Version Numbers. These two read-only fields display the version of BESTCOMS software and the firmware version of the DECS-200 connected to the PC operating BESTCOMS. In order for the DECS200 firmware version to be displayed, communication must be established between BESTCOMS and the DECS-200. 5-4 DECS-200 BESTCOMS Software 9360100990 Rev G

System Data System Data tab functions are shown in Figure 5-8 and described in the following paragraphs.

Figure 5-8. System Configuration Screen, System Data Tab Generator PT Ratings, Primary Voltage. Sets the rated primary voltage of the generator potential transformer (PT). Generator and bus PT ratings must be specified in the same sensing range. A setting of 1 to 30,000 Vac may be entered in 1 Vac increments. Generator PT Ratings, Secondary Voltage. Sets the rated secondary voltage of the generator potential transformer. Generator and bus PT ratings must be specified in the same sensing range. A setting of 1 to 600 Vac may be entered in 1 Vac increments. Generator CT Ratings, Primary Current. Sets the rated primary current of the generator current transformer (CT). A setting of 1 to 60,000 Aac may be entered in 1 Aac increments. Generator CT Ratings, Secondary Current. Sets the rated secondary current of the generator current transformer (CT). A setting of 1 Aac or 5 Aac may be entered. Bus PT Ratings, Primary Voltage. Sets the rated primary voltage of the bus potential transformer (PT). Generator and bus PT ratings must be specified in the same sensing range. A setting of 1 to 500,000 Vac may be entered in 1 Vac increments. Bus PT Ratings, Secondary Voltage. Rated secondary voltage of the bus potential transformer (PT). (Read only.) Internal Tracking, Enabled/Disabled. Enables or disables tracking of the active control mode setpoint by the inactive control modes. Internal Tracking, Delay. Determines the time delay between a control mode change and setpoint tracking. A setting of 0 to 8 seconds may be entered in 0.1 second increments. Internal Tracking, Traverse Rate. Determines the amount of time required for the inactive control mode to traverse (cross) the full setting range of the active control mode setpoint. A setting of 1 to 80 seconds may be entered in 0.1 second increments. External Tracking, Enable/Disable. Enables or disables tracking of a second DECS-200s setpoint. External Tracking, Delay. Determines the time delay between a transfer to a second DECS-200 and start of tracking of the second DECS-200 setpoint. A setting of 0 to 8 seconds may be entered in 0.1 second increments.

9360100990 Rev G

DECS-200 BESTCOMS Software

5-5

External Tracking, Traverse Rate. Determines the amount of time required for the DECS-200 to traverse (cross) the full setting range of a second, active DECS-200. A setting of 1 to 80 seconds may be entered in 0.1 second increments. Rated Data Rated Data tab functions are shown in Figure 5-9 and described in the following paragraphs.

Figure 5-9. System Configuration Screen, Rated Data Tab Generator Rated Data, Voltage. Sets the rated line-to-neutral generator voltage. A setting of 85 to 30,000 Vac may be entered in 1 Vac increments. Generator Rated Data, Current. sets the rated generator line current. A setting of 10 to 60,000 Aac may be entered in 0.1 Aac increments. Generator Rated Data, Power Factor. Sets the rated generator power factor which is used to calculate generator real power. A setting of 0.5 (leading) to 0.5 (lagging) may be entered in 0.01 increments. Generator Rated Data, Real Power. This read-only field is the calculated product of the voltage field, current field, power factor field, and the square root of 3. Generator Rated Data, Rating. This read-only field is the calculated product of the voltage field, current field, and the square root of 3. Exciter Field Rated Data, Field Voltage. Sets the rated exciter field voltage. A setting of 1 to 180 Vdc may be entered in 0.1 Vdc increments. Exciter Field Rated Data, Field Current. Sets the rated exciter field current. A setting of 0.1 to 15 Adc may be entered in 0.1 Adc increments. Exciter Field Rated Data, Field Resistance. This read-only field is the calculated result of the field voltage field being divided by the field current field. Pole Ratio, Calculate Pole Ratio. Clicking this button displays the Pole Ratio Calculator screen (Figure 510). Enter the number of exciter poles and generator poles and press the Enter key to view the calculated result. The Number of EXCITER Poles field accepts even numbers between 0 and 1,000. The Number of GENERATOR Poles field accepts even numbers between 0 and 100. Clicking the Accept button closes the Pole Ratio Calculator screen and enters the ratio in the Pole Ratio field.

5-6

DECS-200 BESTCOMS Software

9360100990 Rev G

Figure 5-10. Pole Ratio Calculator Pole Ratio, Pole Ratio. Sets the ratio of the number of exciter poles to the number of generator poles. A setting of 0 to 10 may be entered in 0.01 increments. This value can be calculated automatically using the pole ratio calculator , accessed by clicking the Calculate Pole Ratio button. Auxiliary Input The auxiliary voltage input signal changes the setpoint of the selected operating mode. For more information on the auxiliary voltage input, refer to Section 3, Functional Description. Auxiliary Input tab functions are shown in Figure 5-11 and described in the following paragraphs.

Figure 5-11. System Configuration Screen, Auxiliary Input Tab Auxiliary Input, Input Type. Selects the accessory input type as voltage or current for remote control of the setpoint. Auxiliary Input, Summing Type. Selects either Inner Loop or Outer Loop as the summing type. When Inner Loop is selected, the operating mode is either AVR of FCR. When Outer Loop is selected, the operating mode is either var or power factor. 9360100990 Rev G DECS-200 BESTCOMS Software 5-7

Auxiliary Input, Auxiliary Gain Settings. The four auxiliary gain setting fields, AVR, FCR, var, and PF, select the gain which affects the setpoint of the selected operating mode. The signal applied to the accessory input is multiplied by the auxiliary gain setting. Each gain setting can be adjusted from 99 to +99 in increments of 0.01. For more information on the accessory gain settings, refer to Section 3, Functional Description. Droop Settings, Reactive Droop Compensation. Sets the level of droop compensation for paralleled generators or line-drop compensations. Droop compensation is adjustable from 0 to +30% of the generator nominal, terminal voltage in 0.1% increments. Line-drop compensation is adjustable from 30 to 0% of the generator nominal terminal voltage in 0.1% increments. Droop Settings, Cross Current Compensation Gain. Sets the level of cross-current compensation (reactive differential) gain for paralleled generators. Cross-current compensation gain is adjustable from 30 to +30% of the rated CTs in 0.01% steps. Refer to Section 4, Installation, for more information on cross-current compensation gain. Setting Adjustments The Setting Adjustments screen consists of eight tabs labeled AVR/FCR, var/PF, Startup, OEL Type, OEL (Summing), OEL (Takeover), UEL, and SCL. To view the setting adjustment screen, click the Settings button on the tool bar or click Screens on the menu bar and click Setting Adjustments. AVR/FCR AVR/FCR tab functions are illustrated in Figure 5-12 and described in the following paragraphs.

Figure 5-12. Setting Adjustments Screen, AVR/FCR Tab Automatic Voltage Regulator, AVR Setpoint. Sets the desired generator output voltage when operating in AVR mode. The range of this setting is based on the generator voltage setting entered on the Rated Data tab of the System Configuration screen. This setting is also limited by the settings of the AVR Min and AVR Max fields. If sensing step-down transformers are used, primary voltage should be entered. Automatic Voltage Regulator, AVR Min. Sets the minimum generator output voltage, expressed as a percentage of the rated generator voltage. A setting of 70 to 100% may be entered in 0.1% increments. Automatic Voltage Regulator, AVR Max. Sets the maximum generator output voltage, expressed as a percentage of the rated generator voltage. A setting of 70 to 100% may be entered in 0.1% increments. Automatic Voltage Regulator, Traverse Rate (sec). Determines the time required to adjust the AVR setpoint from the minimum value to the maximum value of the adjustment range. A setting of 10 to 200 seconds may be entered in 1 second increments. 5-8 DECS-200 BESTCOMS Software 9360100990 Rev G

Automatic Voltage Regulator, Pre-position Setpoint. Defines the pre-position setpoint for AVR mode. This value replaces the AVR setpoint value if pre-position is selected and the AVR Pre-Position mode is Maintain. The setting range is identical to the AVR Setpoint setting range. If sensing step-down transformers are being used, primary voltage should be entered. Automatic Voltage Regulator, Preposition Mode. Determines whether or not the DECS-200 will respond to further setpoint change commands once the operating setpoint is driven to the pre-position value. If Maintain mode is selected, further setpoint changes are ignored. If Release mode is selected, subsequent setpoint changes are possible by using Raise and Lower commands. Field Current Regulator, FCR Setpoint. Sets the field current setpoint when operating in FCR mode. The range of this setting is based on the field current rating entered on the Rated Data tab of the System Configuration screen. This setting is also controlled by the settings of the FCR Min and FCR Max fields. Field Current Regulator, FCR Min. Sets the minimum field current setpoint, expressed as a percentage of the rated field current. A setting of 0 to 100% may be entered in 0.1% increments. Field Current Regulator, FCR Max. Sets the maximum field current setpoint, expressed as a percentage of the rated field current. A setting of 1 to 120% may be entered in 0.1% increments. Field Current Regulator, Traverse Rate. Determines the time required to adjust the FCR setpoint from the minimum value to the maximum value of the adjustment range. A setting of 10 to 200 seconds may be entered in 1 second increments. Field Current Regulator, Preposition Setpoint. Defines the pre-position setpoint for FCR mode. This value replaces the FCR setpoint value if pre-position is selected and the FCR Pre-Position mode is Maintain. The setting range is identical to the FCR Setpoint setting range. Field Current Regulator, Pre-position Mode. Determines whether or not the DECS-200 will respond to further setpoint change commands once the operating setpoint is driven to the pre-position value. If Maintain mode is selected, further setpoint changes are ignored. If Release mode is selected, subsequent setpoint changes are possible by using Raise and Lower commands. Var/PF Var/PF tab functions are illustrated in Figure 5-13 and described in the following paragraphs.

Figure 5-13. Setting Adjustments Screen, var/PF Tab Reactive Power Control, var Setpoint. Sets the reactive power setpoint when operating in var mode. The range of this setting depends on the generator ratings entered on the Rated Data tab of the System Configuration screen. This setting is also controlled by the settings of the var Min and var Max fields. 9360100990 Rev G DECS-200 BESTCOMS Software 5-9

Reactive Power Control, var Min. Sets the minimum var setpoint, expressed as a percentage of the rated generator kVA. A setting of 100 to +100% may be entered in 1% increments. Reactive Power Control, var Max. Sets the maximum var setpoint, expressed as a percentage of the rated generator kVA. A setting of 100 to +100% may be entered in 1% increments. Reactive Power Control, Traverse Rate. Determines the time required to adjust the var setpoint from the minimum value to the maximum value of the adjustment range. A setting of 10 to 200 seconds may be entered in 1 second increments. Reactive Power Control, Preposition Setpoint. Defines the pre-position setpoint for var mode. This value replaces the var setpoint value if pre-position is selected and the var Pre-Position mode is Maintain. The setting range is identical to the var Setpoint setting range. Reactive Power Control, Preposition Mode. Determines whether or not the DECS-200 will respond to further setpoint change commands once the operating var setpoint is driven to the pre-position value. If Maintain mode is selected, further setpoint changes are ignored. If Release mode is selected, subsequent setpoint changes are possible by using Raise and Lower commands. Reactive Power Control, Var/PF Fine Volt Band. Sets the upper and lower boundaries of voltage correction when operating in var or PF mode. Power Factor Control, PF Setpoint. Sets the generator operating power factor. The range of this setting is determined by the settings of the PF (Leading) and PF (Lagging) fields. Power Factor Control, PF (Leading). Sets the limit for leading power factor. A setting of 1 to 0.5 may be entered in 0.005 increments. Power Factor Control, PF (Lagging). Sets the limit for lagging power factor. A setting of 0.5 to 1 may be entered in 0.005 increments. Power Factor Control, Traverse Rate (sec). Determines the time required to adjust the power factor setpoint from the minimum value to the maximum value of the adjustment range. A setting of 10 to 200 seconds may be entered in 1 second increments. Power Factor Control, Preposition Setpoint. Defines the pre-position setpoint for Power Factor mode. This value replaces the PF setpoint value if pre-position is selected and the PF Pre-Position mode is Maintain. The setting range is identical to the PF Setpoint setting range. Power Factor Control, Preposition Mode. Determines whether or not the DECS-200 will respond to further setpoint change commands once the operating PF setpoint is driven to the pre-position value. If Maintain mode is selected, further setpoint changes are ignored. If Release mode is selected, subsequent setpoint changes are possible by using Raise and Lower commands. Startup Startup tab settings are illustrated in Figure 5-14 and described in the following paragraphs. Startup Control, Soft Start Level. Sets the generator soft-start voltage offset used during startup. A setting of 0 to 90% may be entered in 1% increments. Startup Control, Soft Start Time. Sets the soft-start time limit used during startup. A setting of 1 to 7,200 seconds may be entered in 1 second increments. Underfrequency Setting, Corner Frequency. Sets the generator corner frequency for generator underfrequency protection. A setting of 15 to 90 Hz may be entered in 0.1 Hz increments. Underfrequency Setting, Slope. Sets the generator frequency slope for generator underfrequency protection. A setting of 0 to 3 V/Hz may be entered in 0.01 V/Hz increments. Voltage Matching, Band. Configures the generator voltage matching band as a percentage of the generator rated voltage. When the bus voltage falls outside this band, no voltage matching occurs. A setting of 0 to 20% may be entered in 0.01% increments. Voltage Matching, Gen to Bus PT Match Level. Ensures accurate voltage matching by compensation for the error between the generator and bus voltage sensing transformers. The Match Level is expressed as the relationship of the generator voltage to the bus voltage (expressed as a percentage). A setting of 90 to 120% may be entered in 0.1% increments.

5-10

DECS-200 BESTCOMS Software

9360100990 Rev G

Figure 5-14. System Settings Screen, Startup Tab OEL Type Overexcitation Limiter Type tab settings are illustrated in Figure 5-15 and described in the following paragraphs.

Figure 5-15. System Settings Screen, OEL Type Tab OEL Limiter Style. Selects either the summing-point type of overexcitation limiter or the takeover-type of overexcitation limiter. OEL Setting Selection Option. Selects the on-line and off-line OEL settings for various 52J/K and 52L/M contact statuses. 9360100990 Rev G DECS-200 BESTCOMS Software 5-11

Option 1 activates the on-line OEL settings when either the 52J/K contact or 52L/M contact is opened. The off-line OEL settings are activated when both the 52J/K and 52L/M contacts are closed. When the 52L/M contact input is jumpered, the 52J/K input can be used to switch between the on-line OEL and offline OEL. If var/PF modes are disabled, a closed 52J/K contact enables AVR mode and an open 52J/K contact enables droop compensation. Option 2 configures the 52J/K contact to define when the off-line and on-line limiters are active. When the 52J/K contact is closed, the off-line OEL settings are active. When the 52J/K contact is open, the on-line OEL settings are active. This configuration is intended for cross-compound generator applications where both machines are paralleled at low rotational speed. Therefore, droop compensation needs to be active (open 52L/M contact) as the speed of the machines is increased. However, both machines need active, off-line overexcitation limiting protection. Option 3 activates the on-line OEL at all times. This configuration enables the DECS-200 to operate in AVR mode (stand-alone application) without restriction from the off-line OEL settings. The active on-line OEL is able to limit excitation current if needed. This configuration also eliminates the need for the DECS200 to operate in Droop mode when applied in a single-unit application. Therefore, generator voltage should not droop as reactive load increases. OEL (Summing) Summing-Point Overexcitation Limiter tab settings are illustrated in Figure 5-16 and described in the following paragraphs.

Figure 5-16. System Settings Screen, OEL (Summing) Tab Off-Line OEL Setting, High Current Level. Establishes the high-level current setpoint for the off-line, summing-point, overexcitation limiter. A setting of 0 to 30 Adc may be entered in 0.1 Adc increments. Off-Line OEL Setting, High Current Time. Sets the duration for the high current setpoint of the off-line, summing-point, overexcitation limiter. A setting of 0 to 10 seconds may be entered in 1 second increments. Off-Line OEL Setting, Low Current Level. Establishes the low-level current setpoint for the off-line, summing-point, overexcitation limiter. A setting of 0 to 15 Adc may be entered in 0.1 Adc increments. On-Line OEL Setting, High Current Level. Establishes the high-level current setpoint for the on-line, summing-point, overexcitation limiter. A setting of 0 to 30 Adc may be entered in 0.1 Adc increments. On-Line OEL Setting, Medium Current Level. Establishes the medium-level current setpoint for the online, summing point, overexcitation limiter. A setting of 0 to 20 Adc may be entered in 0.1 Adc increments.

5-12

DECS-200 BESTCOMS Software

9360100990 Rev G

On-Line OEL Setting, Medium Current Time. Sets the duration for the medium current setpoint of the online, summing-point, overexcitation limiter. A setting of 0 to 120 seconds may be entered in 1 second increments. On-Line OEL Setting, Low Current Level. Establishes the low-level current setpoint for the on-line, summing-point, overexcitation limiter. A setting of 0 to 15 Adc may be entered in 0.1 Adc increments. OEL (Takeover) Takeover Overexcitation Limiter tab functions are illustrated in Figure 5-17 and described in the following paragraphs. Off-Line Settings, Low Current Level. Establishes the low-level current setpoint for the off-line, takeoverstyle, overexcitation limiter. A setting of 0 to 20 Adc may be entered in 0.1 Adc increments. Off-Line Settings, High Current Level. Establishes the high-level current setpoint for the off-line, takeoverstyle, overexcitation limiter. A setting of 0 to 30 Adc may be entered in 0.1 Adc increments. Off-Line Settings, Time Dial. Sets the time delay for the off-line, takeover-style, overexcitation limiter. A setting of 0.1 to 20 seconds may be entered in 0.1 second increments.

Figure 5-17. Setting Adjustments Screen, OEL (Takeover) Tab On-Line Settings, Low Current Level. Establishes the low-level current setpoint for the on-line, takeoverstyle, overexcitation limiter. A setting of 0 to 15 Adc may be entered in 0.1 Adc increments. On-Line Setting, High Current Level. Establishes the high-level current setpoint for the on-line, takeoverstyle, overexcitation limiter. A setting of 0 to 30 Adc may be entered in 0.1 Adc increments. On-Line settings, Time Dial. Sets the time delay for the on-line, takeover-style, overexcitation limiter. A setting of 0.1 to 20 seconds may be entered in 0.1 second increments. Off-Line Curve and On-Line Curve Checkboxes. Checking these boxes displays a plot of the takeoverstyle off-line and on-line overexcitation limiter curves. Curve magnification is adjusted by the Zoom X, Zoom Y, Zoom XY, and Zoom OUT buttons. UEL Underexcitation Limiter tab functions are illustrated in Figure 5-18 and described in the following paragraphs. UEL Settings, UEL Curve Type Selection. Selects either a user-configured or internally-configured underexcitation limiting curve. Selecting Customized enables the user to create a custom UEL curve that matches specific generator characteristics. When Internal is selected, the DECS-200 automatically 9360100990 Rev G DECS-200 BESTCOMS Software 5-13

creates a UEL curve based on the first point setting of the absorbed, reactive power level. This function operates in all modes except FCR. UEL Settings, Real Power. Up to five setting fields may be used to establish up to five real-power (kW) points of the underexcitation limiter curve. The UEL Curve Type Selection must be set to Customized in order for these setting fields to be enabled. Not all setting fields need be used. For example, entering kW values in three of the five setting fields produces a three-point UEL curve. The range for each setting field is based on the generator ratings entered on the Rated Data tab of the System Configuration screen. UEL Settings, Reactive Power. When the UEL Curve Type Selection is set to Customized, these five setting fields establish the five reactive power points of the underexcitation limiter curve. Not all setting fields need be used. For example, entering kvar values in to of the five setting fields produces a two-point UEL curve. When the UEL curve Type Selection is set to Internal, only the first setting field is enabled and a UEL curve is internally generated based on the value entered in the field. The range for each setting field is based on the generator ratings entered on the Rated Data tab of the System Configuration screen. Curve points are plotted in the UEL graph as values are entered through BESTCOMS. All kW and kvar settings can also be sent at the same time using the Send all UEL Settings to DECS button. Internal Curve and Customized Curve Buttons. These buttons can be clicked and held to preview the corresponding UEL curve.

