Acs Manual
Acs Manual
Acs Manual
ACS Series
ECN 06-069
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until manuals are read and understood. CAUTION - System Re-acceptance Test after Software Changes: To ensure proper system operation, this product must be tested in accordance with NFPA 72 after any programming operation or change in sitespecific software. Re-acceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified. This system meets NFPA requirements for operation at 0-49 C/32-120 F and at a relative humidity 93% 2% RH (noncondensing) at 32C 2C (90F 3F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15-27 C/60-80 F. Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage. Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning induced transients. Although no system is completely immune from lightning transients and interference, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated or encountered. Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits. Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, or printed circuit board location. Do not tighten screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal. This system contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies removed from the unit. Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation. Precau-D1-9-2005
FCC Warning
WARNING: This equipment generates, uses,
and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing devices pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when devices are operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at his or her own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications. Le present appareil numerique n'emet pas de bruits radioelectriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada.
Acclimate Plus, HARSH, NIS, Notifier Integrated Systems, NOTIFIRENET, and ONYXWorks are all trademarks; and FlashScan, NION, NOTIFIER, ONYX, UniNet, VeriFire, and VIEW are all registered trademarks of Honeywell International Inc. Echelon is a registered trademark and LonWorks is a trademark of Echelon Corporation. ARCNET is a registered trademark of Datapoint Corporation. Microsoft and Windows are registered trademarks of the Microsoft Corporation. LEXAN is a registered trademark of GE Plastics, a subsidiary of General Electric Company. 2007 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online Help or printed manuals, you can email us. Please include the following information: Product name and version number (if applicable) Printed manual or online Help Topic Title (for online Help) Page number (for printed manual) Brief description of content you think should be improved or corrected Your suggestion for how to correct/improve documentation
[email protected]
Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services.
Table of Contents
Section 1: Introduction.......................................................... 9
1.1: About This Manual..............................................................................9 1.2: UL 864 Compliance.............................................................................9 1.2.1: Products Subject to AHJ Approval ...............................................9 1.3: Related Documentation .....................................................................10
Table of Contents
5.7: End of Line Resistor for EIA-485 Circuit ........................................ 37 5.8: Earth Ground .................................................................................... 37 5.9: Main Power Supply Connections ..................................................... 37 5.10: Labeling Annunciators & Expanders............................................. 39 5.11: Connecting Annunciator Key Switch and Phone Jack ................... 40 5.12: Setting Address and DIP Switches: ACM-24AT, ACM-48A......... 40 5.12.1: DIP Switch Summary: ACM-24AT, ACM-48A ..................... 40 5.12.2: Addressing ACM-24AT and ACM-48A.................................. 41 5.12.3: Configuring Number of Expander Modules ............................ 42 5.12.4: Speaker Control Mode ............................................................ 42 5.13: Setting Address and DIP Switches: ACM-16AT, ACM-32A......... 47 5.13.1: DIP Switch Summary: ACM-16AT, ACM-32A ..................... 47 5.13.2: Addressing ACM-16AT and ACM-32A.................................. 47 5.13.3: Configuring Number of Expander Modules ............................ 47 5.14: Supervising Devices with ACM-16AT, ACM-32A ........................ 48 5.15: Programming the Control Panel and Annunciators ........................ 48 5.15.1: Selecting LED Colors: ACM-24AT and AEM-24AT ............. 48 5.15.2: Selecting LED Colors: ACM-48A & AEM-48A..................... 49 5.16: Testing the Annunciators ................................................................ 49
Table of Contents
Appendix E: NFS2-640 (UL 9th), NFS-320 (UL 9th) and NFS640 Systems (UL 8th) .......................................................... 73
E.1: Capabilities........................................................................................73 E.2: NFS2-640 and NFS-320 Connections: EIA-485 Circuit and Power ... 74 E.3: NFS-640s EIA-485 Connections .....................................................74 E.4: NFS-640s Power Connections .........................................................74 E.5: Configuring Annunciators for NFS-320, NFS2-640, and NFS-640 .75 E.6: System and Point Annunciation ........................................................75
Appendix F: System 500 Systems: ACM-16AT and ACM32A Only (UL 8th)................................................................. 77