Figure 5-18. Setting Adjustments Screen, UEL Tab SCL Stator Current Limiter tab settings are illustrated in Figure 5-19 and described in the following paragraphs. Stator Current Limiter, Initial Delay. The SCL does not respond until the Initial Delay has expired. A setting of 0 to 10 may be entered in 0.1 second increments. Stator Current Limiter, High SCL Current Level. Configures the high-level current setpoint for the stator current limiter. A setting of 0 to 66,000 Aac may be entered in 1.0 Aac increments. Stator Current Limiter, High SCL Current Time. Sets the time limit for high-level current limiting by the stator current limiter. A setting of 0 to 60 seconds may be entered in 1 second increments. Stator Current Limiter, Low SCL Current Level. Configures the low-level current setpoint for the stator current limiter. A setting of 0 to 66,000 Aac may be entered in 1 Aac increments.

5-14

DECS-200 BESTCOMS Software

9360100990 Rev G

Figure 5-19. Setting Adjustments Screen, SCL Tab Control Gain The Control Gain screen consists of a single tab labeled Control Gain. To view the Control Gain screen, click the Gain button on the tool bar or click Screens on the menu bar and click Control Gain. Control Gain Tab Control Gain tab settings are illustrated in Figure 5-20 and described in the following paragraphs.

Figure 5-20. Control Gain Screen Stability Range. Entering a value from 1 to 20 selects one of 20 predefined stability setting groups for exciter field applications. Table 5-1 lists the stability settings for each of the 20 predefined groups. Entering 21 enables the PID function and allows the user to optimize the stability settings. The PID 9360100990 Rev G DECS-200 BESTCOMS Software 5-15

function provides reference gain settings for user-specified generator and/or exciter time constants. See PID Window for information about customizing stability settings. Table 5-1. Predefined Stability Setting Groups Generator Open Circuit Time Generator Exciter Constant (Tdo) Time Constant (Texc) Kp 1.0 0.17 42.20 1.5 0.25 66.50 2.0 0.33 87.16 2.5 0.42 104.50 3.0 0.50 119.00 3.5 0.58 131.30 4.0 0.67 141.80 4.5 0.75 150.90 5.0 0.83 158.80 5.5 0.92 165.70 6.0 1.00 171.80 6.5 1.08 177.20 7.0 1.17 182.10 7.5 1.25 186.50 8.0 1.33 190.50 8.5 1.42 194.10 9.0 1.50 197.40 9.5 1.58 200.40 10.0 1.67 203.20 10.5 1.75 205.70

Setting Group 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

Ki 115.2 150.0 167.9 175.8 177.8 176.4 173.1 168.8 163.9 158.7 153.6 148.5 143.6 138.9 134.4 130.1 125.9 122.1 118.4 114.8

Kd 4.433 8.750 13.670 18.960 24.500 30.220 36.060 42.000 48.010 54.080 60.200 66.350 72.540 78.750 84.980 91.230 97.500 103.800 110.100 116.400

AVR/FCR, Proportional Gain KP. Selects the proportional constant (KP) stability parameter. The DECS200 provides an output value that is equivalent to KP multiplied by the error between the voltage setpoint and the actual generator output voltage. Typical values of KP range from 0 to 1,000. General guidelines for tuning KP are as follows: If the transient response has too much overshoot, decrease KP. If the transient response is too slow with little or no overshoot, increase KP. A setting of 0 to 1,000 may be entered in 0.1 increments. AVR/FCR, Integral Gain KI. Selects the integral constant (KI) stability parameter. The DECS-200 provides an output value that is equivalent to KI multi-plied by the integral of the error between the voltage setpoint and the actual generator output voltage. Typical values of KI range fro 0 to 1,000. Generally, if the time to reach steady state is deemed too long, then increase the value of KI. A setting of 0 to 1,000 may be entered in 0.1 increments. AVR/FCR, Derivative Gain KD. Selects the derivative constant (KD) stability parameter. The DECS-200 provides an output value that is equivalent to KD multiplied by the derivative of the error between the voltage setpoint and the actual generator output voltage. A setting of 0 to 1,000 may be entered in 0.1 increments. Typical values of KD range from 1 to 10. If the transient response has too much ringing, then KD should be increased. AVR/FCR, Derivative Gain TD. Removes the effects of noise on numerical differentiation. A setting of 0 to 1 may be entered in 0.01 increments. Typical TD values range from 0.01 to 0.03. AVR/FCR, AVR Loop Gain Kg. Sets the coarse loop-gain level of the PID algorithm for AVR mode. A setting of 0 to 1,000 may be entered in 0.1 increments. _AVR/FCR, FCR Loop Gain Kg. Sets the coarse loop-gain level of the PID algorithm for FCR mode. A setting of 0 to 1,000 may be entered in 0.1 increments.

5-16

DECS-200 BESTCOMS Software

9360100990 Rev G

VAR/PF, var Integral Gain KI. Adjusts the integral gain, which determines the characteristic of the DECS200 dynamic response to a changed var setting. A setting of 0 to 1,000 may be entered in 0.01 increments. VAR/PF, PF Integral Gain KI. Adjusts the integral gain, which determines the characteristic of the DECS200 dynamic response to a changed power factor setting. A setting of 0 to 1,000 may be entered in 0.1 increments. VAR/PF, var Loop Gain Kg. Sets the coarse loop-gain level of the PID algorithm for var control. A setting of 0 to 1,000 may be entered in 0.01 increments. VAR/PF, PF Loop Gain Kg. Sets the coarse loop-gain level of the PID algorithm for power factor control. A setting of 0 to 1,000 may be entered in 0.1 increments. SCL, Integral Gain KI. Adjusts the rate at which the DECS-200 limits stator current. A setting of 0 to 1,000 may be entered in 0.1 increments. SCL, Loop Gain Kg. Sets the coarse loop-gain level of the PID algorithm for the stator current limiter. A setting of 0 to 1,000 may be entered in 0.1 increments. OEL, Integral Gain KI. Adjusts the rate at which the DECS-200 responds during an overexcitation condition. A setting of 0 to 1,000 may be entered in 0.1 increments. OEL, Loop Gain Kg. Sets the coarse loop-gain level of the PID algorithm for the overexcitation limiter. A setting of 0 to 1,000 may be entered in 0.1 increments. UEL, Integral Gain KI. Adjusts the rate at which the DECS-200 responds during an underexcitation condition. A setting of 0 to 1,000 may be entered in 0.1 increments. UEL, Loop Gain Kg. Sets the coarse loop-gain level of the PID algorithm for the underexcitation limiter. A setting of 0 to 1,000 may be entered in 0.1 increments Voltage Matching, Loop Gain Kg. Adjusts the coarse loop-gain level of the PID algorithm for matching the generator voltage to the bus voltage. A setting of 0 to 1,000 may be entered in 0.1 increments. Analysis The Analysis screen consists of four tabs labeled AVR, FCR, var, and PF. To view the Analysis screen, click the Analysis button on the tool bar or click Screens on the menu bar and click Analysis. Trigger Data Logging on Step Change. Checking this box causes an oscillography report to be triggered every time that a step change occurs. AVR AVR tab settings are illustrated in Figure 5-21 and described in the following paragraphs. Voltage Step Response, Increment of AVR Setpoint. Sets the voltage step size that the DECS-200 uses when incrementing the generator terminal voltage setpoint. A setting of 0 to 10% may be entered in 1% increments. A button adjacent to this setting is clicked to increment the terminal voltage setpoint. A readonly field indicates the terminal voltage setpoint that will be achieved when the increment button is clicked. If the specified step size is outside the setpoint limit, a warning message will appear. Voltage Step Response, AVR Setpoint. This read-only field indicates the generator terminal voltage setpoint that was set on the AVR/FCR tab of the Setting Adjustments screen. A button adjacent to this field is clicked to return the AVR setpoint to the displayed value. Voltage Step Response, Decrement of AVR Setpoint. Sets the voltage step size that the DECS-200 uses when decrementing the generator terminal voltage setpoint. A setting of 0 to 10% may be entered in 1% increments. A button adjacent to this setting is clicked to decrement the terminal voltage setpoint. A readonly field indicates the terminal voltage setpoint that will be achieved when the decrement button is clicked. Voltage Step Response, Vrms. This read-only field indicates the value of terminal voltage. The other three fields are described in the corresponding tab setting descriptions. Alarm Signals. During step response analysis, nine alarm indicators are available to indicate system alarms. The indicators annunciate the following conditions: Field overcurrent Field overvoltage Generator overvoltage Generator undervoltage Loss of sensing 9360100990 Rev G

DECS-200 BESTCOMS Software

5-17

Overexcitation limiting System frequency below 10 Hz Underexcitation limiting Underfrequency or volts per hertz

Figure 5-21. Analysis Screen, AVR Tab

FCR FCR tab settings are illustrated in Figure 5-22 and described in the following paragraphs.

Figure 5-22. Analysis Screen, FCR Tab 5-18 DECS-200 BESTCOMS Software 9360100990 Rev G

Field Current Step Response, Increment of FCR Setpoint. Sets the current step size that the DECS-200 uses when incrementing the field current setpoint. A setting of 0 to 10% may be entered in 1% increments. A button adjacent to this setting is clicked to increment the field current setpoint. A read-only field indicates the field current setpoint that will be achieved when the increment button is clicked. If the specified step size is outside the setpoint limit, a warning message will appear. Field Current Step Response, FCR Setpoint. This read-only field indicates the field current setpoint that was set on the AVR/FCR tab of the Setting Adjustments screen. A button adjacent to this field is clicked to return the AVR setpoint to the displayed value. Field Current Step Response, Decrement of FCR Setpoint. Sets the field current step size that the DECS200 uses when decrementing the field current setpoint. A setting of 0 to 10% may be entered in 1% increments. A button adjacent to this setting is clicked to decrement the field current setpoint. A read-only field indicates the field current setpoint that will be achieved when the decrement button is clicked. Field Current Step Response, Ifd. This read-only field indicates the value of field current. The other three fields are described in the corresponding tab setting descriptions. Alarm Signals. During step response analysis, nine alarm indicators are available to indicate system alarms. A list of the indicators is provided under Analysis, AVR. Alarm annunciations are updated approximately once every second. Var Var tab settings are illustrated in Figure 5-23 and described in the following paragraphs.

Figure 5-23. Analysis Screen, var Tab Reactive Power Step Response, Range Control, Min. Changes the range indicated by the var Step Settings dial and the minimum allowable var settings for the generator. To change the minimum dial value, double-click the field value, enter a new minimum limit, and press the Enter key. Reactive Power Step Response, Range Control, Max. Changes the range indicated by the var Step Settings dial and the minimum allowable var settings for the generator. To change the maximum dial value, double-click the field value, enter a new minimum limit, and press the Enter key. Reactive Power Step Response, Setpoint Value. This read-only field indicates the reactive power setpoint established on the var/PF tab of the Setting Adjustments screen. If a step-response setpoint change has been made from this screen, the actual setpoint value for the regulator will differ from this read-only indication. Reactive Power Step Response, Step Value Change var Value. Provides one of three methods for changing the kvar setpoint and observing the generator response. (The other two methods include 9360100990 Rev G DECS-200 BESTCOMS Software 5-19

adjusting the var Step Settings dial or slide bar.) Once the desired value is entered, the value is sent to the DECS-200 by clicking the Send var Value to DECS (OK) button. When clicked and held, the button color changes to red and the button label changes to Index 1. Upon release of the button, the new var value setting is sent to the DECS-200 as the reactive power setpoint for the var regulator. If the specified var value is outside the range limit, a dialog box appears and shows the acceptable values for the step response. Changing the var setpoint through the var Value field does not change the dial or slide indicators. The pointer of the var Step Settings dial can be clicked and dragged to the approximate, desired setting. As the pointer is dragged, the slide bar moves to show the relative percentage of the minimum or maximum var setting. The setpoint can then be fine tuned using the up and down scrolling buttons of the var Value window. Reactive Power Step Response, Step Value Change Index. Up to three var step-response setpoints (indexes) can be activated. An index is created by using the methods described in the previous paragraphs. Index 2 is added by clicking the Add var Step button. (It may be necessary to drag the red index 1 pointer out of the way to access the yellow index 2 pointer.) When the Send var Value to DECS button is clicked and held, the button color changes to yellow and the button label changes to Index 2. A third index is added n the same manner as index 2, but the third index color is blue. Reactive Power Step Response, Var Steps, Add Var Step. Adds a setpoint index. A maximum of three setpoint indexes may be created. Refer to the previous paragraph for additional information on adding setpoint indexes (var Steps). Reactive Power Step Response, Var Steps, Remove Step. Removes the last setpoint index created. Var, Var Step Response. This read-only field indicates the value of the regulated var level. The other three fields are described in the corresponding tab setting descriptions. Alarm Signals. During step response analysis, nine alarm indicators are available to indicate system alarms. A list of the indicators is provided under Analysis, AVR. Alarm annunciations are updated approximately once every second. PF PF tab settings are illustrated in Figure 5-24 and described in the following paragraphs.

Figure 5-24. Analysis Screen, PF Tab Power Factor Step Response, Add PF Step. Adds a power factor setpoint index. Up to three setpoint indexes can be created. The addition of indexes is discussed in the paragraphs describing the Step Value Change settings. Power Factor Step Response, Remove Steps. Removes the last setpoint index created. 5-20 DECS-200 BESTCOMS Software 9360100990 Rev G

Power Factor Step Response, PF Setpoint Value. This read-only field indicates the reactive power setpoint established on the var/PF tab of the Setting Adjustments screen. If a step response setpoint change has been made from this screen, the actual setpoint value for the regulator will differ from this read-only indication. Power Factor Step Response, Step Value Change PF Value. Provides one of two methods for changing the power factor setpoint and observing the generator response. (The other method consists of adjusting the PF Step Response Settings dial.) Once the desired value is entered, the value is sent to the DECS200 by clicking the Send PF Value to DECS button. When clicked and held, the button color changes to red and the button label changes to Index 1. Upon release of the button, the new power factor value is sent to the DECS-200 and the PF setpoint for the power factor regulator. If the specified PF value is outside the range limit, a dialog box appears and shows the acceptable values for the step response. Changing the var setpoint through the PF Value field does not change the dial indicator. The pointer of the PF Step Response Settings dial can be clicked and dragged to the approximate, desired setting. The setpoint can then be fine tuned using the up and down scrolling buttons of the PF Value window. Power Factor Step Response, Step Value Change Index. Up to three power factor step-response setpoints (indexes) can be activated. An index is created by using the methods described in the previous paragraphs. Index 2 is added by clicking the Add PF Step button. (It may be necessary to drag the red Index 1 pointer out of the way to access the yellow index 2 pointer.) When the Send PF Value to DECS button is clicked and held, the button color changes to yellow and the button label changes to Index 2. A third index is added in the same manner as index 2, but the third index color is blue. Power Factor Step Response, PF. This read-only field indicates the value of the regulated power factor level. The other three fields are described in the corresponding tab setting descriptions. Alarm Signals. During step response analysis, nine alarm indicators are available to indicate system alarms. A list of the indicators is provided under Analysis, AVR. Alarm annunciations are updated approximately once every second. Protection/Relay The Protection/Relay screen consists of five tabs labeled Options, Settings, Gain, Relay #1, #2 Logic, Relay #3 Logic, and Relay Settings. To view the Protection/Relay screen, click the Protection button on the tool bar or click Screens on the menu bar and click Protection/Relay. Options Options tab settings are illustrated in Figure 5-25 and described in the following paragraphs. Protection. DECS-200 protection functions are enabled and disabled using these settings. DECS-200 protection functions include generator overvoltage, exciter field overvoltage, open exciter diode, loss of field, generator undervoltage, exciter field overcurrent, and shorted exciter diode. When a protection function is enabled or disabled, the change is sent immediately to the DECS-200. Loss of Sensing Voltage, LOS. Enables and disables the loss of sensing function. Loss of Sensing Voltage, Time Delay. Sets the time delay between when the DECS-200 detects a loss of sensing voltage and when the alarm annunciates and the output relay actuates (if programmed). A setting of 0 to 30 seconds may be entered in 0.1 second increments. Loss of Sensing Voltage, Balanced Level. When all phases of sensing voltage decrease below this setting, the loss of sensing voltage time delay begins timing out. A setting of 0 to 100% (of nominal) may be entered in 0.1% increments. Loss of Sensing Voltage, Unbalanced Level. When any one of three phases of sensing voltage decreases below this setting, the loss of sensing voltage time delay begins timing out. This setting applies to threephase sensing applications only. A setting of 0 to 100% (of nominal) may be entered in 0.1% increments. Loss of Sensing Voltage, Transfer to FCR Mode. Enables and disables a transfer from AVR mode to FCR mode when a loss of sensing voltage condition occurs.

9360100990 Rev G

DECS-200 BESTCOMS Software

5-21

Figure 5-25. Protection Screen, Options Tab Settings Settings tab settings are illustrated in Figure 5-26 and described in the following paragraphs.

Figure 5-26. Protection Screen, Settings Tab Generator Overvoltage, Level. Configures the setpoint, in primary voltage, for generator overvoltage protection. This setting is active only when generator overvoltage protection is enabled on the Options tab. When the generator terminal voltage reaches the level of this setting and the associated time delay expires, the corresponding protection alarm LED lights. (See the Alarm/Status or Analysis screens for the location of the specific alarm signal LEDs.) If programmed for the overvoltage function, one or more of the three programmable output relays are actuated. A setting of 0 to 30,000 Vac may be entered in 1 Vac increments. 5-22 DECS-200 BESTCOMS Software 9360100990 Rev G

Generator Overvoltage, Delay. Sets the time delay for the generator overvoltage protection function. This setting is active only when generator overvoltage protection is enabled on the Options tab. A setting of 0.1 to 60 seconds may be entered in 0.1 second increments. Exciter Field Overvoltage, Level. Configures the setpoint for field overvoltage protection. This setting is active only when field overvoltage protection is enabled on the Options tab. When the field voltage reaches the level of this setting and the associated time delay expires, the corresponding protection alarm indicator lights. (See the Alarm/Status or Analysis Screen for the detailed alarm LED signals.) If programmed for the field overvoltage function, one or more of the three programmable output relays are actuated. A setting of 1 to 325 Vdc may be entered in 1 Vdc increments. Exciter Field Overvoltage, Delay. Sets the time delay for the field overvoltage protection function. This setting is active only when field overvoltage protection is enabled on the Options tab. A setting of 0.2 to 30 seconds may be entered in 0.1 second increments. Exciter Open Diode, Level. Configures the percent of rated field current that indicates an open exciter diode. This setting is active only when open exciter diode protection is enabled on the Options tab. A setting of 0 to 100% may be entered in 0.1% increments. Exciter Open Diode, Inhibit Level. Configures the percent of rated field current that disables both openand shorted-diode protection. This setting is active only when open exciter diode protection is enabled on the Options tab. A setting of 0 to 100% may be entered in 0.1% increments. Exciter Open Diode, Delay. Sets the time delay between when an open exciter diode is detected and annunciated. This setting is active only when open exciter diode protection is enabled on the Options tab. A setting of 10 to 60 seconds may be entered in 0.1 second increments. Generator Undervoltage, Level. Configures the setpoint for generator undervoltage protection. This setting is active only when generator undervoltage protection is enabled on the Options tab. When the generator terminal voltage reaches the level of this setting and the associated time delay expires, the corresponding protection alarm LED lights. (See the Alarm/Status or Analysis screen for the detailed alarm LED signals.) If programmed for the undervoltage function, one or more of the three programmable output relays are actuated. A setting of 0 to 30,000 Vac may be entered in 1 Vac increments. Generator Undervoltage, Delay. Sets the time delay for the generator undervoltage protection function. This setting is active only when generator undervoltage protection is enabled on the Options tab. A setting of 0.5 to 60 seconds may be entered in 0.1 second increments. Exciter Field Overcurrent, Level. Configures the setpoint for field overcurrent protection. This setting is active only when field overcurrent protection is enabled on the Options tab. When the field current exceeds the level of this setting and the associated time delay expires, the corresponding protection alarm LED lights. (See the Alarm/Status or Analysis Screen for the detailed alarm LED signals.) If programmed for the field overcurrent function, one or more of the three programmable output relays are actuated. A setting of 0.1 to 16.0 Adc may be entered in 0.1 Adc increments. Exciter Field Overcurrent, Delay. Selects the time delay between when the field current reaches the Exciter Field Overcurrent Level setting and when the alarm annunciates. The time delay is initiated when the sensed current exceeds the overcurrent setpoint and is inversely proportional to the overcurrent level. The higher the current level, the less time delay before alarm annunciations. This setting is active only when shorted exciter diode protection is enabled on the Options tab. A setting of 0.1 to 20 seconds may be entered in 0.1 second increments. Exciter Shorted Diode, Level. Configures the percent of rated field current that indicates a shorted exciter diode. This setting is active only when shorted exciter diode protection is enabled on the Options tab. A setting of 0 to 100% may be entered in 0.1% increments. Exciter Shorted Diode, Delay. Sets the time delay between when a shorted exciter diode is detected and annunciated. This setting is active only when shorted exciter diode protection is enabled on the Options tab. A setting of 5 to 30 seconds may be entered in 0.1 second increments. Loss of Field, Level. Configures the setpoint for loss of field protection. This setting is active only when loss of field protection is enabled on the Options tab. When the kvar value decreases below the negative value of this setting for the duration of the Loss of Field Delay setting, the corresponding protection alarm LED lights. (See the Alarm/Status tab of the Metering screen or the Analysis screen for the detailed alarm LED signals.) Any of the three programmable DECS-200 output relays can be programmed to annunciate a loss of field condition. A setting of 0 to 3,000,000 kvar may be entered in1 kvar increments. Loss of Field, Delay. Sets the loss of field protection time delay. This setting is active only when loss of field protection is enabled. A setting of 0 to 9.9 seconds may be entered in 0.1 second increments. 9360100990 Rev G DECS-200 BESTCOMS Software 5-23

Relay Logic Logic settings for the three programmable relays are divided between two tabs labeled Relay #1, #2 Logic and Relay #3 Logic. Because the settings for each programmable relay are identical, only the Relay #1, #2 Logic tab is illustrated here (Figure 5-27).

Figure 5-27. Protection Screen, Relay #1, #2 Logic Tab Protection. A programmable relay can be configured to annunciate any of nine active protection functions. These protection functions include: Field overcurrent Loss of sensing voltage Field overvoltage Open exciter diode Generator overvoltage Shorted exciter diode Generator undervoltage System frequency below 10 Hz Loss of field Setpoint Limit. A programmable output can be configured to close when the active setpoint reaches the upper limit or lower limit. FCR Mode. Enabling this setting closes the programmable output when the DECS-200 is operating in FCR (Manual) mode. Limit. A programmable output can be configured to close when the following limits are reached: overexcitation, stator current, underfrequency or volts per hertz, and underexcitation. Relay Setting Contact settings for each of the three programmable relays are adjusted on the Relay Setting tab. Relay Setting tab settings are illustrated in Figure 5-28 and described in the following paragraphs. Contact Status. Configures the output contacts as normally open (NO) or normally closed (NC). Normally closed, programmable relay outputs do not remain closed when control power is removed from the DECS-200. Contact Type. Selects one of three contact types: Momentary, Maintained, or Latched. Selecting Momentary closes or opens the relay contacts for the duration determined by the Momentary Time setting. Selecting Maintained closes or opens the relay contact for the duration of the condition triggering the relays change of state. Selecting Latched latches the relay contacts closed or open until the relay is reset by the user. Momentary Time. When Momentary is selected as the contact type, this setting controls the duration that the contact is open/closed when the relay output is active. A setting of 0.1 to 5 seconds may be entered in 0.05 second increments. 5-24 DECS-200 BESTCOMS Software 9360100990 Rev G

Figure 5-28. Protection Screen, Relay Setting Tab Data Log The Data Log screen consists of three tabs labeled Log Setup/Sequence of Events, Logic Triggers, and Level Triggers/Logged Parameters. To view the Data Log screen, click the Data Log button on the tool bar or click Screens on the menu bar and click Data Log. Log Setup/Sequence Of Events Log Setup/Sequence of Events tab settings are illustrated in Figure 5-29 and described in the following paragraphs.

Figure 5-29. Data Log Screen, Log Setup/Sequence of Events Tab 9360100990 Rev G DECS-200 BESTCOMS Software 5-25

Data Logging Setup, Data Logging Enable. Enables and disables data logging. Data Logging Setup, Pre-Trigger Points. Selects the number of data points that are recorded prior to a data log being triggered. A setting of 0 to 599 may be entered in increments of 1. Data Logging Setup, Post Trigger Points. Displays the number of data points that are recorded after a data log is triggered. The value of this read-only field is determined by the Pre-Trigger Points and Sample Interval settings. Data Logging Setup, Sample Interval. Establishes the sample rate of the data points. When the Generator Frequency setting (System Configuration screen, System Options tab) is 60 hertz, a sample interval of 0.016 to 10 seconds may be selected from the pull-down menu. When the Generator Frequency setting is 50 hertz, a sample interval of 0.004 to 10 seconds may be selected from the pull-down menu. Data Logging Setup, Pre-Trig Duration. Displays the length of time that pre-trigger data points are recorded. The value of this read-only field is determined by the Pre-Trigger Points and Sample Interval settings. Data Logging Setup, Post Trig Duration. Displays the length of time that post-trigger data points are recorded. The value of this read-only field is determined by the Pre-Trigger Points and Sample Interval settings. Data Logging Setup, Total Log Duration. Displays the total recording time for a data log and equals the sum of the values in the Pre-Trig Duration and Post Trig Duration fields. The value of this read-only field is determined by the Pre-Trigger Points and Sample Interval settings. View Sequence Of Events Reporting. Clicking this button displays the Sequence of Events Reporting screen (Figure 5-30). Sequence of Events Reporting screen displays and controls are described in the following paragraphs.

Figure 5-30. Sequence of Event Reporting Report Summary. This area of the Sequence of Event Recording screen lists the available sequence of events records. The records displayed are determined by the selection made in the Display the Following Events setting area. Event List. This area of the Sequence of Event Recording screen lists the available sequence of events records. The records displayed are determined by the selection made in the Display the Following Events setting area. Reset New Event List. Clicking this button clears all new events from the Event List. Display the Following Events. The event type displayed in the Event List is controlled by selection made here. Available event-type selections are New, All New and Old, New Alarm, New I/O, and New Mode. Print/Save Report. Clicking this button allows the report to be saved as a text file or printed. 5-26 DECS-200 BESTCOMS Software 9360100990 Rev G

View and Download Data log. Clicking this button displays the Data Logging screen of Figure 5-31. Data Logging screen displays and controls are described in the following paragraphs.

Figure 5-31. Data Logging Screen Report Summary. This area of the Data Logging screen displays information such as the time and date, station, device and user identification information, and the number of new and total records. Event List. This area of the Sequence of Event Recording screen lists the available sequence of events records. The records displayed are determined by the selection made in the Display the Following Events setting area. Selected Record Information. This area of the Data Logging screen displays information relating to the data log record selected in the Record List. Displayed information includes the number of pre-trigger points, number of post-trigger points, total number of points, the sample interval, and the number of parameters reported. Data Record List Options, Reset New Record Counter. Clicking this button resets the number of new records reported in the Report Summary to zero. Data Record List Options, Reset Total Record Counter. Clicking this button resets the number of total records reported in the Report Summary to zero. Data Record List Options, Trigger a Record. Clicking this button manually triggers data record acquisition. A data log cannot be manually triggered unless data logging is enabled on the Log Setup/Sequence of Events tab. Data Record List Options, Stop Record. Clicking this button ends acquisition of a manually triggered data record. Data Record List Options, Refresh Summary and List. Clicking this button updates the Report Summary data and Record List with the latest available information. Data Record List Options, Download Selected Record. Clicking this button downloads the selected record and allows it to be saved as either a text file or a COMTRADE file viewable in BESTwave. Print/Save Report. Clicking this button allows a report to be either saved as a text file or printed. Print/Save Record. Clicking this button allows a record to be either saved as a text file or printed. Logic Triggers Logic Triggers tab settings are illustrated in Figure 5-32 and described in the following paragraphs.

9360100990 Rev G

DECS-200 BESTCOMS Software

5-27

Figure 5-32. Data Log Screen, Logic Triggers Tab Contact Inputs. This area of the Logic Triggers tab lists the available DECS-200 contact inputs that can be selected to trigger a data log report. The following contact inputs are available for triggering a data log report: 52J/K AVR 52L/M FCR Alarm Reset Pre-Position Any combination of contact inputs may be selected. Secondary Enable Start Stop

Relay Outputs. This area of the Logic Triggers tab lists the DECS-200 contact outputs that can be selected to trigger a data log report. The following relay outputs are available for triggering a data log report: Relay 1 Relay 3 Relay 2 Stop/Start Any combination of relay outputs may be selected. Watchdog

Alarm States. This area of the Logic Triggers tab lists the available alarm conditions that can be selected to trigger a data log report. The following alarm conditions are available for triggering a data log report: Generator sensing <10 Hz Generator undervoltage Loss of field Loss of sensing Overexcitation limit Setpoint at lower limit Any combination of alarm states may be selected. Exciter field overcurrent Exciter field overvoltage Exciter open diode FCR mode Generator overvoltage Setpoint at upper limit Shorted exciter diode Stator current limit Underexcitation limit Underfrequency

System Status, Start/Stop. Enables the Start or Stop mode to trigger a data log report. Selecting No Trigger disables a Start or Stop mode trigger. System Status, Soft Start. Enables a data log report to be triggered when Underfrequency protection is active or inactive. Selecting No Trigger disables a Soft Start trigger. System Status, Underfrequency. Enables a data log report to be triggered when either AVR mode or FCR mode is active. Selecting No Trigger disables an Underfrequency trigger. System Status, Control Mode. Enables a data log report to be triggered when either AVR mode or FCR mode is active. Selecting No Trigger disables a control mode trigger. 5-28 DECS-200 BESTCOMS Software 9360100990 Rev G

System Status, Operating Mode. Enables a data log report to be triggered when power factor control is active or var control is active. Selecting No Trigger disables an operating mode trigger. System Status, Load Compensation. Enables a data log report to be triggered when droop compensation is active or inactive. Selecting No Trigger disables a load compensation trigger. System Status, Limiter Mode. Enables a data log report to be triggered when the underexcitation limiter, overexcitation limiter, or stator current limiter are active. Additionally, a data log report can be triggered when two of the limiters are active. The available limiter mode selections are listed below: No Trigger (disables a limiter mode trigger) OEL (overexcitation limiter active) Off (no limiters active) SCL (stator current limiter active) SCL, OEL (stator current limiter and overexcitation limiter active) SCL, UEL (stator current limiter and underexcitation limiter active) UEL (underexcitation limiter active) UEL, OEL (underexcitation limiter and overexcitation limiter active)

System Status, Voltage Matching. Enables a data log report to be triggered when voltage matching is enabled (On) or disabled (Off). Selecting No Trigger disables a voltage matching trigger. System Status, Auto Tracking. Enables a data log report to be triggered when the DECS-200 is functioning as the primary controller or the secondary controller in a redundant DECS-200 system. Selecting No Trigger disables an auto-tracking trigger. Level Triggers/ Logged Parameters The Level Triggers/Logged Parameters tab (Figure 5-33) consists of a list of parameters that can be selected to trigger a data log report. Up to six parameters can be selected as triggers. Each parameter has Level Trigger Enable buttons that are used to trigger a data log when the parameter increases above the upper threshold setting, decreases below the lower threshold setting, or either increases above or decreases below the upper or lower threshold setting. The available parameters that can be selected to trigger a data log report are listed in Table 5-2.

Figure 5-33. Data Log Screen, Level Triggers/Logged Parameters

9360100990 Rev G

DECS-200 BESTCOMS Software

5-29

Table 5-2. Data Log Report Parameter Triggers Threshold Unit of Parameter Measure Lower Upper Auto Tracking Output N/A 65535 to 65535 65535 to 65535 Auxiliary Input Voltage PU 2 to 2 2 to 2 Average Gen. Voltage, L-L PU 2 to 2 2 to 2 AVR Error Signal N/A 65535 to 65535 65535 to 65535 Bus Frequency Hz 0 to 90 0 to 90 Bus Voltage PU 2 to 2 2 to 2 Control Output N/A 65535 to 65535 65535 to 65535 Cross-Current Input PU 2 to 2 2 to 2 Field Current PU 2 to 2 2 to 2 Field Voltage PU 2 to 2 2 to 2 Gen. Apparent Power kVA PU 2 to 2 2 to 2 Gen. Reactive Power kvar PU 2 to 2 2 to 2 Gen. Real Power kW PU 2 to 2 2 to 2 Generator Current Ib PU 2 to 2 2 to 2 Generator Frequency Hz 0 to 90 0 to 90 Generator Power Factor PF 1 to 1 1 to 1 Generator Voltage Vab PU 2 to 2 2 to 2 Generator Voltage Vbc PU 2 to 2 2 to 2 Generator Voltage Vca PU 2 to 2 2 to 2 Phase Angle, V-I Degrees 180 to 180 180 to 180 PID Integrator State N/A 65535 to 65535 65535 to 65535 Var/PF Controller Output N/A 65535 to 65535 65535 to 65535

Increment 1 0.01 0.01 1 0.01 0.01 1 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 1 1

Metering The Metering screen consists of two tabs labeled Operation and Alarm/Status. To view the Metering screen, click the Metering button on the tool bar or click Screens on the menu bar and click Metering/Operation. Operation Operation tab parameters and controls are illustrated in Figure 5-34 and described in the following paragraphs. DECS-200 BESTCOMS software provides real-time monitoring of the following data. This data is refreshed approximately once every second. Metering is enabled or disabled through the pull-down menu or by clicking the Metering button. Real-time metering values on the Operation tab are refreshed approximately once per second. Metering is enabled or disabled through the Metering menu on the menu bar or by clicking the Metering button. Gen Voltage. Displays three values of generator voltage: Vab, Vbc, and Vca. Gen Current. Displays phase B generator current. Field Voltage. Displays the level of field voltage. Field Current. Displays the level of field current. EDM SD/OD Ripple. Displays the percentage of ripple detected across the exciter diodes by the exciter diode monitor. Bus Voltage. Displays the level of bus voltage. Phase Angle. Displays the phase angle between the generator voltage and current. Position Indication. Displays the relative position (in percent) of the current setpoint value to the programmed minimum or maximum setpoint. 5-30 DECS-200 BESTCOMS Software 9360100990 Rev G

Figure 5-34. Metering Screen, Operation Tab Frequency. Displays the frequency of the generator voltage and bus voltage. Aux DC Input. Displays a value of voltage that is relative to the accessory input voltage or current, depending on the mode selected. Apparent Power. Displays the apparent power, in VA, being supplied by the generator. Real Power. Displays the real power, in watts, being supplied by the generator. Reactive Power. Displays the reactive power, in vars, being supplied by the generator. Power Factor. Displays the operating power factor of the generator. Tracking Error. Displays the ratio, expressed as a percentage, of the nominal value of the tracking mode to the mode being tracked. For example, if operating in AVR mode with 100 Vac nominal generator voltage and a tracking error of 0.5%, a transfer to another operating mode would cause a decrease in generator output voltage to 99.5 Vac. Control Mode. AVR and FCR mode status is reported by two indicators. When the DECS-200 is operating in AVR mode, the AVR indicator changes from gray to red. When operating in FCR mode, the FCR indicator changes from gray to green. A button is provided to toggle between AVR and FCR modes. Operating Status. Three indicators report whether Var mode is active, Power Factor mode is active, or neither mode is active. An option button below each indicator is used to select the corresponding operating mode. When Var mode is active, the Var indicator changes from gray to green. When Power Factor mode is active, the PF indicator changes from gray to red. When neither mode is active, the Off indicator changes from gray to blue. If the control mode is FCR and Var of PF mode is selected, that selection will be ignored by the DECS-200. Even if the Var or PF indicator turns on, the system will not be in those modes unless the DECS-200 52J/K input is open. See Table 5-3 for additional information on 52J/K and 52L/M logic. DECS-200 Operating Mode AVR mode active, off-line OEL enabled, no droop, no var/PF Droop mode active, on-line OEL enabled, no var/PF Var/PF mode active, on-line OEL enabled Table 5-3. 52J/K and 52L/M Logic 52 L/M 52 J/K Generator Operating Mode Closed Closed Single unit/stand-alone Open Closed Paralleled to the utility grid (droop) or two or more generators islanded (droop or cross-current compensation) Paralleled to utility grid

Open

Open

NOTE: If neither var or power factor modes are selected via the operator interfaces, then the operating mode is droop.

9360100990 Rev G

DECS-200 BESTCOMS Software

5-31

System Operating Status. Two indicators show the start/stop mode status of the DECS-200. in Start mode, the START indicator changes from gray to red. In Stop mode, the STOP indicator changes from gray to green. A button is provided for toggling between Start and Stop modes. Pre-position Set. Clicking this button adjusts the excitation setpoint to the pre-position value. Fine Adjustment. Clicking the Raise button increases the active operating setpoint. Clicking the Lower button decreases the active operating setpoint. The raise and lower increment is a function of the setpoint range of adjustment and the active operating setpoint. The raise and lower increment is a function of the setpoint range of adjustment and the active mode traverse rate. The increments are directly proportional to the adjustment range and inversely proportional to the traverse rate. Alarm/Status Alarm/Status tab indicators and controls are illustrated in Figure 5-35 and described in the following paragraphs.

Figure 5-35. Metering Screen, Alarm/Status Tab System Status. When any of the 15 conditions listed in Figure 5-35 exist, the corresponding indicator changes from gray to red. Clicking the Reset Alarms button resets the system status annunciations. Any condition that remains active will annunciate again after the Reset Alarms button is clicked. Switch Status. Three indicators provide contact input status. The 52 JK indicator turns on when the 52J/K contact input is open. The 52 LM indicator turns on when the 52L/M contact is open. The Secondary DECS indicator turns on when the SECEN (secondary enable) contact input is closed. Front Panel LED Signal Status. Six indicators provide remote indication of the front panel LEDs. Refer to Section 2, Human-Machine Interface for information regarding the function of the front panel indicators.

SAVING, PRINTING, AND OPENING FILES


BESTCOMS provides the ability to save DECS-200 settings in a file for reference or future use. Using a settings file can save setup time when configuring multiple units with the same configuration. Settings files may be opened and edited using any text editing application. A settings file can also be printed from BESTCOMS. Saving Files A DECS-200 settings file is saved through a Save As dialog box. The Save As dialog box is accessed by using any of three methods:

5-32

DECS-200 BESTCOMS Software

9360100990 Rev G

Click the Save File button on the tool bar Press Ctrl + A on the keyboard Click File, Save As on the menu bar

The Save As dialog box enables you to navigate to the desired folder and save the DECS-200 settings file. DECS-200 setting files are saved with a .de2 extension. Printing Files A printed copy of DECS-200 settings can be made for record keeping or as a reference. Settings are printed by accessing the print preview screen. The print preview screen is accessed by using any of three methods: Click the Print Data button on the tool bar Press Ctrl + P on the keyboard Click File, Print on the menu bar

Executing a print command displays a user information box with fields for adding a title and comments to the printout. Clicking OK or Cancel displays a print preview of the settings. The print preview screen enables you to select a printer and configure the page layout (Print Setup button), print the settings list (printer icon button), and save the list of settings in a text file (Save button). The BESTCOMS software version, the DECS-200 firmware version, and the time and date are printed along with the settings. Opening/Uploading Files DECS-200 settings files can be opened by BESTCOMS and uploaded to a DECS-200 communicating with the PC running BESTCOMS. A DECS-200 settings file is retrieved through the BESTCOMS Open dialog box. The Open dialog box is accessed by using any of three methods: Click the File Open button on the tool bar Press Ctrl + O on the keyboard Click File, Open on the menu bar

The Open dialog box enables you to navigate to the desired settings file and retrieve the settings. Settings can be retrieved into BESTCOMS and uploaded to the DECS-200 or retrieved into BESTCOMS without uploading to the DECS-200. When you execute the Open command, a warning dialog box appears. This dialog box warns you that equipment damage may occur as a result of the changes that were made in the computer file. If you have confidence that no damage will occur, you may send the data to the DECS-200. CAUTION A file data transfer while the DECS-200 is on-line may result in poor system performance or equipment damage. Make sure that the new settings are safe to upload before you transfer the data file.

If you select Yes, then 17 blocks of DECS-200 setting data are sent to the DECS-200 block by block. Please wait until all 17 blocks of data have been transferred. When power is next applied to the DECS200 unit, the previously saved settings will become the current settings.

PID WINDOW
The PID window of BESTCOMS provides the ability to increase generator stability by changing the PID (proportional + integral + derivative) parameters. PID parameters are calculated automatically after the user selects the generator time constant (Tdo) and/or exciter time constant (Texc). The PID window is accessed by clicking the PID button on the tool bar. This button is enabled only when the Control Gain screen is being viewed and the Stability Range setting is 21. PID window functions are shown in Figure 5-36 and described in the following paragraphs. Field Input Data, Generator Information. This setting field is used to enter and display a descriptive name for the selected group of PID settings. The Generator Information field accepts up to 27 alphanumeric characters.