F.1: Capabilities ........................................................................................77 F.2: Connecting EIA-485 Circuit..............................................................78 F.3: Providing Power to Annunciators......................................................78 F.4: Configuring the ACS for System 500 ...............................................79 F.5: ACS Program Mapping .....................................................................79
Appendix G: System 5000 Systems: ACM-16AT and ACM32A Only (UL 8th)................................................................. 82
G.1: Capabilities........................................................................................82 G.2: Connecting the EIA-485 Circuit .......................................................82 G.3: Providing Power to Annunciators .....................................................83
ACS Manual P/N 15842:M 12/28/2006 7
Table of Contents
G.4: Installing Modules in the System ..................................................... 84 G.5: Configuring the ACS for System 5000 ............................................ 85 G.6: ACS Program Mapping .................................................................... 85 G.7: AIM-200 Point Annunciation........................................................... 87
Appendix H: Combination Fire Alarm/Burglary Systems 89 Appendix I: NCA Systems (UL 8th) .................................... 90
I.1: Capabilities ........................................................................................ 90 I.2: Connecting the EIA-485 Circuit........................................................ 90 I.3: Providing Power to Annunciators ..................................................... 90 I.4: Programming the NCA for Remote Annunciation............................ 91 I.5: Configuring Annunciators for the NCA ............................................ 92
Appendix J: NFS-3030 Systems (UL 8th), NFS2-3030 Systems (UL 9th), and NCA-2 Systems (UL 9th) 93
J.1: Capabilities........................................................................................ 93 J.2: Connecting the EIA-485 Circuit ....................................................... 94 J.3: Providing Power to Annunciators ..................................................... 94 J.4: Programming the NFS-3030/NFS2-3030/NCA-2 for Remote Annunciation............................................................................................ 95 J.5: Configuring Annunciators for NFS-3030, NFS2-3030, or NCA-2... 96 J.6: Configurations for Specific Applications with NFS-3030, NFS2-3030, or NCA-2 ................................................................................................. 96 J.6.1: Common System Annunciation.................................................. 97 J.6.2: Speaker and Telephone Mode with NFS-3030/NFS2-3030/NCA-2 97 J.6.3: Manual Override with NFS-3030/NFS2-3030/NCA-2 .............. 98 J.7: ACS Program Mapping with NFS-3030/NFS2-3030/NCA-2 .......... 99
Section 1: Introduction
1.1 About This Manual
The core of this manual provides instructions for connecting an ACS series annunciator to various fire alarm control panels (FACPs). Each appendix contains instructions that are unique to a particular control panel. Section 1.3 Related Documentation lists part numbers for manuals of compatible equipment such as control panels. This manual provides instructions for two sets of ACS series annunciators. Both sets can be used in the same fire alarm system. There are four basic controller modules, each with its own expander module: ACM-24AT, ACM-48A, AEM-24AT, and AEM-48A: Up to 96 points can occupy the same address, subject to the limits of the control panel. ACM-16AT, ACM-32A, AEM-16AT, AEM-32A, and multi-color variations (Section 3 Product Overview lists similarly numbered models that provide different LED colors): Up to 64 points can occupy the same address, subject to the limits of the control panel. In this manual, when the two varieties of ACS annunciator differ, the ACM-24AT/ACM-48A annunciators are discussed first.
Introduction
Related Documentation
10
ACS annunciators provide Notifier fire alarm control panels or network displays with remote serially connected annunciators. Arrays of LEDs indicate, at a remote location, the status of circuits within the system. Individual fire alarm control panels offer different methods of identifying annunciator points. Common system functions such as signal silence, system reset, and local annunciation controls (local acknowledge and lamp test) are controlled through switches on the annunciators keypad. Communication between the control panels or network displays and these annunciators is accomplished over a power-limited, two-wire serial interface employing an EIA-485 communication standard. Power for these annunciators is provided via a separate power-limited power loop from the control panel which is inherently supervised by these annunciators (loss of power results in an annunciator communication failure at the control panel). These annunciators can also be powered from a power-limited and regulated remote power supply listed for fire-protective signalling use. The National Standard of Canada (CAN/ULC-S527) requires that a dedicated display use yellow visual indicators to indicate the status of supervisory inputs. The annunciators listed below are intended to be used for Canadian Supervisory Service in conjunction with AFP-200, AFP400, S500, S2500, and S5000 control units (subject to annunciatorpanel compatibility): ACM-24AT/ACM-48A and expanders: These modules provide programmable colors (red/green/yellow).