9360100990 Rev G

DECS-200 BESTCOMS Software

5-33

Field Input Data, Generator Time Constant Tdo. The time constant of the generator is entered in this field. The generator time constant and exciter time constant are used to calculate gain parameters Kp, Ki, and Kd. A setting of 1 to 15 may be selected from the pull-down menu. Field Input Data, Exciter Time Constant Texc. The time constant of the exciter is entered in this field. The exciter time constant and generator time constant are used to calculate gain parameters Kp, Ki, and Kd. The exciter time constant setting range varies according to the generator time constant value selected. The default value for the exciter time constant is the generator time constant divided by six. Field Output Data, Gain Kp. This read-only field displays the calculated value of Kp based on the generator time constant (Tdo) and exciter time constant (Texc). Field Output Data, Gain Ki. This read-only field displays the calculated value of Ki based on the generator time constant (Tdo) and exciter time constant (Te). Field Output Data, Gain Kd. This read-only field displays the calculated value of Kd based on the generator time constant (Tdo) and exciter time constant (Texc).

Figure 5-36. PID Window Field Output Data Gain Kg. This read-only field displays the calculated value of Kg based on the generator time constant (Tdo) and exciter time constant (Texc). Buttons below the Field Output Data fields enable existing PID records to be deleted (Remove Record), enable calculated setting to be saved in a record (Add to PID List), enable a set of PID parameters to be retrieved from the PID list and invoked, and update the PID settings displayed in the PID window and used by the DECS-200N (Update Setting Screen). Clicking the Close button exits the PID window and returns to the Control Gain screen. PID List. This area of the PID window displays the groups of available PID settings. PID Calculations Based On Input Values The available exciter time constant range is determined by the generator time constant input value. (The default value for the exciter time constant is the generator time constant divided by six (Tdo 6).) The generator time constant input value must be in the range of 1.0 to 15.0 seconds and in 0.05 second increments. When the generator time constant value is 1.00, the available exciter time constant range is 0.03 to 0.50 in 0.01 second increments. When the generator time constant value is 15.00, the available exciter time constant range is 0.30 to 3.00 in 0.01 second increments. For example, when you set Tdo = 2.0 seconds, Texc is 0.33. After specifying the input values, a set of PID parameters (Output Data) is generated automatically. If you set Tdo = 5.00 seconds, then Texc will be 0.83 seconds. The calculated KP is 155.47, KI is 138.72, KD is 48, and Kg is 1. PID parameters can be directly removed from, added to, or modified in the PID List Data. PID parameters may also be saved into a file (pidlist.dat).

5-34

DECS-200 BESTCOMS Software

9360100990 Rev G

Adding To PID List CAUTION Improper PID numbers can result in poor system performance or equipment damage.

PID parameters can be added to a list and recalled for operational use and comparison. To add to the list, type the name for the generator (or other appropriate information) in the generator information box. Choose the generator time constant and, if appropriate, the exciter time constant. Observe the PID gain parameters in the Field Output Data boxes. If these gain parameters are appropriate, select the Add to PID List button. To check for the new parameters, pull down the PID Parameters List (click on the down arrow). The new gain and time constant parameters will be displayed. Removing A PID List Record PID parameters can also be removed from the list. To remove a list (record), pull down the PID Parameters List and select the record or list so that the gain and time constant parameters are displayed. Click the Remove Record button and the listed record is deleted. Retrieving Existing Data From PID List To retrieve existing data, pull down the PID Parameters List and select the record or list so that the gain and time constant parameters are displayed and highlighted. Click the Get from a list button and the listed record input and output data displays in the text boxes.

TERMINATING COMMUNICATION
Communication between BESTCOMS and the DECS-200 is terminated by clicking Communications on the menu bar and clicking Close Comm Port.

9360100990 Rev G

DECS-200 BESTCOMS Software

5-35

This page intentionally left blank.

5-36

DECS-200 BESTCOMS Software

9360100990 Rev G

SECTION 6 SETUP
TABLE OF CONTENTS
SECTION 6 SETUP ................................................................................................................................ 6-1 INTRODUCTION.................................................................................................................................... 6-1 Equipment Required........................................................................................................................... 6-1 System Data ....................................................................................................................................... 6-1 SETTINGS ENTRY................................................................................................................................ 6-1 System Configuration Screen............................................................................................................. 6-1 Setting Adjustments Screen ............................................................................................................... 6-4 Protection/Relay Screen................................................................................................................... 6-10 OFF-LINE TESTS - TURBINE NOT SPINNING.................................................................................. 6-13 Start/Stop Tests................................................................................................................................ 6-13 Control Gain Settings ....................................................................................................................... 6-14 PID Settings...................................................................................................................................... 6-14 OFF-LINE TESTS - TURBINE SPINNING .......................................................................................... 6-14 FCR Mode ........................................................................................................................................ 6-14 EXCITATION PERFORMANCE EVALUATION .................................................................................. 6-17 Off-Line Excitation Limiter Operation ............................................................................................... 6-17 Limit and Protection Check .............................................................................................................. 6-18 Parallel Operation, Generator On Line............................................................................................. 6-18 Conclusion Of Testing ...................................................................................................................... 6-20 Figures Figure 6-1. System Options Tab................................................................................................................ 6-2 Figure 6-2. System Data Tab .................................................................................................................... 6-2 Figure 6-3. Rated Data Tab....................................................................................................................... 6-3 Figure 6-4. Auxiliary Input Tab .................................................................................................................. 6-4 Figure 6-5. AVR/FCR Tab ......................................................................................................................... 6-5 Figure 6-6. Var/PF Tab.............................................................................................................................. 6-5 Figure 6-7. Startup Tab ............................................................................................................................. 6-6 Figure 6-8. Setting Adjustments Screen, OEL Type Tab .......................................................................... 6-7 Figure 6-9. OEL Summing Tab.................................................................................................................. 6-7 Figure 6-10. Setting Adjustments Screen, OEL (Takeover) Tab............................................................... 6-8 Figure 6-11. UEL Tab ................................................................................................................................ 6-9 Figure 6-12. Setting Adjustments Screen, SCL Tab ................................................................................. 6-9 Figure 6-13. Protection Options Tab ....................................................................................................... 6-10 Figure 6-14. Protection Settings Tab....................................................................................................... 6-11 Figure 6-15. Relay #1, #2 Logic Tab ....................................................................................................... 6-12 Figure 6-16. Relay Setting Tab................................................................................................................ 6-13 Figure 6-17. Field Voltage Output Waveform.......................................................................................... 6-15 Figure 6-18. KG Gain Effect on Generator Performance ......................................................................... 6-16 Figure 6-19. Insufficient Proportional Gain.............................................................................................. 6-16 Figure 6-20. Prolonged Instability............................................................................................................ 6-16 Figure 6-21. Insufficient Derivative Gain ................................................................................................. 6-17 Figure 6-22. Final Solution Step Response............................................................................................. 6-17 Tables Table 6-1. Generator and Field Ratings .................................................................................................... 6-1 Table 6-2. Programmable Output Function Assignments ....................................................................... 6-12

9360100990 Rev G

DECS-200 Setup

This page intentionally left blank.

ii

DECS-200 Setup

9360100990 Rev G

SECTION 6 SETUP
INTRODUCTION
This section provides generic setup and operation procedures for excitation systems using the DECS200. These procedures are provided only as a guide and are not intended as a replacement for the setup and operation procedures required by a specific system. In these procedures, DECS-200 settings are entered through the BESTCOMS interface. Therefore, a PC operating with BESTCOMS software will need to be connected to the DECS-200 being configured. For information about using BESTCOMS, refer to Section 5, BESTCOMS Software. Equipment Required The following equipment is required to perform the procedures presented here: Two-channel chart recorder or the DECS-200s oscillography. First channel measures the generator voltage at DECS-200 terminals A1 (E1) and A3 (E3). Second channel measures the field voltage at DECS-200 terminals C5 (F+) and C6 (F). Oscilloscope Personal computer (PC) running BESTCOMS. The minimum requirements for a PC running BESTCOMS are provided in Section 5, BESTCOMS Software. Nine-pin serial communication cable to connect the DECS-200 to the PC.

Basler Electric Application Note 126, while not required, provides helpful information about paralleling circuits. This application note is available for downloading (in PDF format) from the Basler Electric website at www.basler.com. System Data Record your system ratings in Table 6-1. Table 6-1. Generator and Field Ratings Generator Ratings Voltage: Frequency: Reactive Power: Rotational Speed: Vac Hz kvar rpm Exciter Field Ratings No-Load Voltage: No-Load Current: Full-Load Voltage: Full-Load Current: Vdc Adc Vdc Adc

SETTINGS ENTRY
The DECS-200 settings entered on each BESTCOMS screen should be evaluated to ensure that they are appropriate for the application. When entering settings, remember to press the Enter key to save individual settings or click the SendToDECS button to save all of the settings on a screen. System Configuration Screen As shown in the following paragraphs, enter the desired settings on each tab of the Configuration screen. Review those settings and enable the functions that apply. System Options Select the desired system options illustrated in Figure 6-1. Select the limiter mode ................................................................................................................. _________ Select the sensing configuration................................................................................................... _________ Select the underfrequency mode.................................................................................................. _________ Select the nominal generator frequency....................................................................................... _________ Enable or disable voltage matching.............................................................................................. _________ 9360100990 Rev G DECS-200 Setup 6-1

Figure 6-1. System Options Tab System Data Enter the system PT and CT ratings and configure the internal and external tracking settings illustrated in Figure 6-2.

Figure 6-2. System Data Tab Enter the generator PT primary voltage rating ............................................................................. ________ Enter the generator PT secondary voltage rating......................................................................... ________ Enter the generator CT primary current rating ............................................................................. ________ 6-2 DECS-200 Setup 9360100990 Rev G

Enter the generator CT secondary current rating......................................................................... _________ Enter the bus PT primary voltage rating (if applicable) ................................................................ _________ Enter the bus PT secondary voltage rating (if applicable)............................................................ _________ Enable or disable internal tracking ............................................................................................... _________ Set the internal tracking delay (1 second is suggested)............................................................... _________ Set the internal tracking traverse rate (10 seconds is suggested) ............................................... _________ Enable or disable external tracking (applies only to redundant DECS-200 systems).................. _________ Set the external tracking delay (applies only to redundant DECS-200 systems)......................... _________ Set the external tracking traverse rate (applies only to redundant DECS-200 systems) ............. _________ Rated Data Enter the generator and exciter field ratings and exciter-to-generator pole ratio settings illustrated in Figure 6-3.

Figure 6-3. Rated Data Tab Enter the rated generator terminal voltage................................................................................... _________ Enter the rated generator current ................................................................................................. _________ Enter the rated generator power factor ........................................................................................ _________ Enter the exciter-to-generator pole ratio....................................................................................... _________ Enter the rated exciter field voltage ............................................................................................. _________ Enter the rated exciter field current .............................................................................................. _________ Auxiliary Input Configure the accessory input selections and settings illustrated in Figure 6-4. Select either voltage or current as the accessory input type........................................................ _________ Select either inner loop (AVR/FCR) or outer loop (var/PF) as the summing type........................ _________ Enter the accessory input gain (multiplier) setting for AVR mode................................................ _________ Enter the accessory input gain (multiplier) setting for FCR mode................................................ _________ 9360100990 Rev G DECS-200 Setup 6-3

Figure 6-4. Auxiliary Input Tab Enter the accessory input gain (multiplier) setting for var mode .................................................. ________ Enter the accessory input gain (multiplier) setting for Power Factor mode.................................. ________ Enter the droop compensation level for paralleled generators or line-drop compensation.......... ________ Enter the cross-current compensation (reactive differential) gain for paralleled generators........ ________ Setting Adjustments Screen Enter the desired settings and enable the desired functions on each tab of the BESTCOMS Setting Adjustments screen. Figures 6-5 through 6-9 illustrate the settings of each System Configuration screen tab. AVR/FCR Configure the AVR mode and FCR mode settings illustrated in Figure 6-5. During commissioning, review setpoints unique for starting; especially review those for the FCR (manual) mode where the system would be started at the no-load excitation value or less. If pre-position is used, set the pre-position values as required. Enter the AVR setpoint based on the generator terminal voltage ................................................ ________ Enter the minimum desired AVR mode setpoint, expressed as a percent of nominal ................. ________ Enter the maximum desired AVR mode setpoint, expressed as a percent of nominal ................ ________ Enter the AVR mode traverse rate ............................................................................................... ________ Enter the AVR mode pre-position setpoint ................................................................................... ________ Select either maintain or release as the AVR pre-position mode................................................. ________ Enter the field current setpoint for FCR mode.............................................................................. ________ Enter the minimum desired FCR mode setpoint, expressed as a percent of nominal ................. ________ Enter the maximum desired FCR mode setpoint, expressed as a percent of nominal ................ ________ Enter the FCR mode traverse rate ............................................................................................... ________ 6-4 DECS-200 Setup 9360100990 Rev G

Figure 6-5. AVR/FCR Tab Enter the FCR mode pre-position setpoint ................................................................................... _________ Select either maintain or release as the FCR pre-position mode................................................. _________ Var/PF Configure the var mode and power factor mode settings illustrated in Figure 6-7. If var or PF mode is enabled, the setpoint will be active only after transfer occurs into the specific mode because autotracking always forces a null condition to any operating mode.

Figure 6-6. Var/PF Tab 9360100990 Rev G DECS-200 Setup 6-5

Enter the var mode setpoint ......................................................................................................... ________ Enter the minimum desired var mode setpoint, expressed as a percent of nominal ................... ________ Enter the maximum desired var mode setpoint, expressed as a percent of nominal .................. ________ Enter the var mode traverse rate.................................................................................................. ________ Enter the var mode pre-position setpoint...................................................................................... ________ Select either maintain or release as the var pre-position mode ................................................... ________ Set the voltage correction band for var and PF modes ................................................................ ________ Enter the PF mode setpoint.......................................................................................................... ________ Enter the limit for leading power factor ......................................................................................... ________ Enter the limit for lagging power factor ......................................................................................... ________ Enter the PF mode traverse rate .................................................................................................. ________ Enter the PF mode pre-position setpoint...................................................................................... ________ Select either maintain or release as the PF pre-position mode ................................................... ________ Startup Configure the startup control, underfrequency, and voltage matching settings illustrated in Figure 6-7.

Figure 6-7. Startup Tab Enter the soft-start voltage offset used during startup.................................................................. ________ Enter the soft-start time limit used during startup......................................................................... ________ Enter the corner frequency for generator underfrequency protection .......................................... ________ Enter the generator frequency slope for underfrequency protection............................................ ________ Enter the voltage matching band, expressed as a percent of the rated generator voltage.......... ________ Enter the ratio (percentage) of the generator PT output to the bus PT output............................. ________

6-6

DECS-200 Setup

9360100990 Rev G

OEL Type Select either Summing Point or Takeover as the overexcitation limiter style. Select the desired OEL setting selection option. OEL Type tab selections are illustrated in Figure 6-8.

Figure 6-8. Setting Adjustments Screen, OEL Type Tab Summing-Point OEL If summing-point overexcitation limiting is enabled, configure the off- and on-line OEL settings illustrated in Figure 6-10.

Figure 6-9. OEL Summing Tab

9360100990 Rev G

DECS-200 Setup

6-7

Enter the high-level current setpoint for off-line overexcitation limiting ........................................ ________ Enter the duration for high-level, off-line overexcitation limiting................................................... ________ Enter the low-level current setpoint for off-line overexcitation limiting ......................................... ________ Enter the high-level current setpoint for on-line overexcitation limiting ........................................ ________ Enter the duration for high-level, on-line overexcitation limiting................................................... ________ Enter the medium-level current setpoint for on-line overexcitation limiting .................................. ________ Enter the duration for medium-level, on-line overexcitation limiting............................................. ________ Enter the low-level current setpoint for on-line overexcitation limiting ......................................... ________ Takeover OEL If takeover style overexcitation limiting is enabled, configure the off- and on-line OEL settings illustrated in Figure 6-10.

Figure 6-10. Setting Adjustments Screen, OEL (Takeover) Tab Enter the low-level current setpoint for off-line overexcitation limiting ......................................... ________ Enter the high-level current setpoint for off-line overexcitation limiting ........................................ ________ Enter the time delay for off-line overexcitation limiting ................................................................. ________ Enter the low-level current setpoint for on-line overexcitation limiting ......................................... ________ Enter the high-level current setpoint for on-line overexcitation limiting ........................................ ________ Enter the time delay for on-line overexcitation limiting ................................................................. ________ UEL Set the underexcitation limiter values based on the generator capability curve. Either internal or customized UEL settings can be applied. When internal UEL settings are used, only one data point is required. When customized UEL settings are used, up to five data coordinates may be entered to match a specific generator curve. Figure 6-11 illustrates the settings of the UEL tab.

6-8

DECS-200 Setup

9360100990 Rev G

Figure 6-11. UEL Tab SCL Configure the stator current limiter settings illustrated in Figure 6-12.

Figure 6-12. Setting Adjustments Screen, SCL Tab Enter the high-level current setpoint for stator current limiting..................................................... _________ Enter the duration for high-level stator current limiting................................................................. _________ Enter the low-level current setpoint for stator current limiting ...................................................... _________

9360100990 Rev G

DECS-200 Setup

6-9

Protection/Relay Screen Enter the desired settings and enable the desired functions on each tab of the BESTCOMS Protection/Relay screen. Figures 6-13 through 6-16 illustrate the settings of each Protection/Relay screen tab. Options Enable/disable the protection functions and configure the loss of sensing voltage settings illustrated in Figure 6-13.

Figure 6-13. Protection Options Tab Enable or disable generator overvoltage protection..................................................................... ________ Enable or disable field overvoltage protection.............................................................................. ________ Enable or disable open exciter diode protection .......................................................................... ________ Enable or disable generator undervoltage protection................................................................... ________ Enable or disable field overcurrent protection .............................................................................. ________ Enable or disable shorted exciter diode protection ...................................................................... ________ Enable or disable loss of field protection...................................................................................... ________ Enable or disable loss of sensing voltage protection ................................................................... ________ Enter the time delay for loss of sensing annunciation .................................................................. ________ Enter the balanced loss of sensing threshold............................................................................... ________ Enter the unbalanced loss of sensing threshold........................................................................... ________ Enable or disable a transfer to FCR mode when loss of sensing is detected .............................. ________ Settings Enter the protection settings illustrated in Figure 6-14. Only protection functions enabled on the Options tab need to be configured here. Enter the threshold for generator overvoltage protection ............................................................. ________ Enter the time delay for generator overvoltage protection ........................................................... ________

6-10

DECS-200 Setup

9360100990 Rev G

Figure 6-14. Protection Settings Tab Enter the threshold for field overvoltage protection...................................................................... _________ Enter the time delay for field overvoltage protection .................................................................... _________ Enter the percent of rated field current that indicates an open exciter diode............................... _________ Enter the percent of rated field current that disables open- and shorted-diode protection .......... _________ Enter the annunciation time delay for open exciter diode protection ........................................... _________ Enter the threshold for generator undervoltage protection........................................................... _________ Enter the time delay for generator undervoltage protection ......................................................... _________ Enter the threshold for field overcurrent protection ...................................................................... _________ Enter the time delay for field overcurrent protection..................................................................... _________ Enter the percent of rated field current that indicates a shorted exciter diode............................. _________ Enter the annunciation time delay for shorted exciter diode protection ....................................... _________ Enter the threshold for loss of field protection .............................................................................. _________ Enter the time delay for loss of field protection ............................................................................ _________ Relay Logic Review the excitation system interconnection drawings and verify the relay configurations. Relay logic settings for each of the three DECS-200 programmable outputs are contained on two tabs with identical configuration options. Only the tab for Relays 1 and 2 is illustrated here (Figure 6-15). Table 6-2 lists all of the available functions that can be assigned to the programmable outputs. Checkmarks may be placed in Table 6-2 to identify the functions assigned to each relay output.

9360100990 Rev G

DECS-200 Setup

6-11

Figure 6-15. Relay #1, #2 Logic Tab Table 6-2. Programmable Output Function Assignments Relay Function Generator overvoltage Generator undervoltage Loss of sensing voltage Open exciter diode Loss of field Field overvoltage Field overcurrent Sensing input below 10 Hz Shorted exciter diode FCR mode Upper setpoint limit Lower setpoint limit Overexcitation limit Underexcitation limit Underfrequency or V/Hz limit Stator current limit 1 2 3

6-12

DECS-200 Setup

9360100990 Rev G

Relay Setting Configure the contact status and type settings illustrated in Figure 6-16. Select the Relay #1 contact status as normally open (NO) or normally closed (NC)................... _________ Configure the Relay #1 contact type as momentary, maintained, or latched............................... _________ If the Relay #2 contact type is momentary, enter the open/closed contact duration.................... _________ Select the Relay #2 contact status as normally open (NO) or normally closed (NC)................... _________ Configure the Relay #2 contact type as momentary, maintained, or latched............................... _________ If the Relay #2 contact type is momentary, enter the open/closed contact duration.................... _________ Select the Relay #2 contact status as normally open (NO) or normally closed (NC)................... _________ Configure the Relay #2 contact type as momentary, maintained, or latched............................... _________ If the Relay #2 contact type is momentary, enter the open/closed contact duration.................... _________

Figure 6-16. Relay Setting Tab

OFF-LINE TESTS - TURBINE NOT SPINNING


In the following tests, control of the machine is demonstrated via BESTCOMS, front panel HMI, and usersupplied, remote switches. These tests ensure that the machine is not stressed because of incorrect wiring or faulty components. The parameters listed here are only temporary, initial settings. Start/Stop Tests Check the operation of the following start and stop controls. BESTCOMS Metering Screen, Operation tab .............................................................................. _________ DECS-200 front panel .................................................................................................................. _________ Remote switches .......................................................................................................................... _________ With excitation off, check AVR/FCR transfer from the BESTCOMS, the front panel, and remote switches............................................................................................................................ _________ Verify transfer indications from the remote status indicators, front panel HMI, or BESTCOMS interface................................................................................................................... _________ 9360100990 Rev G DECS-200 Setup 6-13

Check the raise and lower limits................................................................................................... ________ Verify raise/lower limit indications from the remote status indicators, front panel HMI, or BESTCOMS interface .............................................................................................................. ________ Control Gain Settings Configure the initial gain settings. Set the generator no-load setpoint in FCR mode (20% of exciter rated current recommended). ________ On the Control Gain screen, enter 200 in the FCR loop gain settings field ................................. ________ Enter the following recommended gain settings for OEL, UEL, and Var/PF. Set OEL KI at 3............................................................................................................................. ________ Set OEL Kg at 5............................................................................................................................ ________ Set UEL KI at 3 ............................................................................................................................. ________ Set UEL Kg at 5 ............................................................................................................................ ________ Set var/PF KI at 3 ......................................................................................................................... ________ Set var/PF Kg at 5 ........................................................................................................................ ________ PID Settings On the Control Gain screen, click the tool bar PID button to open the PID window. (The Control Gain screen Stability Range setting must be 21.) Use the PID window to select the correct PID values based on generator time constant Tdo and exciter time constant Te. For more information about PID settings, refer to Section 5, BESTCOMS Software, PID Window. NOTE If proper startup is not achieved, increase the value of loop gain (Kg) for AVR and FCR modes. The following suggested settings may be used for AVR and FCR modes when the generator and exciter time constants are unknown. Set KP at 80.................................................................................................................................. ________ Set KI at 20 ................................................................................................................................... ________ Set KD at 15 ................................................................................................................................. ________ Set AVR Kg at 7............................................................................................................................ ________ Set TD at 0.01............................................................................................................................... ________ Set FCR Kg at 400........................................................................................................................ ________ Verify transfer indications from the remote status indicators, front panel HMI or BESTCOMS

OFF-LINE TESTS - TURBINE SPINNING


For off-line tests with the turbine spinning, the generator circuit breaker is open. FCR Mode Initial testing should be conducted in FCR (manual) mode and minimum generated voltage. Place the DECS-200 in FCR mode .............................................................................................. ________ Place the Start/Stop switch in the Start position........................................................................... ________ Generator output voltage should build to a percentage of the rated voltage. (The FCR setpoint was set at 20% of the no-load excitation current in a previous step.) ........................................................... ________ Increase the exciter field rated current to 75% of current............................................................. ________ 6-14 DECS-200 Setup 9360100990 Rev G

The generator output voltage should build to a percentage of the rated voltage......................... _________ Use an oscilloscope to check the field voltage for proper output (see Figure 6-17) .................... _________

Figure 6-17. Field Voltage Output Waveform Use a voltmeter to check for correct voltage at generator sensing voltage terminals A1 (E1), A2 (E2), and A3 (E3) .................................................................................................................... _________ Measure the PT secondary voltages ............................................................................................ _________ Use the Raise/Lower control to raise the terminal voltage to the rated generator level............... _________ Place the Start/Stop switch in the Stop position and let the generator voltage decrease to the residual level........................................................................................................................... _________ Place the Start/Stop switch in the Start position to initiate buildup again in FCR mode .............. _________ Record the voltage buildup characteristic as it reaches full, rated output .................................... _________ Using the BESTCOMS Analysis Screen, perform 5% step change in FCR mode ...................... _________ Decrease value, then increase the value. Observe stable performance with chart recorder....... _________ Note the Overshoot and settling time. (The FCR output should be very stable.)......................... _________ Verify that the AVR setpoint tracks the FCR setpoint, then transfer. During this test, use the NOTE In the following steps, verify that, if the pre-position setpoint is enabled, the setpoint changes to the assigned value.

Verify that FCR autotracking follows, and is nulled to AVR, then transfer ................................... _________ Use a chart recorder or BESTCOMS oscillography to perform a step response in AVR mode .. _________ Review the PID numbers.............................................................................................................. _________ On the System Options tab of the BESTCOMS System Configuration screen, turn all limiters off ..................................................................................................................................... _________ Perform a 2% voltage step response and record performance to verify stability ......................... _________ Adjust the PID values until desired performance is achieved. If performance appears stable, repeat step change at 5%............................................................................................................. _________ NOTE Assuming Te (exciter field) is known (as applicable for exciter field voltage regulator applications), increasing Kg will decrease the response time of the generator. See Figure 6-21.

9360100990 Rev G

DECS-200 Setup

6-15

Figure 6-18. KG Gain Effect on Generator Performance When individual adjustment is needed to further refine performance, Figures 6-22 through 6-25 demonstrate the effect that PID changes have for additional control. These figures have a one second major division. In Figure 6-22, the generator voltage exhibits one under-damp (overshoot) and one over-damp (undershoot) before settling. The total time (five seconds) is too long. Here KP (proportional gain) needs to be increased.

Figure 6-19. Insufficient Proportional Gain Figure 6-23 demonstrates that the terminal voltage has prolonged instability after a voltage step change because there is too much integral gain (I). Integral gain value needs to be decreased.

Figure 6-20. Prolonged Instability

6-16

DECS-200 Setup

9360100990 Rev G

In Figure 6-24, less overshoot is desired, KD (derivative gain) is increased.

Figure 6-21. Insufficient Derivative Gain Figure 6-25 illustrates the final solution. Increased KD (derivative gain) decreases voltage overshoot.

Figure 6-22. Final Solution Step Response Place the Start/Stop Switch in the Stop position .......................................................................... _________ Place the system in AVR mode .................................................................................................... _________ Monitor the generator voltage soft start time................................................................................ _________ Place the Start/Stop Switch in the Start position .......................................................................... _________ Use the Raise/Lower control to increase the terminal voltage to the setpoint ............................. _________

EXCITATION PERFORMANCE EVALUATION


In this performance evaluation, temporarily settings will be used to enable the testing of excitation performance without stressing the machine or exceeding ancillary protection device settings. Procedures are provided that will allow you to set your final operating values. This evaluation is a continuation of the previous tests. Off-Line Excitation Limiter Operation In this test, with the generator set below the rated voltage output, the AVR setpoint will be set above the maximum setting and the system should annunciate an alarm. If an alarm is not annuciated, the OEL gain (KI and Kg) may be set too low. If an alarm is annunciated and the system oscillates, the OEL gain, (KI and Kg) may be set too high. Enable the Off-Line Overexcitation Limiter (OEL) ........................................................................ _________ Determine the field current required to reach 105% of the rated generator voltage. ................... _________ Set the off-line OEL for a value equal to the no load field current................................................ _________ Lower the terminal voltage to 10% below rated ........................................................................... _________ To speed performance in the following test, you may increase the OEL gain (KI and Kg terms). On the AVR/FCR tab of the BESTCOMS Setting Adjustments screen, adjust the AVR setpoint to 110% of the rated output. (the AVR Max setting should remain at 105%.).............................. _________ 9360100990 Rev G DECS-200 Setup 6-17

If an output relay is programmed to alarm, the output, BESTCOMS, front panel HMI, and any remote indicator should annunciate the alarm....................................................................... ________ Reset the AVR setpoint to the rated output.................................................................................. ________ Limit and Protection Check In this test, operation of generator overvoltage protection, generator undervoltage protection, field overvoltage protection, and field overcurrent protection will be verified. Review the overvoltage protection settings in BESTCOMS......................................................... ________ Reduce the Generator Overvoltage Level setting to the alarm threshold .................................... ________ Verify that all alarms and annunciation function as programmed ................................................ ________ Reset the generator Overvoltage Level setting to the desired value ........................................... ________ Raise the Generator Undervoltage Level setting to the alarm threshold ..................................... ________ Verify that all alarms and annunciations function as programmed............................................... ________ Reset the Generator Undervoltage Level setting to the desired value......................................... ________ Reduce the Exciter Field Overvoltage Level setting to the alarm threshold................................. ________ Verify that all alarms and annunciations function as programmed............................................... ________ Reduce the Exciter Field Overvoltage Level setting to the desired value .................................... ________ Reduce the Exciter Field Overcurrent Level setting to the alarm threshold ................................. ________ Verify all alarms and annunciations function as programmed...................................................... ________ Reset the Exciter Field Overcurrent Level setting to the desired value ....................................... ________ Parallel Operation, Generator On Line In this test, the generator is connected to the bus and the phase relationship between the current and sensed voltage is checked. If the polarity of the CT is incorrect, a shorting terminal block can be used to reverse the CT polarity. If sensed voltage has the wrong phasing, the generator breaker must be opened, and the wiring corrected. In the following procedures, overexcitation and underexcitation protection is exercised, and var and power factor performance evaluations are conducted at levels that will not stress the machine. For more information about paralleling circuits, download Application Note 126 from the Basler Electric website at www.basler.com. Phase Relationship Test Transfer to FCR mode .................................................................................................................. ________ Parallel the generator with the bus ............................................................................................... ________ Set the machine kilowatt level at approximately 25% of the machine rating at 0 vars................. ________ Check for phase shift at the voltage and current sensing inputs of the DECS-200. The B-phase current should lag the sensed voltage (between E1 and E3) by 90. If the phase relationship is correct, proceed with testing. If the phase relationship is incorrect, troubleshoot the system, resolve the problem, and retest as appropriate before transferring to AVR mode. ............................................................................................................................... ________ Verify that the AVR setpoint is nulled to the FCR setpoint ........................................................... ________ Verify that all null status indicators provide the null indication ..................................................... ________ Verify that AVR Pre-position mode is disabled or that the external pre-position contacts are open........................................................................................................................................ ________ In the following step, be prepared to transfer back to Manual mode if the excitation voltage increases suddenly. Transfer to AVR ............................................................................................................................ ________

6-18

DECS-200 Setup

9360100990 Rev G

OEL Test Disable overexcitation limiting on the System Options tab of the BESTCOMS System Configuration screen .................................................................................................................... _________ Set the three on-line, OEL current limits at 15% above the no-load field current, with a 5 second time delay................................................................................................................... _________ Using a chart recorder, prepare to check the OEL response time. If the response time is too slow, increase the OEL gain (KI and Kg terms) and repeat the test. Increase field excitation until the field current reaches 125% of the no load field current setting _________ Enable OEL .................................................................................................................................. _________ Verify that the response time is within specified limits ................................................................. _________ Enter final OEL values.................................................................................................................. _________ UEL Test Disable underexcitation limiting on the System Options tab of the BESTCOMS System Configuration screen .................................................................................................................... _________ Set the UEL var limit for 5% vars into the generator .................................................................... _________ Adjust the var level into the generator for 15% at 25% load ........................................................ _________ Perform a step response into the UEL limit by enabling underexcitation limiting on the System Options tab of the BESTCOMS System Configuration screen .................................................... _________ Verify stable performance and speed of response....................................................................... _________ If the response time is too slow, increase the UEL gain (KI and Kg terms) and repeat the test.. _________ Verify stable performance of the UEL by testing the machine from 25 through 100% real-power loading, underexcited ................................................................................................. _________ Increase the excitation above the UEL limit ................................................................................. _________ Enter the final UEL values ............................................................................................................ _________ Var Test (If Applicable) Verify that the var setpoint is nulled to the AVR setpoint ............................................................. _________ Verify that all null status indicators provide a null indication ........................................................ _________ Verify that the var Pre-Position mode is disabled or the external pre-position contacts are open_________ In the following step, be prepared to transfer back to AVR if the excitation voltage increases suddenly. Transfer to var mode .................................................................................................................... _________ Set the kilowatt level for 25% output ............................................................................................ _________ Adjust the var level to 30% of rated.............................................................................................. _________ Monitor the exciter field voltage to determine performance while performing the following step. Using BESTCOMS, perform 5% step response stability test....................................................... _________ If necessary, increase the var gain, (KI and Kg terms) to decrease the response time. Repeat the test. ............................................................................................................................ Power Factor Test (If Applicable) Verify that the PF mode setpoint is nulled to the var mode setpoint ............................................ _________ Verify that all null status indicators provide a null indication ........................................................ _________ Verify that PF Pre-Position mode is disabled or external pre-position contacts are open ........... _________ In the following step, be prepared to transfer back to AVR mode if the excitation voltage increases suddenly. Transfer to PF............................................................................................................................... _________ 9360100990 Rev G DECS-200 Setup 6-19

Adjust PF for 0.9, lagging ............................................................................................................. ________ Perform a step response by changing PF setpoint to 0.85, lagging to determine stability .......... ________ If necessary, increase the PF gain (KI and Kg terms) to decrease the response time. Repeat the test.. ........................................................................................................................... ________ Conclusion Of Testing Configure the excitation system with the required parameters. Once satisfactory performance is achieved, save all information to EEPROM.

6-20

DECS-200 Setup

9360100990 Rev G

SECTION 7 MODBUS COMMUNICATION


TABLE OF CONTENTS
SECTION 7 MODBUS COMMUNICATION ......................................................................................... 7-1 INTRODUCTION.................................................................................................................................... 7-1 DECS-200 MODBUS PROTOCOL ........................................................................................................ 7-1 MESSAGE STRUCTURE ...................................................................................................................... 7-1 Device Address Field ......................................................................................................................... 7-1 Function Code Field ........................................................................................................................... 7-2 Data Block Field ................................................................................................................................. 7-2 Error Check Field ............................................................................................................................... 7-2 SERIAL TRANSMISSION DETAILS ...................................................................................................... 7-2 Message Framing and Timing Considerations................................................................................... 7-3 Error Handling and Exception Responses ......................................................................................... 7-3 COMMUNICATIONS HARDWARE REQUIREMENTS.......................................................................... 7-3 DETAILED MESSAGE QUERY AND RESPONSE................................................................................ 7-4 Read Holding Registers ..................................................................................................................... 7-4 Preset Multiple Registers ................................................................................................................... 7-4 Preset Single Register (Write Single Holding Register)..................................................................... 7-5 Error Response .................................................................................................................................. 7-5 Loop Back Diagnostic Test (FC= 8) with Diagnostic Sub-function, Return Query Data .................... 7-6 Loop Back Diagnostic Test with Diagnostic Sub-function, Restart Communications Option............. 7-6 Loop Back Diagnostic Test with Diagnostic Sub-function, Force Slave to Listen Only Mode ........... 7-6 DATA FORMATS ................................................................................................................................... 7-6 Generic Types UI8 and I8 .................................................................................................................. 7-7 Generic Types UI16 and I16 .............................................................................................................. 7-7 Generic Types UI32 and I32 .............................................................................................................. 7-7 Floating Point (R23_32) Data Format ................................................................................................ 7-8 CRC ERROR CHECK ............................................................................................................................ 7-9 DECS-200 MODBUS REGISTER SPACE............................................................................................. 7-9 DECS-200 REGISTER TABLE ............................................................................................................ 7-10 Holding Registers for Information Category C1 ............................................................................... 7-10 Holding Registers for Information Category C2 ............................................................................... 7-12 Holding Registers for Information Category C3 ............................................................................... 7-14 Holding Registers for Information Category C4 ............................................................................... 7-14 Holding Registers for Information Category C5 ............................................................................... 7-15 Holding Registers for Information Category C6 ............................................................................... 7-16 Holding Registers for Information Category C7 ............................................................................... 7-19 Holding Registers for Information Category C8 ............................................................................... 7-19 Holding Registers for Information Category C9 ............................................................................... 7-21 Holding Registers for Information Category C10 ............................................................................. 7-22 Holding Registers for Information Category C11 ............................................................................. 7-23 Holding Registers for Information Category C12 ............................................................................. 7-23 Holding Registers for Information Category C13 ............................................................................. 7-26 Holding Registers for Information Category C14 ............................................................................. 7-27 Holding Registers for Information Category C15 ............................................................................. 7-27

Tables Table 7-1. DECS-200 Communication Settings ........................................................................................ 7-2 Table 7-2. Timing Considerations for 10 Character Bits (8 Data Bits + 1 Start Bit + 1 Stop Bit) .............. 7-3 Table 7-3. Supported Exception Response Codes ................................................................................... 7-3 Table 7-4. Generic Data Types and Description ....................................................................................... 7-7 Table 7-5. HR 44005 Contents.................................................................................................................. 7-7 Table 7-6. HR 47003 Mapping .................................................................................................................. 7-7 9360100990 Rev G DECS-200 ModbusTM Communication i

Table 7-7. Typical Mapping ....................................................................................................................... 7-8 Table 7-8. Floating Point Format ............................................................................................................... 7-8 Table 7-9. Number 123 In Floating Point Format ...................................................................................... 7-8 Table 7-10. Information Category Summary ............................................................................................. 7-9 Table 7-11. Information Category C1 (Product Information) ................................................................... 7-10 Table 7-12. Information Category C2 (Metering)..................................................................................... 7-12 Table 7-13. Information Category C3 (Reporting) ................................................................................... 7-14 Table 7-14. Information Category C4 (Control System Configuration Parameters)................................ 7-14 Table 7-15. Information Category C5 (Operating Mode Parameters) ..................................................... 7-15 Table 7-16. Information Category C6 (Setpoint Parameters).................................................................. 7-17 Table 7-17. Information Category C7 (Start-up Parameters) .................................................................. 7-19 Table 7-18. Information Category C8 (Limiter Parameters) ................................................................... 7-20 Table 7-19. Information Category C9 (Control Loop Gain Parameters).................................................. 7-21 Table 7-20. Information Category C10 (Protective Functions Parameters) ............................................ 7-22 Table 7-21. Information Category C11 (Calibration related Parameters)................................................ 7-23 Table 7-22. Information Category C12 (Relay Parameters).................................................................... 7-23 Table 7-23. Information Category C13 (Communications Parameters) .................................................. 7-26 Table 7-24. Information Category C14 (Front Panel Metering Configuration Parameters)..................... 7-27 Table 7-25. Information Category C15 (Control System Configuration Parameters Group II)................ 7-27

ii

DECS-200 ModbusTM Communication

9360100990 Rev G

SECTION 7 MODBUS COMMUNICATION


INTRODUCTION
This section describes the Modbus communication protocol employed by the DECS-200 and how to exchange information with the DECS-200 over a Modbus network. The DECS-200 communicates by emulating a subset of the ModiconTM 984 Programmable Controller.

DECS-200 MODBUS PROTOCOL


Modbus communications use a master-slave technique in which only the master can initiate a transaction called a query. When appropriate, a slave (DECS-200 ) responds to the query. When a Modbus master communicates with a slave, information is provided or requested by the master. Information residing in the DECS-200 is grouped characteristically in categories. The following information categories are maintained by the DECS-200: C1 - Product Information Registers C2 - Metering Registers C3 - Reporting Registers C4 - Control System Configuration Parameters Registers Group 1 C5 - Operating Mode Parameter Registers C6 - Setpoints Parameter Registers C7 - Startup Parameter Registers C8 - Limiter Parameter Registers C9 - Gains Registers C10 - Protective Functions Parameter Registers C11 - Calibration Parameter Registers C12 - Relay Parameter Registers C13 - Communications Parameter Registers C14 - Front Panel Metering Configuration Registers C15 - Control System Configuration Parameters Registers Group 2 All supported data can be read or written as specified in the register table. Abbreviations are used in the register table to indicate the register access type. Register access types are read/write (RW) and read only (R -). All categories except Product Information (C1), Metering (C2), Reporting (C3) and Calibration (C11) can generally be written via a Modbus message as well as read. Categories C1 and C2 are strictly read-only. (Categories C3 and C11 are currently not supported and therefore cannot be read or written.) When a slave receives a query, the slave responds by either supplying the requested data to the master or performing the requested action. A slave device never initiates communications on the Modbus network and will always generate a response to the query unless certain error conditions occur. The DECS-200 is designed to communicate on the Modbus network only as a slave device. A master can only query slaves individually. If a query requests actions unable to be performed by the slave, the slave response message contains an exception response code defining the error detected.

MESSAGE STRUCTURE
Master initiated queries and DECS-200 (slave) responses share the same message structure. Each message is comprised of four message fields. They are: Device Address (1 byte) Function Code (1 byte) Data Block (n bytes) Error Check field (2 bytes)

Device Address Field The device address field contains the unique Modbus address of the slave being queried. The addressed slave repeats the address in the device address field of the response message. This field is one byte.

DECS-200

Modbus Communication

7-1

Modbus protocol limits a device address from 1 to 247. The address is user-selectable at installation, and can be altered during real-time operation. Function Code Field The function code field in the query message defines the action to be taken by the addressed slave. This field is echoed in the response message and is altered by setting the most significant bit (MSB) of the field to 1 if the response is an error response. This field is 1 byte. The DECS-200 maps all registers into the ModiconTM 984 holding register address space (4XXXX) and supports the following function codes: - READ OUTPUT REGISTERS (function code 3), - PRESET SINGLE REGISTER WRITE (function code 6) - PRESET MULTIPLE REGISTERS (function code 16), and - LOOPBACK DIAGNOSTIC TEST (function code 8) with diagnostic sub-functions: - Return Query Data (diagnostic code 0), - Restart Comm. option (diagnostic code 1), and - Force Slave To Listen Only Mode (LOM, diagnostic code 4). DECS-200 Modbus performs all of the above functions when a Modbus message has its unique address which is numbered from 1 to 247. DECS-200 also recognizes a broadcast (group) address of 0. Only functions 16 and 8 are recognized as valid for broadcast. The DECS-200 does not send a response message for a broadcast query. In listen-only mode (LOM), received data is monitored (but no responses are transmitted). The only query that will be recognized and processed while in LOM is a maintenance restart command (function code 8, diagnostic code 1). Data Block Field The query data block contains additional information needed by the slave to perform the requested function. The response data block contains data collected by the slave for the queried function. An error response will substitute an exception response code for the data block. The length of this field varies with each query. See the paragraphs on Register Definitions in this manual for interpretation of register data. Error Check Field The error check field provides a method for the slave to validate the integrity of the query message contents and allows the master to confirm there validity. This field is 2 bytes.

SERIAL TRANSMISSION DETAILS


A standard Modbus network offers two transmission modes for communication: ASCII or Remote Terminal Unit (RTU). The DECS-200 supports only the RTU mode via rear RS-485 serial interface. Communication settings for the DECS-200 Rear RS-485 port are listed in Table 7-1. Table 7-1. DECS-200 Communication Settings Setting Baud Rate Data Size in Bits Parity Stop Bits Modbus Slave Address Modbus Response Delay Time in ms Programmable Y(Yes) / N(No) Y N Y Y Y Y Default Value 9600 8 None 2 247 10 ms Value Range 1200/2400/4800/9600/19200 N/A N=None, O=Odd, E=Even 1 or 2 0 for broadcast, 1 to 247 for slave From 0 to 200 ms in increments of 10 ms

Communication settings are user-selectable and can be set at installation and altered during real-time operation.

7-2

Modbus Communication

DECS-200

Message Framing and Timing Considerations When receiving a message, the DECS-200 requires an inter-byte latency of 3.5 character times before considering the message complete. Once a valid query is received, the DECS-200 waits a specified amount of time as specified in the Modbus Response Delay Time Register (48108) before responding. This Register contains a value from 0 to 200 milliseconds. The default value is 10 milliseconds. The user may set the remote delay time parameter to 0 to minimize response latency. Table 7-2 provides the response message transmission time (in milliseconds) and 3.5 character times (in milliseconds) for the maximum response message length (225 characters), response to a read query for 125 points and various baud rates. Table 7-2. Timing Considerations For 10 Character Bits (8 Data Bits + 1 Start Bit + 1 Stop Bit) Max. Read Register Response Message 1 Character 3.5 Characters (255 characters) Transmission Time (ms) Baud Rate Time (ms) Time (ms) 1,200 2,400 4,800 9,600 19,200 8.33 4.17 2.083 1.0417 0.52083 29.17 14.58 7.292 3.645 1.823 2,124.15 1,063.35 531.165 265.6335 132.812

Error Handling and Exception Responses Any query received that contains a nonexistent device address, a framing error, or CRC error is ignored. No response is transmitted. Queries addressed to a DECS-200 with an unsupported function code, unsupported register references or illegal values in the data block result in an error response message with an exception response code. Each error response message consists of a slave (DECS-200) address, function code with the high order bit set, error code and error check (CRC) field. The exception response error codes supported by the DECS-200 are provided in Table 7-3. Table 7-3. Supported Exception Response Codes Code 01 Name Illegal Function Meaning The query Function/Sub-function Code is unsupported; query read of more than 125 registers; query preset multiple registers of more than 100 registers A register referenced in the data block does not support queried read/write; For Function Codes 3 and 16 additionally: 1. Starting Register address is mapped to DECS-200 Modbus address space but is not referenced to the highest order 16 bits of the assigned application data (see explanation in 2.7 Data Formats), and 2. The number of registers is too small to hold entire value of all data (variables) assigned to those registers (see explanation in 2.7 Data Formats). 03 Illegal Data Value A preset register data block contains an incorrect number of bytes or one or more data values out of range.

02

Illegal Data Address

COMMUNICATIONS HARDWARE REQUIREMENTS


The DECS-200 RS-485 physical interface consists of three positions of a terminal strip with locations for Send/Receive A (A), Send/Receive B (B) and Signal Ground (C).

DECS-200

Modbus Communication

7-3

DETAILED MESSAGE QUERY AND RESPONSE


A detailed description of DECS-200 supported message queries and responses are provided in the following paragraphs. Read Holding Registers Query This query message requests a register or block of registers to be read. The data block contains the starting register address and the quantity of registers to be read. A register address of N will read holding register N+1. Device Address Function Code = 03 Starting Address High Starting Address Low No. of Registers High No. of Registers Low CRC Low CRC High

The number of registers cannot exceed 125 without causing an error response with the exception code for an illegal function. Response The response message contains the data queried. The data block contains the block length in bytes followed by the data for each requested register. For each requested register, there is one Data Hi and one Data Lo. Attempting to read an unused register or a register that does not support a read results in an error response with the exception code for an illegal data address. If the query is a broadcast (device address = 0), no response message is returned. Maximum response message length obtained for query of 125 registers is 5 + (125 x 2) = 255 bytes. Device Function Byte Address Code = 03 Count 250 max. Data High First queried register High Data Low First queried register Low For each requested register Data High and data Low Data High Last queried register High Data Low Last queried register Low CRC Low CRC High

Preset Multiple Registers A preset multiple registers query could address multiple registers in one slave or multiple slaves. If the query is broadcast (device address = 0), no response is required. Query A Preset Multiple Registers query message requests a register or block of registers to be written. The data block contains the starting address and the quantity of registers to be written, followed by the Data Block byte count and data. The DECS-200 will perform the write when the device address is the same as the DECS-200 remote address or when the device address is 0. A device address is 0 for a broadcast query. A register address of N will write Holding Register N+1. All Modbus Generic Data Formats can be loaded by this function (see Data Formats). No data will be written if any of the following exceptions occur: Queries to write to Read Only or unsupported registers result in an error response with an exception code of Illegal Data Address. Queries attempting to write more than 100 registers cause an error response with an exception code of Illegal Function. An incorrect Byte Count will result in an error response with an exception code of Illegal Function. A query to write an illegal value (out of range) to a register results in an error response with an exception code of Illegal Data Value. Query Starting Register address is mapped to DECS-200 Modbus address space but is not referenced to the lower order 16 bits of the assigned application data. (See explanation in Data Formats.) Modbus Communication DECS-200

7-4

The number of query registers is too small to hold entire value of all data (variables) assigned to those registers. (See explanation in Data Formats.)

Query message format is: Device Address Function Code = 10 (hex) Starting Address High Starting Address Low Number of Registers High (total number of registers to be loaded) Number of Registers Low Byte Count (total number of registers to be loaded times 2) Data High Data Low ... Data High Data Low CRC Error Check (Lo, Hi) Note: The maximum length of a Preset Multiple Registers Query is 9 + (100 x 2) = 209 bytes. Response The response message echoes the starting address and the number of registers. There is no response message when the query is a broadcast (device address of 0). Device Address Function Code = 10 (hex) Starting Address High Starting Address Low Number of Registers High Number of Registers Low CRC Low CRC High

Preset Single Register (Write Single Holding Register) A Preset Single Register query message requests a single register to be written. The DECS-200 will perform the write when the device address is the same as the DECS-200s remote address. Query Device Address Function Code = 06 (hex) Address Hi Address Lo Data Hi Data Lo CRC Hi error check CRC Lo error check The response message echoes the Query message after the register has been altered. Error Response Data will cease to be written if any of the following exceptions occur. Queries to write to Read Only registers result in an error response with Exception Code of Illegal Data Address. A query to write an out of range value to a register results in an error response with Exception Code of Illegal Data Value.

There are several instances of registers that are grouped together to collectively represent a single numerical DECS-200 data value (i.e., floating point data and 32-bit integer data). A query to write a subset of such a register group will result in an error response with Exception Code Illegal Data Address.

DECS-200

Modbus Communication

7-5

NOTE Variables changed by this function will not be directly saved to nonvolatile memory (EEPROM). If specific categories (one or more) of data have to be saved to EEPROM, then Holding Register 48161 (Data Id=13001, variable SaveCommand) has to be preset after a category has been changed. The exceptions to this rule are only those Holding Registers dealing with communication port RS-485. They will be changed and immediately saved to EEPROM with the function FC16.

Loop Back Diagnostic Test (FC= 8) with Diagnostic Sub-function, Return Query Data This query contains data to be returned (looped back) in the response. The response and query messages should be identical. If the query is a broadcast (device address = 0), no response message is returned. Device Address Function Code = 08 (hex) Sub-function High 00 Sub-function Low 00 Data High XX (dont care) Data Low XX (dont care) CRC Low CRC High

Loop Back Diagnostic Test with Diagnostic Sub-function, Restart Communications Option This query causes the remote communications function of the DECS-200 to restart, terminating an active listen only mode of operation. No effect is made upon primary relay operations. Only the remote communications function is affected. If the query is a broadcast (device address of 0), no response message is returned. If the DECS-200 receives this query while in the listen only mode (LOM), no response message is generated. Otherwise, a response message identical to the query message is transmitted prior to the communications restart.

Device Address

Function Code = 08 (hex)

Sub-function High 00

Sub-function Low 01

Data High XX (dont care)

Data Low XX (dont care)

CRC Low

CRC High

Loop Back Diagnostic Test with Diagnostic Sub-function, Force Slave to Listen Only Mode This query forces the addressed DECS-200 to the listen only mode for Modbus communications, isolating it from other devices on the network. While in Listen Only Mode (LOM), received data is monitored (but no responses are transmitted). The only query that will be recognized and processed while in LOM is a maintenance restart command (function Code 8, diagnostic code 1). When the DECS-200 receives the restart communications query, the Listen Only mode is terminated. Device Address Function Code = 08 (hex) Sub-function High 00 Sub-function Low 04 Data High XX (dont care) Data Low XX (dont care) CRC Low CRC High

DATA FORMATS
DECS-200 data does not need to be converted into any special format for transmission over a Modbus network. Modbus Registers hold original DECS-200 data of the generic (built-in) data types listed in Table 7-4.

7-6

Modbus Communication

DECS-200

Table 7-4. Generic Data Types and Description Generi c Data Types UI8 UI6 UI32 I8 I16 I32 R32_23 Data Size in bytes 1 2 4 1 2 4 4 Total number of Modbus Registers to hold data 1 1 2 1 1 2 2

Corresponding built-in data type (Storage Format) UCHAR: unsigned character UINT16: unsigned short integer UINT32: unsigned long integer CHAR: signed character INT16: signed short integer INT32: signed long integer FLOAT: floating point number

Data Range 0 to 255 0 to 65,535 0 to 4,294,967,295 -128 to 127 -32,768 to 32,767 -2,147,483,648 to 2,147,483,647 From approximately 8.43 x 10 to 3.38 x 1038
-37

It should be noted that an ASCII string is not a DECS-200 generic data type. An ASCII string will be considered as a sequence of (string length + 1) data of I8 type, and for its transmission via a Modbus network (string length + 1) holding registers are needed. DECS-200 data is copied to assigned Holding Register(s) [HR] by the rules presented in the following paragraphs.

Generic Types UI8 and I8 Data of type UI8 or I8 is copied to one holding register (HR). The high (first) HR byte always contains 0, and second (low) HR byte contains the data. Example: Assume that the value of UI8 type data is 0x56, and that the data is mapped to HR 44005. The content of HR 44005 will be as listed in Table 7-5. Table 7-5. HR 44005 Contents HR 44004 Low Byte ... Generic Types UI16 and I16 Data of type UINT16 or INT16 is saved in 1 one holding register. The high data byte is copied to the high HR byte and the low data byte to the low HR byte. Example: Assume that the DECS-200 UINT16 or INT16 type data value of 0xF067 is mapped to HR 47003. Data is copied to HR 47003 as shown in Table 7-6. Table 7-6. HR 47003 Mapping HR 47002 Low Byte ... Generic Types UI32 and I32 Data of type UI32 or I32 is 4 bytes long. The Modbus 4-byte long data generic types use two consecutive registers to represent a data value. The lower numbered holding register contains the low order 16 bits, Low Order word [LO w] and the higher numbered holding register contains the higher order 16 bits, Higher Order word [HO w]. DECS-200 Modbus Communication 7-7 HR 47003 High Byte 0xF0 HR 47003 Low Byte 0x67 HR 47004 High Byte ... HR 44005 High Byte 0x00 HR 44005 Low Byte 0x56 HR 44006 High Byte ...

Example: The UI32 data type, value is 0xE0234567 and is mapped to two Holding registers (such as 45003 and 45004) as shown in Table 7-7. Table 7-7. Typical Mapping Register Hexadecimal Binary 45003 4567 0100 0101 0110 0111 45004 E023 1110 0000 0010 0011

HR 45002 LO byte ...

HR 45003 HO byte 45

HR 45003 LO byte 67

HR 45004 HO byte E0

HR 45004 LO byte 23

HR 45005 HO byte ...

Floating Point (R23_32) Data Format The specific floating-point format matches the floating-point format used for Modicon 984-8 family of programmable controllers. Its representation in bit format is: S EEE EEEE E MMMM byte 3 byte 2

MMM

MMMM MMMM byte 1

MMMM MMMM Byte 0

where the S is the sign bit for the floating point value: 1 if negative and 0 if positive; The E field is the twos complement exponent biased by 127 decimal; The M field is the 23-bit normalized mantissa. The most-significant bit of the mantissa is always assumed to be 1 and is not explicitly stored yielding an effective precision of 24 bits. The value of the floating-point number is obtained by multiplying the binary mantissa times two raised to the power of the unbiased exponent. The assumed bit of the binary mantissa has the value of 1.0 with the remaining 23 bits providing a fractional value. Table 7-8 shows the floating-point format. Sign 1 bit Table 7-8. Floating Point Format 2's Complement Of (Exponent + 127) 8 bits Mantissa 23 bits

The floating point format allows a maximum value of 3.38 x 1038. Note that bytes 0 and 1 of the floating-point value are stored in the lower numbered register and bytes 2 and 3 are contained in the higher numbered register. For example: Number 123 in floating point format is mapped to two Holding registers (such as 45005 and 45006) as shown in Table 7-9. Table 7-9. Number 123 in Floating Point Format Register Hexadecimal Binary 45005 0000 0000 0000 0000 0000 45006 42F6 0100 0010 1111 0110

CAUTION For DECS-200 Modbus, two consecutive holding registers which are mapped to any of the 4-byte generic data types, are considered to be linked together as one atomic, indivisible unit of information which can be read or written by Modbus message only as one entity (that is, one cannot be read or written without the other). 7-8 Modbus Communication DECS-200

CRC ERROR CHECK


This field contains a two-byte CRC value for transmission error detection. The master first calculates the CRC and appends it to the query message. The DECS-200 recalculates the CRC value for the received query and performs a comparison to the query CRC value to determine if a transmission error has occurred. If so, no response message is generated. If no transmission error has occurred, the slave calculates a new CRC value for the response message and appends it to the message for transmission. The CRC calculation is performed using all bytes of the device address, function code and data block fields. A 16-bit CRC register is initialized to all 1's. Then, each eight-bit byte of the message is used in the following algorithm. First, exclusive-OR the message byte with the low-order byte of the CRC-register. The result, stored in the CRC-register, will then be right-shifted eight times. The CRC-register MSB is zero-filled with each shift. After each shift, the CRC-register LSB is examined. If the LSB a 1, the CRC-register is then exclusive-ORed with the fixed polynomial value A001 (hex) prior to the next shift. Once all bytes of the message have undergone the above algorithm, the CRC-register will contain the message CRC value to be placed in the error check field.

DECS-200 MODBUS REGISTER SPACE


Modbus Address space from 40000 to 49999 refers to Functions Code 3, 6 and 16. The DECS-200 uses address space from 47001 to 48250 (1250 registers). This address space is divided into 14 areas referred to as information categories. Table 7-10 provides a statistical summary for each information category. Table 7-10. Information Category Summary Total # of Holding Number Reserved Register Information Holding Address Of Used Registers Category Registers Space Product Information Metering Reporting (Status) Control System Configuration Group 1 Operating Modes Setpoints Start-up Limiters Control Loop Gains Protective Functions Calibration 250 125 125 47001 to 47250 47251 to 47375 47376 to 47500 47501 to 47560 47561 to 47620 47621 to 47740 47741 to 47800 47801 to 47860 47861 to 47920 47921 to 47980 47981 to 48040 63 55 None Data Types Mapped To Registers (Total # Of Variables) UCHAR: 63 FLOAT: 24 UINT16: 7 None (for future use) FLOAT: 26 UINT16: 7 UINT16: 23 FLOAT: 45 UINT16: 4 FLOAT: 8 FLOAT: 19 FLOAT: 15 FLOAT: 15 UINT16: 7 None (for future use)

Information Category ID C1 C2 C3

Access Right R R R 58 RW 1R 16 RW 7R 48 R 46 RW RW RW RW RW

C4 C5 C6 C7 C8 C9 C10

60 60 120 60 60 60 60

59 23 94 16 38 30 37 None (for future use)

C11

60

RW

DECS-200

Modbus Communication

7-9

Information Category ID C12 C13 C14

Information Category Relays General System FP Metering Configuration Control System Configuration Group II

Total # of Reserved Holding Registers 120 60 30 50

Holding Register Address Space 48041 to 48160 48161 to 48220 48221 to 48250 48501 to 48550

Number Of Used Registers 83 8 3 10

Access Right RW 2R 6 RW 3 RW RW

Data Types Mapped To Registers (Total # Of Variables) UINT16: 83 UINT16: 6 UCHAR: 2 UINT16: 3 FLOAT: 4

C15

DECS-200 REGISTER TABLE


Each data to be transmitted via Modbus network is identified by its holding register(s). The following tables provide the complete list of holding register assignments and descriptions for the DECS-200. There is a separate table for each information category. Holding Registers for Information Category C1 Table 7-11. Information Category C1 (Product Information) Registers 47001 47002 47003 47004 47005 47006 47007 47008 47009 47010 47011 47012 47013 47014 47015 47016 7-10 Data Description 1st character of the ASCII string of model information 2nd character of the ASCII string of model information 3rd character of the ASCII string of model information 4th character of the ASCII string of model information 5th character of the ASCII string of model information 6th character of the ASCII string of model information 7th character of the ASCII string of model information 8th character of the ASCII string of model information Last character of the ASCII string of model information 1st character of the ASCII string of application program version number 2nd character of the ASCII string of application program version number 3rd character of the ASCII string of application program version number 4th character of the ASCII string of application program version number 5th character of the ASCII string of application program version number 6th character of the ASCII string of application program version number 7th character of the ASCII string of application program version Modbus Communication Access RRRRRRRRRRRRRRRRData Format UI8 UI8 UI8 UI8 UI8 UI8 UI8 UI8 UI8 UI8 UI8 UI8 UI8 UI8 UI8 UI8 DECS-200

Table 7-11. Information Category C1 (Product Information) Registers number 47017 47018 47019 47020 47021 47022 47023 47024 47025 47026 47027 47028 47029 47030 47031 47032 47033 47034 47035 47036 47037 47038 47039 47040 47041 47042 47043 47044 47045 47046 47047 47048 Last character of the ASCII string of application program version number 1st character of the ASCII string of date of the application program 2nd character of the ASCII string of date of the application program 3rd character of the ASCII string of date of the application program 4th character of the ASCII string of date of the application program 5th character of the ASCII string of date of the application program 6th character of the ASCII string of date of the application program 7th character of the ASCII string of date of the application program 8th character of the ASCII string of date of the application program Last character of the ASCII string of date of the application program 1st character of the ASCII string of DSP program version number 2nd character of the ASCII string of DSP program version number 3rd character of the ASCII string of DSP program version number 4th character of the ASCII string of DSP program version number 5th character of the ASCII string of DSP program version number 6th character of the ASCII string of DSP program version number 7th character of the ASCII string of DSP program version number Last character of the ASCII string of DSP program version number 1st character of the ASCII string of date of the DSP program 2nd character of the ASCII string of date of the DSP program 3rd character of the ASCII string of date of the DSP program 4th character of the ASCII string of date of the DSP program 5th character of the ASCII string of date of the DSP program 6th character of the ASCII string of date of the DSP program 7th character of the ASCII string of date of the DSP program 8th character of the ASCII string of date of the DSP program Last character of the ASCII string of date of the DSP program 1st character of the ASCII string of Boot program version number 2nd character of the ASCII string of Boot program version number 3rd character of the ASCII string of Boot program version number 4th character of the ASCII string of Boot Program version number 5th character of the ASCII string of Boot program version number RRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRUI8 UI8 UI8 UI8 UI8 UI8 UI8 UI8 UI8 UI8 UI8 UI8 UI8 UI8 UI8 UI8 UI8 UI8 UI8 UI8 UI8 UI8 UI8 UI8 UI8 UI8 UI8 UI8 UI8 UI8 UI8 UI8 Data Description Access Data Format

DECS-200

Modbus Communication

7-11

Table 7-11. Information Category C1 (Product Information) Registers 47049 47050 47051 47052 47053 47054 47055 47056 47057 47058 47059 47060 47061 47062 47063 47064 to 47250 Data Description 6th character of the ASCII string of Boot program version number 7th character of the ASCII string of Boot program version number Last character of the ASCII string of Boot program version number 1st character of the ASCII string of date of the Boot program 2nd character of the ASCII string of date of the Boot program 3rd character of the ASCII string of date of the Boot program 4th character of the ASCII string of date of the Boot program 5th character of the ASCII string of date of the Boot program 6th character of the ASCII string of date of the Boot program 7th character of the ASCII string of date of the Boot program 8th character of the ASCII string of date of the Boot program Last character of the ASCII string of date of the Boot program 1st character of the ASCII string of style number information 2nd character of the ASCII string of style number information Last character of the ASCII string of style number information Reserved for future C1 data Access RRRRRRRRRRRRRRRNot supported Data Format UI8 UI8 UI8 UI8 UI8 UI8 UI8 UI8 UI8 UI8 UI8 UI8 UI8 UI8 UI8 Not defined

Holding Registers for Information Category C2 Table 7-12. Information Category C2 (Metering) Registers Data Description Access RRRRRRRRRRRRRModbus Communication Data Format R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 DECS-200

47251-52 Phase A to B rms generator voltage 47253-54 Phase B to C rms generator voltage 47255-56 Phase C to A rms generator voltage 47257-58 Average of the 3 rms line-to-line voltages 47259-60 Phase B generator current in amps 47261-62 Generator apparent power in kVA 47263-64 Generator real power in kW 47265-66 Generator reactive power in kvar 47267-68 Power factor 47269-70 Generator frequency in hertz 47271-72 Bus frequency in Hz 47273-74 RMS bus voltage in volts 47275-76 Field voltage in volts 7-12

Table 7-12. Information Category C2 (Metering) Registers 47277-78 Field current in amps 47279-80 Var/PF controller output in volts 47281-82 Phase angle between phase B voltage and current in degrees 47283-84 Auxiliary input in volts (PSS input) 47285-86 Current input for load compensation 47287-88 Null balance (tracking error) in percent 47289-90 Error signal to autotracking loop 47291-92 Active controller output 47293 47294 47295 PF state: 0 = leading / 1 = lagging Generator state: 0 = generating / 1 = motoring Status of the Front panel LEDs (bit flags, where 0=off, 1=on for all LEDs except Null Balance and Internal Tracking which are reversed): b0=Null Balance, b1=Tracking, b2=Pre-position, b3=Upper Limit, b4=Lower Limit, b5=Edit, b6-b15=unassigned Voltage matching status: 0=off / 1=on Protection status bit flags (0=clear, 1=condition present): b0=field overvoltage, b1=field overcurrent, b2=gen. Undervoltage, b3=gen. overvoltage, b4=underfrequency, b5=in OEL, b6=in UEL, b7=in FCR mode, b8=loss of sensing voltage, b9=setpoint at lower limit, b10=setpoint at upper limit, b11=gen. failed to build up, b12= gen. below 10Hz, b13=unassigned, b14=exciter diode open, b15=exciter diode shorted. 47298-99 Reserved for future C2 data 47300-01 The active operating setpoint expressed as a percent of its present adjustment range. 47302 47303 The state of some contact inputs: b0 = 52JK, b1 = 52LM, b2 = Automatic transfer, b3 = External Tracking Enable Annunciation status bit flags (0=clear, 1=annunciation present): b0=field overvoltage, b1=field overcurrent, b2=gen. undervoltage, b3=gen. overvoltage, b4=underfrequency, b5=in OEL, b6=in UEL, b7=in FCR mode, b8=loss of sensing voltage, b9=setpoint at lower limit, b10=setpoint at upper limit, b11=gen. failed to build up, b12= gen. below 10Hz, b13=unassigned, b14=exciter diode open, b15=exciter diode shorted.. 47304-05 47306 47307 Reserved Protection status bit flags (0 = clear, 1 = condition present) b0 = loss of field, b1 = in SCL, b2 b15 are unassigned Annunciation status bit flags (0 = clear, 1 = condition present) b0 = loss of field, b1 = in SCL, b2 b15 are unassigned 47308 to 47375 DECS-200 Modbus Communication 7-13 Reserved for C2 data RRRR32_23 UI16 UI16 RRRRR32_23 R32_23 UI16 UI16 Data Description Access RRRRRRRRRRRData Format R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 UI16 UI16 UI16

47296 47297

RR-

UI16 UI16

Holding Registers for Information Category C3 Table 7-13. Information Category C3 (Reporting) Registers 47376 to 47500 Data Description Reserved for future C3 data Access Not supported Data Format Not defined

Holding Registers for Information Category C4 Table 7-14. Information Category C4 (Control System Configuration Parameters) Registers 47501-02 47503-04 47505-06 47507-08 47509-10 47511-12 47513-14 47515-16 47517-18 47519-20 47521-22 47523-24 47525-26 47527-28 47529-30 47531-32 47533-34 47535-36 47537-38 Data Description Generator rated frequency, selectable to be 50 or 60 Hz Generator PT primary voltage rating, adjustable from 1 to 30,000 Vac in 1 volt increments Generator PT secondary voltage rating, adjustable from 1 to 240 Vac in 1 volt increments Generator CT primary current rating, adjustable from 1 to 60,000 Aac in 1 amp increments Generator CT secondary current rating, selectable to be 1 or 5 Aac Field current rating, adjustable from 1 to 18 Adc, in 0.1 amp increments Field voltage connections to isolation box, selectable to be 32V, 63V, 125V, 250V or 375V Bus sensing PT primary rating, adjustable from 1 to 500,000 Vac in 1 volt increments Bus sensing PT secondary rating, adjustable from 1 to 240 Vac in 1 volt increments Reserved Reserved Generator rated voltage, adjustable from 85 to 30,000 Vac in 1 volt increments Generator rated output current, adjustable from 10 to 60,000 Aac in 0.1 amp increments Generator rated field voltage, adjustable from 1 to 400 Vdc in 1 volt increments Generator rated field current, adjustable from 0.1 to 9999.0 Adc in 0.1 amp increments Nominal bus voltage, adjustable from 85 to 500,000 Vac in 1 volt increments Auxiliary input gain for AVR mode, adjustable from 0 to 99 in 0.01 increments Internal tracking time delay, adjustable from 0 to 8 seconds in 0.1second increments Internal tracking traverse rate, adjustable from 1 to 80 seconds in 0.1 second increments Access RW RW RW RW RW RW RW RW RW RW RW RW RW RW RW RW RW RW RW Data Format R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23

7-14

Modbus Communication

DECS-200

Table 7-14. Information Category C4 (Control System Configuration Parameters) Registers 47539-40 47541-42 47543 47544 47545 47546 47547 47548 47549-50 47551-52 47553 47554-55 47556-57 47558-59 47560 Data Description Null balance level, adjustable from 0 to 9,999 in 0.01 increments Gain for cross current compensation, adjustable from 0 to 30 in 0.01 increments Voltage sensing configuration: 0 = 1 phase (A-C) / 1 = 3 phase Auxiliary input summing mode: 0 = Inner Loop for AVR and FCR modes / 1 = Outer Loop for var and PF modes Control signal output range: 0 or 1 = 0+10V / 2 = -10+10V / 3 = 4-20 mA Reserved Auxiliary input selection: 0 = voltage input / 1 = current input PSS input mode reserved for future C4 data External tracking time delay, adjustable from 0 to 8 seconds in 0.1 second increments External tracking traverse rate, adjustable from 1 to 80 seconds in 0.1-second increments Voltage sensing hardware gain control signal: 0 = gen. PT secondary <= 160 Vac / 1 = gen. PT secondary > 160 Vac Auxiliary input gain for FCR mode, adjustable from -99 to 99 in 0.01 increments Auxiliary input gain for var mode, adjustable from -99 to 99 in 0.01 increments Auxiliary input gain for PF mode, adjustable from -99 to 99 in 0.01 increments Reserved Access RW RW RW RW RW RW RW RW RW RW RRW RW RW RW Data Format R32_23 R32_23 UI16 UI16 UI16 UI16 UI16 UI16 R32_23 R32_23 UI16 R32_23 R32_23 R32_23 UI16

Holding Registers for Information Category C5 Table 7-15. Information Category C5 (Operating Mode Parameters) Registers 47561 Data Description Virtual toggle switch for Start or Stop: 0 = no change / 1 = change state. Holding register 47572 contains unit mode status. Note: Read value of register 47561 is always 0. 47562 Virtual toggle switch for changing control mode from comm. port between AVR and FCR: 0 = no change / 1 = change state. Holding register 47573 contains Control mode status. Note: Read value of register 47562 is always 0. 47563 Switch for changing operating mode via comm. port, to one of three modes, 0=OFF / 1=PF / 2=var. Holding register 47571 contains Operating mode status. Note: Read value of register 47563 is always 4. Internal tracking status from comm. port: 0 = Off / 1 = On Preposition enable status from comm. port: 0 = Off / 1 = On Modbus Communication RW UI16 RW UI16 Access RW Data Format UI16

47564 47565 DECS-200

RW RW

UI16 UI16 7-15

Table 7-15. Information Category C5 (Operating Mode Parameters) Registers 47566 47567 47568 47569 47570 47571 47572 47573 47574 47575 47576 47577 47578 Data Description Raise input enable status from comm. port: 0 = Off / 1 = On Lower input enable status from comm. port: 0 = Off / 1 = On External tracking enable status from comm. port: 0 = Off / 1 = On Limiter Mode options: 0 = both off / 1 = UEL on / 2 = OEL on / 3 = both on / 4 = SCL / 5 = SCL/UEL / 6 = SCL/OEL / 7 = OEL/UEL/SCL Voltage matching mode: 0 = Off / 1 = On Operating mode: 0 = Off / 1 = PF Control / 2 = var Control Unit mode status: 0 = Stop / 1 = Start Control mode status: 1 = FCR / 2 = AVR Internal (mode-to-mode) tracking status: 0 = Off / 1 = On Reserved for future C5 data Secondary unit enable status: 0 = primary unit / 1 = secondary unit Load compensation mode status: 0 = Off / 1 = Droop / 2 = Line Drop Load compensation mode selection via comm. ports: 0 = Off/1 = Droop / 2 = Line Drop. Holding register 47577 contains Load compensation mode status. Note: Read value of register 47578 is always 0. Input for resetting front panel annunciations and latched relay annunciations: 0 = no change / 1 = reset. Note: Read value of register 47579 is always 0. Loss-of-sensing detection enable: 0 = disable / 1 = enable Loss of sensing triggered transfer-to-FCR-mode enable. Under frequency or volts per hertz mode enable. External Tracking enabled: 0 = disabled /1 = enabled Virtual toggle switch for OEL style: 0 = no change, 1 = change Read back: 0 = summing point, 1 = takeover 47585 47586 47587 to 47620 OEL option: 0 = Option 1, 1 = Option 2, 3 = Option 3 PF/var option status: 0 = Off, 1 = PF, 2 = var Reserved for future C5 data RW RNot supported UI16 UI16 Not defined Access RW RW RW RW RW RRRRRRRRW Data Format UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16

47579

RW

UI16

47580 47581 47582 47583 47584

RW RW RW RW RW

UI16 UI16 UI16 UI16 UI16

Holding Registers for Information Category C6 Table 7-16. Information Category C6 (Setpoint Parameters) Registers 47621-22 47623-24 Data Description FCR (field current regulator) mode setpoint; adjustment range is determined by registers (47699-700) and (47707-08) AVR (automatic voltage regulator) mode setpoint; adjustment range is determined by registers (47701-02) and (47709-10) Access RW RW Data Format R32_23 R32_23

7-16

Modbus Communication

DECS-200

Table 7-16. Information Category C6 (Setpoint Parameters) Registers 47625-26 47627-28 47629-30 47631-32 47633-34 47635-36 47637-38 47639-40 47641-42 47643-44 47645-46 47647-48 47649-50 47651-52 Data Description Var mode setpoint (in kvar); adjustment range is determined by registers (47703-04) and (47711-12) PF mode setpoint; adjustment range is determined by registers (47705-06) and (47713-14) Droop setting in percent (of rated generator voltage), adjustable from -30 to 30% in 0.1% increments FCR mode traverse rate, adjustable from 10 to 200 seconds in 1second increments AVR mode traverse rate, adjustable from 10 to 200 seconds in 1second increments Var mode traverse rate, adjustable from 10 to 200 seconds in 1second increments PF mode traverse rate, adjustable from 10 to 200 seconds in 1second increments FCR mode setpoint preposition; adjustment range is determined by registers (47699-700) and (47707-08) AVR mode setpoint preposition; adjustment range is determined by registers (47701-02) and (47709-10) Var mode setpoint preposition (in kvar); adjustment range is determined by registers (47703-04) and (47711-12) PF mode setpoint preposition; adjustment range is determined by registers (47705-06) and (47713-14) FCR mode setpoint step size = setpoint range / (traverse rate x 10): [ (regs. 47707-08) - (regs. 47699-700) ] / [ (regs. 47631-32) x 10 ] AVR mode setpoint step size = setpoint range / (traverse rate x 10): [ (regs. 47709-10) - (regs. 47701-02) ] / [ (regs. 47633-34) x 10 ] Var mode setpoint step size (in kvar) = setpoint range / (traverse rate x 10): [ (regs. 47711-12) - (regs. 47703-04) ] / [ (regs. 4763536) x 10 ] PF mode setpoint step size = setpoint range / (traverse rate x 10):[ 2 + (regs.47713-14) - (regs.47705-06) ] / [ (regs.47635-36) x 10 ] FCR mode setpoint minimum (in % of rated field current), adjustable from 0 to 100% in 0.1% increments AVR mode setpoint minimum (in % of rated generator output voltage), adjustable from 70 to 100% in 0.1% increments Var mode setpoint minimum (in % of rated generator VA), adjustable from -100 to 100% in 0.1% increments PF mode setpoint adjustable minimum, adjustable from 0.5 to 1.0 in 0.005 increments FCR mode setpoint maximum (in % of rated field current), adjustable from 100 to 120% in 0.1% increments AVR mode setpoint maximum (in % of rated generator output voltage), adjustable from 100 to 110% in 0.1% increments Modbus Communication Access RW RW RW RW RW RW RW RW RW RW RW R R R Data Format R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23

47653-54 47655-56 47657-58 47659-60 47661-62 47663-64 47665-66

R RW RW RW RW RW RW

R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23

DECS-200

7-17

Table 7-16. Information Category C6 (Setpoint Parameters) Registers 47667-68 47669-70 47671-72 47673-74 47675-76 47677-78 47679-80 47681-82 47683-84 47685-86 47687-88 47689-90 47691-92 47693-94 47695 47696 47697 47698 Data Description Var mode setpoint maximum (in % of rated generator VA), adjustable from -100 to 100% in 0.1% increments PF mode setpoint adjustable maximum, adjustable from -1.0 to -0.5 in 0.005 increments Minimum value for FCR mode setpoint adjustable minimum (in % of rated field current) = 0% Minimum value for AVR mode setpoint adjustable minimum (in % of rated generator output voltage) = 80% Minimum value for var mode setpoint adjustable minimum (in % of rated generator VA) = -100% Minimum value for PF mode setpoint adjustable minimum Maximum value for FCR mode setpoint adjustable maximum (in % of rated field current) = 120% Maximum value for AVR mode setpoint adjustable maximum in (in % of rated generator output voltage) = 110% Maximum value for var mode setpoint adjustable maximum (in % of rated generator VA) = 100% Maximum value for PF mode setpoint adjustable maximum Step size for FCR mode setpoint adjustable maximum (in % of rated field current) = 0.1% Step size for AVR mode setpoint adjustable maximum (in % of rated generator output voltage) = 0.1% Step size for var mode setpoint adjustable maximum in % of rated generator VA) = 0.1% Step size for PF mode setpoint adjustable maximum = 0.005 FCR preposition mode: 0 = maintained / 1 = release AVR preposition mode: 0 = maintained / 1 = release Var preposition mode: 0 = maintained / 1 = release PF preposition mode: 0 = maintained / 1 = release Access RW RW R R R R R R R R R R R R RW RW RW RW RRRRRRData Format R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 UI16 UI16 UI16 UI16 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23

47699-700 FCR minimum setpoint (in amps) = % of nominal x rated field current:(regs. 47655-56) x (regs. 47529-30) / 100 47701-02 47703-04 47705-06 47707-08 47709-10 AVR minimum setpoint (in volts) = % of nominal x rated gen. voltage:(regs. 47657-58) x (regs. 47525-26) / 100 Var minimum setpoint (in kvar) = % of nominal x rated generator VA:(regs. 47659-60) x rated VA / 100 PF minimum setpoint = registers 47661-62 FCR maximum setpoint (in amps) = % of nominal x rated field current:(regs. 47663-64) x (regs. 47529-30) / 100 AVR maximum setpoint (in volts) = % of nominal x rated gen. Voltage:(regs. 47665-66) x (regs. 47525-26) / 100

7-18

Modbus Communication

DECS-200

Table 7-16. Information Category C6 (Setpoint Parameters) Registers 47711-12 47713-14 47715 to 47740 Data Description Var maximum setpoint (in kvar) = % of nominal x rated gen. VA:(regs. 47667-68) x rated VA / 100 PF maximum setpoint = registers 47669-70 Reserved for future C6 data Access RRNot supported Data Format R32_23 R32_23 Not defined

Holding Registers for Information Category C7 Table 7-17. Information Category C7 (Startup Parameters) Registers 47741-42 47743-44 47745-46 47747-48 47749-50 47751-52 47753-54 47755-56 47757-58 47759-60 47761 to 47800 Data Description Soft start level, adjustable from 0 to 90 % (of rated generator voltage) in 1% increments Soft start duration, adjustable from 1 to 7,200 seconds in 1 second increments Underfrequency corner frequency, adjustable from 15 to 90 Hz in 0.1 Hz increments Slope of underfrequency curve, adjustable from 0.00 to 3.00 V/Hz in 0.01 V/Hz increments Width of voltage matching window, adjustable from 0 to 20 % (of rated generator voltage) in 0.01 % increments Voltage matching reference, adjustable from 90 to 120 % (of rated generator voltage) in 0.01 % increments Fine voltage adjust band, adjustable from 0 to 30 % (of rated generator voltage) in 0.1 % increments Time delay for loss of sensing, adjustable from 0 to 3 seconds in 0.1-second increments Loss of sensing level under balanced conditions, adjustable from 0% to 100% of rated generator voltage in 0.1% increments Loss of sensing level under unbalanced conditions, adjustable from 0% to 100% of rated generator voltage in 0.1% increments Reserved for future C7 data Access RW RW RW RW RW RW RW RW RW RW Not supported Data Format R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 Not defined

Holding Registers for Information Category C8 Table 7-18. Information Category C8 (Limiter Parameters) Registers 47801-02 47803-04 47805-06 DECS-200 Data Description On-line OEL high limit level, adjustable from 0.1 to 30 Adc in 0.1amp increments Time allowed at on-line OEL high limit level, adjustable from 0 to 10 seconds in 1-second increments On-line OEL medium limit level, adjustable from 0.1 to 20 Adc in Modbus Communication Access RW RW RW Data Format R32_23 R32_23 R32_23 7-19

Table 7-18. Information Category C8 (Limiter Parameters) Registers 0.1-amp increments 47807-08 47809-10 47811-12 47813-14 47815-16 47817-18 47819-20 47821-22 47823-24 47825-26 47827-28 47829-30 47831-32 47833-34 47835-36 47837-38 47839-40 47841-42 47843-44 47845-46 47847-48 7-20 Time allowed at on-line OEL medium limit level, adjustable from 0 to 120 seconds in 1-second increments On-line low OEL low limit level, adjustable from 0.1 to 15 Adc in 0.1amp increments Internal UEL curves starting point (reactive power level at 0 kW). This should be 0 to allow the programmable UEL curve to be used. Time allowed at off-line OEL high limit level, adjustable from 0 to 10 seconds in 1-second increments Off-line OEL high limit level, adjustable from 0 to 30 Adc in 0.1-amp increments Off-line OEL low limit level, adjustable from 0 to 15 Adc in 0.1-amp increments 1st UEL point real power value, adjustable from 0 to generators full rating (in kW) 2nd UEL point real power value, adjustable from 0 to generators full rating (in kW) 3rd UEL point real power value, adjustable from 0 to generators full rating (in kW) 4th UEL point real power value, adjustable from 0 to generators full rating (in kW) 5th UEL point real power value, adjustable from 0 to generators full rating (in kW) 1st UEL point reactive power value, adjustable from 0 to generators full rating (in kvar) 2nd UEL point reactive power value, adjustable from 0 to generators full rating (in kvar) 3rd UEL point reactive power value, adjustable from 0 to generators full rating (in kvar) 4th UEL point reactive power value, adjustable from 0 to generators full rating (in kvar) 5th UEL point reactive power value, adjustable from 0 to generators full rating (in kvar) SCL high limit level, adjustable from 0 to 66,000 A in 0.1 A increments Time allowed at SCL high limit level, adjustable from 0 to 60 seconds in 0.1 second increments. SCL low limit level, adjustable from 0 to 66,000 A, in 0.1 A increments Takeover OEL offline high limit level, adjustable from 0 to 9,999 A in 0.1 A increments Takeover OEL offline low limit level, adjustable from 0 to 9,999 A in 0.1 A increments. Modbus Communication RW RW RW RW RW RW RW RW RW RW RW RW RW RW RW RW RW RW RW RW RW R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 DECS-200 Data Description Access Data Format

Table 7-18. Information Category C8 (Limiter Parameters) Registers 47849-50 47851-52 47853-54 47855-56 47857 to 47860 Data Description Takeover OEL offline time dial, adjustable from 0.1 to 20, in 0.1 increments Takeover OEL online high limit level, adjustable from 0 to 9,999 A in 0.1 A increments. Takeover OEL online low limit level, adjustable from 0 to 9,999 A in 0.1 a increments. Takeover OEL online time dial, adjustable from 0.1 to 20 in 0.1 increments Reserved for future C8 data Access RW RW RW RW Not supported Data Format R32_23 R32_23 R32_23 R32_23 Not defined

Holding Registers for Information Category C9 Table 7-19. Information Category C9 (Control Loop Gain Parameters) Registers 47861-62 47863-64 47865-66 47867-68 47869-70 47871-72 47873-74 47875-76 47877-78 47879-80 47881-82 47883-84 47885-86 47887-88 47889-90 47891-92 Data Description Stability setting group number: 1 to 21, where groups 1 to 20 are preprogrammed values and group 21 is user programmable AVR/FCR mode proportional gain (Kp), adjustable from 0 to 1,000 in 0.1 increments AVR/FCR mode integral gain (Ki), adjustable from 0 to 1,000 in 0.1 increments AVR/FCR mode derivative gain (Kd), adjustable from 0 to 1,000 in 0.1 increments OEL integral gain (Ki), adjustable from 0 to 1000 in 0.1 increments PF mode integral gain (Ki), adjustable from 0 to 1,000 in 0.1 increments Var mode integral gain (Ki), adjustable from 0 to 1,000 in 0.01 increments FCR mode loop gain (Kg), adjustable from 0 to 1,000 in 0.1 increments AVR mode loop gain (Kg), adjustable from 0 to 1,000 in 0.1 increments Var mode loop gain (Kg), adjustable from 0 to 1,000 in 0.01 increments PF mode loop gain (Kg), adjustable from 0 to 1000 in 0.1 increments OEL loop gain (Kg), adjustable from 0 to 1000 in 0.1 increments UEL loop gain (Kg), adjustable from 0 to 1000 in 0.1 increments UEL integral gain (Ki), adjustable from 0 to 1000 in 0.1 increments Voltage matching loop gain (Kg), adjustable from 0 to 1,000 in 0.1 increments AVR mode derivative time constant, adjustable from 0 to 1 in 0.01 increments Modbus Communication Access RW RW RW RW RW RW RW RW RW RW RW RW RW RW RW RW Data Format R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23

DECS-200

7-21

47893 to 47905 47906-07 47908-09 47910-20

Reserved for future C9 data SCL loop gain (Kg), adjustable from 0 to 1,000 in 0.1 increments SCL loop gain (Ki), adjustable from 0 to 1,000 in 0.1 increments Reserved for future C9 data

Not supported RW RW Not supported

Not defined R32_23 R32_23 Not defined

Holding Registers for Information Category C10 Table 7-20. Information Category C10 (Protective Functions Parameters) Registers 47921-22 47923-24 47925-26 47927-28 47929-30 47931-32 47933-34 47935-36 47937 47938 47939 47940 47941-42 47943-44 47945 47946-47 47948-49 47950 47951-52 47953-54 7-22 Data Description Field overvoltage level, adjustable from 1 to 325 Vdc in 1-volt increments Field overcurrent base level, adjustable from 0.1 to 16 Adc in 0.1amp increments Stator undervoltage level, adjustable from 0 to 30,000 Vac in 1-volt increments Stator overvoltage level, adjustable from 0 to 30,000 Vac in 1-volt increments Field overvoltage time delay, adjustable from 0.2 to 30 seconds in 0.1-second increments Field overcurrent time dial multiplier, adjustable from 0.1 to 20 in 0.1 increments Stator undervoltage time delay, adjustable from 0.5 to 60 seconds in 0.1-second increments Stator overvoltage time delay, adjustable from 0.1 to 60 seconds in 0.1-second increments Field overvoltage alarm enable: 0 = disabled / 1 = enabled Field overcurrent alarm enable: 0 = disabled / 1 = enabled Stator undervoltage alarm enable: 0 = disabled / 1 = enabled Stator overvoltage alarm enable: 0 = disabled / 1 = enabled Reserved Reserved Reserved Exciter open diode ripple pickup level, adjustable from 0% to 100% in 0.1% increments. Exciter open diode time delay, adjustable from 10 to 60 seconds in 0.1 second increments. Exciter open diode protection enable: 0 = disabled / 1 = enabled Exciter shorted diode ripple pickup level, adjustable from 0% to 100% in 0.1% increments. Exciter shorted diode time delay, adjustable from 5 to 30 seconds in 0.1 second increments. Modbus Communication Access RW RW RW RW RW RW RW RW RW RW RW RW RW RW RW RW RW RW RW RW Data Format R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 R32_23 UI16 UI16 UI16 UI16 R32_23 R32_23 UI16 R32-23 R32-23 UI16 R32-23 R32-23 DECS-200

Registers 47955 47956-57 47958 47959-60 47961-62 47963 to 47980

Data Description Exciter shorted diode protection enable: 0 = disabled / 1 = enabled Exciter diode protection disable level, adjustable from 0% to 100% of rated exciter field current in 0.1% increments. Loss of field alarm enable: 0 = disabled, 1 = enabled Loss of field level, adjustable from 0 to 3,000 Mvar in 1 kvar increments Loss of field delay (in seconds): adjustable from 0.1 to 9.9 seconds Reserved for future C10 data

Access RW RW RW RW RW Not supported

Data Format UI16 R32_23 UI16 R32_23 R32_23 Not defined

Holding Registers for Information Category C11 Table 7-21. Information Category C11 (Calibration related Parameters) Registers 47981 to 48040 Data Description Reserved for future C11 data Access Not supported Data Format Not defined

Holding Registers for Information Category C12 Table 7-22. Information Category C12 (Relay Parameters) Registers 48041 Data Description Annunciation enable for Relay 1: 0 = disabled, 1 = enabled b0 = field overvoltage, b1 = field overcurrent, b2 = gen. Undervoltage, b3 = gen. Overvoltage, b4 = underfrequency, b5 = in OEL, b6 = in UEL, b7 = in FCR mode, b8 = loss of sensing voltage, b9 = setpoint at lower limit, b10 = setpoint at upper limit, b11 = unassigned, b12 = gen. Below 10 Hz, b13 = field overtemperature, b14, b15 are unassigned. 48042 48043 48044 48045 48046 48047 48048 48049 48050 48051 48052 48053 DECS-200 Annunciation enable for Relay 1: 0 = disabled, 1 = enabled b0 = loss of field, b1 = in SCL, b2-b15 are unassigned Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Modbus Communication RW RW RW RW RW RW RW RW RW RW RW RW UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16 7-23 Access RW Data Format UI16

Table 7-22. Information Category C12 (Relay Parameters) Registers 48054 48055 48056 48057 48058 48059 48060 Reserved Reserved 16th annunciation enable for Relay 1 - Reserved for future C12 data Output for Relay 1: 0 = contact open / 1 = contact closed Relay 1 annunciation: 0 = momentary / 1 = maintained / 2 = latched Relay 1 contact sense: 0 = closed for normal operation, open for annunciation; 1 = open for normal operation, closed for annunciation Relay 1 output duration for momentary type, adjustable 2 to 100 in unity increments (which is 0.1 to 5 seconds in 0.05-second increments) b0 = field overvoltage, b1 = field overcurrent, b2 = gen. Undervoltage, b3 = gen overvoltage, b4 = underfrequency, b5 = in OEL, b6 = in UEL, b7 = in FCR mode, b8 = loss of sensing voltage, b9 = setpoint at lower limit, b10 = setpoint at upper limit, b11 = unassigned, b12 = gen. Below 10 Hz, b13 = field overtemperature, b14-b15 are unassigned. b0 = loss of field, b1 = in SCL, b2-b15 are unassigned Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved 16th annunciation enable for Relay 2 Reserved for future C12 data Output for Relay 2: 0 = contact open / 1 = contact closed Relay 2 annunciation type: 0 = momentary / 1 = maintained / 2 = latched Relay 2 contact sense: 0 = closed for normal operation, open for annunciation; 1 = open for normal operation, closed for annunciation Relay 2 output duration for momentary type, adjustable from 2 to 100 in unity increments (which is 0.1 to 5 seconds in 0.05 second increments) Modbus Communication Data Description Access RW RW RW R RW RW RW Data Format UI16 UI16 UI16 UI16 UI16 UI16 UI16

48061

RW

UI16

48062 48063 48064 48065 48066 48067 48068 48069 48070 48071 48072 48073 48074 48075 48076 48077 48078 48079 48080

RW RW RW RW RW RW RW RW RW RW RW RW RW RW RW R RW RW RW

UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16

7-24

DECS-200

Table 7-22. Information Category C12 (Relay Parameters) Registers 48081 Data Description b0 = field overvoltage, b1 = field overcurrent, b2 = gen. Undervoltage, b3 = gen overvoltage, b4 = underfrequency, b5 = in OEL, b6 = in UEL, b7 = in FCR mode, b8 = loss of sensing voltage, b9 = setpoint at lower limit, b10 = setpoint at upper limit, b11 = unassigned, b12 = gen. Below 10 Hz, b13 = field overtemperature, b14-b15 are unassigned. b0 = loss of field, b1 = in SCL, b2-b15 are unassigned Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved 16th annunciation enable for Relay 3 - Reserved for future C12 data Output for Relay 3: 0 = contact open / 1 = contact closed Relay 3 annunciation type: 0 = momentary / 1 = maintained / 2 = latched Relay 3 contact sense: 0 = closed for normal operation, open for annunciation; 1 = open for normal operation, closed for annunciation Relay 3 output duration for momentary type, adjustable from 2 to 100 in unity increments (which is 0.1 to 5 s in 0.05 s increments) Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Modbus Communication Access RW Data Format UI16

48082 48083 48084 48085 48086 48087 48088 48089 48090 48091 48092 48093 48094 48095 48096 48097 48098 48099 48100 48101 48102 48103 48104 48105 48106 48107 48108 48109 DECS-200

RW RW RW RW RW RW RW RW RW RW RW RW RW RW RW R RW RW RW RW RW RW RW RW RW RW RW RW

UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16 7-25

Table 7-22. Information Category C12 (Relay Parameters) Registers 48110 48111 48112 48113 48114 48115 48116 48117 48118 48119 48120 48121 48122 48123 48124 to 48160 Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved for future C12 data Data Description Access RW RW RW RW RW RW RW RW RW RW RW RW RW RW Data Format UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16 UI16

Not Not supported defined

Holding Registers for Information Category C13 Table 7-23. Information Category C13 (Communications Parameters) Registers 48161 Data Description Save data to EEPROM flags: 0x0001 saves C4 and C6; 0x0002 saves C5 and C7; 0x0004 saves C6; 0x0008 saves C5 and C7; 0x0010 saves C8; 0x0020 saves C9; 0x0040 saves C10; 0x0080 saves C11; 0x0100 saves C12; 0x0800 saves C14. (Changes in C13 are automatically saved.) 48162 48163 48164 48165 Comm. Port 0, front RS-232, baud rate, selectable to be 1200, 2400, 4800, 9600, or 19200 Comm. port 1, rear RS-232, baud rate, selectable to be 1200, 2400, 4800, 9600 or 19200 Comm. port 2, rear RS-485, baud rate, selectable to be 1200, 2400, 4800, 9600 or 19200 Comm. port 2, Rear RS-485, Parity: O = 79 = 0x4F for Odd Parity,E = 69 = 0x45 for Even Parity, and N = 78 = 0x4E for No Parity Comm. port 2, Rear RS-485, stop bits, selectable to be 1 or 2 DECS-200 polling address (Modbus slave address), selectable from 1 to 247 (slave address) Modbus Response Time Delay, adjustable from 10 to 200 ms in 10 ms increments R R RW RW UI16 UI16 UI16 UI8 Access RW Data Format UI16

48166 48167 48168

RW RW RW

UI8 UI16 UI16

7-26

Modbus Communication

DECS-200

Registers 48169 to 48220 Reserved for future C13

Data Description

Access Not supported

Data Format Not defined

Holding Registers for Information Category C14 Table 7-24. Information Category C14 (Front Panel Metering Configuration Parameters) Registers 48221 48222 48223 48224 to 48250
nd rd

Data Description 1st metering display field on the front panel metering screen: 0 to 14 2 metering display field on the front panel metering screen: 0 to 14 3 metering display field on the front panel metering screen: 0 to 14 Reserved for future C14 data

Access RW RW RW Not supported

Data Format UI16 UI16 UI16 Not defined

Holding Registers for Information Category C15 Table 7-25. Information Category C15 (Control System Configuration Parameters Group II) Registers 48501-02 48503-04 48505-06 48505-07 48505-08 Reserved Reserved Reserved Reserved Reserved Data Description Access RW RW RW RW RW RW Data Format R32_23 R32_23 R32_23 UI16 UI16 R32_23

48505-09, EDM Pole Ratio (1 to 10 in steps of 0.01, Enter 0 if unknown) 10

DECS-200

Modbus Communication

7-27

This page intentionally left blank.

7-28

Modbus Communication

DECS-200

SECTION 8 MAINTENANCE
PREVENTIVE MAINTENANCE
The only preventive maintenance required for the DECS-200 is the periodic checking of DECS-200 connections to ensure that they are clean and tight.

WARRANTY AND REPAIR SERVICE


DECS-200 units are manufactured using state-of-the-art, surface-mount technology. As such, Basler Electric recommends that no repair procedures be attempted by anyone other than Basler Electric. The DECS-200 is warranted against defective material and workmanship for 18 months from the date of shipment from Basler Electric. Units submitted for warranty repair should be returned to Basler Electrics Highland, Illinois facility, freight prepaid, with a complete description of the application and the reported problem. Prearrangement with either the nearest Basler Electric sales office or with the Technical Sales Support department at Basler Electric will assure the fastest possible turnaround time.

TROUBLESHOOTING
The following troubleshooting procedures assume the excitation system components are properly matched, fully operational, and correctly connected. If you do not obtain the results that you expect from the DECS-200, first check the programmable settings for the appropriate function. DECS-200 Appears Inoperative If the DECS-200 does not power up (no backlighting on front panel display), ensure that the control power applied to the unit is at the correct level. If dc control power is being used, verify that the polarity is correct. Units with style number XL have an input voltage range of 16 to 60 Vdc. Units with style number XC have an input voltage range of 90 to 150 Vdc or 82 to 132 Vac (50/60 Hz). If the correct control power is being applied, return the unit to Basler Electric as described under Warranty and Repair Service. NOTE When both ac and dc control power is used, an isolation transformer must be connected between the ac voltage source and the ac control power terminals of the DECS-200. Display Blank or Frozen If the front panel display (LCD) is blank or frozen (does not scroll), remove control power for about 60 seconds and then reapply control power. If the problem occurred during software uploading, repeat the upload procedures as described in the associated instructions. If the problem persists, return the unit to Basler Electric as described under Warranty and Repair Service. Generator Voltage Does Not Build Check the DECS-200 settings and system voltages for the following: a. Generator potential transformer (PT) primary voltage b. Generator PT secondary voltage c. AC voltage on the DECS-200 operating (bridge) power terminals (C5 (A), C6 (B), and C7 (C)) Check the DECS-200 soft start bias and soft start time settings. If necessary, increase the generator soft start bias and decrease the generator soft start time. If the generator voltage still does not build, increase the value of Kg. Temporarily disable the overexcitation limiter. Low Generator Voltage in AVR Mode Check the following DECS-200 settings and system parameters: a. AVR voltage setpoint b. Generator potential transformer (PT) primary voltage c. Generator PT secondary voltage 9360100990 Rev G DECS-200 Maintenance

8-1

d. e. f. g.

Overexcitation limiter (not activated) Accessory inputs (should be zero) Var/PF and droop (should be disabled) Cut-in underfrequency setting (should be below the generator operating frequency)

If the problem persists, contact the Basler Electric Technical Sales Support department for advice. High Generator Voltage in AVR Mode Check the following DECS-200 settings and system parameters: a. AVR voltage setpoint b. Generator potential transformer (PT) primary voltage c. Generator PT secondary voltage d. Accessory inputs (should be zero) e. Var/PF and droop (should be disabled) If the problem persists, contact the Basler Electric Technical Sales Support department for advice. Generator Voltage Unstable (Hunting) Verify that the exciter power converter is working correctly by substituting the appropriate battery voltage in place of the DECS-200 drive voltage. If the problem is caused by the DECS-200, check the gain settings for the specific mode of operation selected. If the problem persists, contact the Basler Electric Technical Sales Support department for advice. Protection or Limit Annunciation If a protection function or limiting function is annunciated, check the associated setting values. If the problem persists, contact the Basler Electric Technical Sales Support department for advice. HMI Meter Readings Incorrect If your PF, var, or watt readings are significantly different from the expected readings for a known load, verify that the B-phase current sensing input of the DECS-200 is connected to a CT on phase B and not phases A or C. No Communication If communication with the DECS-200 cannot be initiated, check the connections at the communication ports, the baud rate, and supporting software. DECS-200 Reboots Frequently If a single DECS-200 control power source is used and the power source is supplying less than the minimum required voltage or is fluctuating below the minimum required voltage, the DECS-200 will reboot. Increase the control power source voltage so that it is within the specified operating range. Units with style number XL have an input voltage range of 16 to 60 Vdc. Units with style number XC have an input voltage range of 90 to 150 Vdc or 82 to 132 Vac (50/60 Hz).

8-2

DECS-200 Maintenance

9360100990 Rev G

ROUTE 143, BOX 269 HIGHLAND, IL 62249 USA http://www.basler.com, [email protected] PHONE +1 618-654-2341 FAX +1 618-654-2351

You might also like