ACS Manual P/N 15842:M 12/28/2006 11
Product Overview
General
ACM-16AT/ACM-32A and expanders: Modules in the -16/-32 Y series have been designed with yellow LEDs; other colors are also available (see Section 3.3 and Section 3.4). The ACM-32A, AEM-32A, ACM-16AT, and AEM-16AT annunciators can not be employed for ULC Supervisory Service. See Canadian Requirements for Supervisory Signal in Notifier Document 50056.
WARNING: ACM-24AT, ACM-48A and expanders have been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864 9th Edition. Operation of this product with products tested for UL 864 9th Edition has not been evaluated and may not comply with NFPA 72 and/or the latest edition of UL 864. These applications will require the approval of the local Authority Having Jurisdiction (AHJ). WARNING: ACM-16AT, ACM-32A and expanders have not been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864 9th Edition. Operation of this product with products tested for UL 864 9th Edition has not been evaluated and may not comply with NFPA 72 and/or the latest edition of UL 864. These applications will require the approval of the local Authority Having Jurisdiction (AHJ).
1. Section 1.3 Related Documentation lists part numbers for manuals of compatible equipment such as control panels. AFC-600 has been discontinued; to service existing installations, refer to the original manuals shipped with the panel.
12
General
Product Overview
AFP-200 (64 points) AFP-300/AFP-400 (64 points) NCA and NCA-2 (64 points) INA (64 points) System 500, System 5000, System 2500 (64 points)
13
Product Overview
General
NFS-320, NFS2-640, and NFS-640. Annunciator points are programmable by group or by point. (Note: User-defined points can be defined by using VeriFire software; see your control panel manual.) AM2020, AFP1010. Annunciator points are completely programmable and can be employed to annunciate and manually control common system, voice or telephone circuits. AFP-100, AFP-200, AFP-300, AFP-400. Annunciator points are programmable by group. (Note: User-defined points can be defined for AFP-300/AFP-400 systems by using VeriFire software; see your control panel manual.*) System 5000, System 2500, System 500. Annunciator points directly follow the circuit arrangement of modules installed in the cabinet. The Network Control Annunciator (NCA or NCA-2) and Intelligent Network Annunciator (INA) can employ these annunciators on the EIA485 interface. Refer to the NCA Manual, NCA-2 Manual or INA Manual* for further details.
14
This section is intended as a basic inventory of components that can be used in an ACS system. For system design considerations, see Section 4. For installation, configuration and programming instructions, see Section 5. For LED and Switch functions instructions, see Section 6.
Expander: The AEM-24AT is an expander board for the ACM-24AT with an additional 24 switched and controlled annunciator points. An ACM-24AT can support one, two, or three
1. Check local regulations when programming colors; some jurisdictions restrict color choice. For example, in Canada red indicates active alarm inputs; yellow indicates supervisory, burglary or trouble signals; green indicates the presence of power, or an activated output.
ACM-24atface.wmf
15
Product Overview
expanders at the same address, to a maximum of 96 system points. Note: The AEM-24AT cannot be used to expand the ACM-48A, ACM-16AT series, or ACM-32A series.
Expander The AEM-48A is an expander board for the ACM-48A with an additional 48 switched and controlled annunciator points. An ACM-48A can support one expander at the same address for a maximum of 96 system points. Note: The AEM-48A cannot be used to expand the ACM-24AT, ACM-16AT series, or ACM-32A series. Power Requirements 24VDC nominal, 27.6VDC max, 70mA max
current.
1. In Canada the color red must be used to indicate active alarm inputs. Yellow indicates supervisory, burglary or trouble signals. Green indicates the presence of power, or an activated output.
16
acm-16AT-face.cdr
ACM-48A-FACE.wmf
Product Overview
ACM-16ATY* Same as the ACM-16AT, except that all LEDs are yellow (yellow On/Alarm and yellow Trouble). In Canada this module must be used to annunciate supervisory and burglary signals from associated points/zones. ACM-16ATCS4* (for use in Canada) The Annunciator Control
Module 16ATCS4 contains 12 red point active, four yellow point active, and 16 yellow trouble LEDs, 16 momentary touch-pad switches for controlling each point, a system trouble LED, an On-line/Power LED, and a local piezo sounder with a silence/acknowledge switch for audible indication of alarm and trouble conditions at each annunciator. In Canada this module must be used to annunciate supervisory and burglary signals from associated points/zones.
ACM-16ATCS* (for use in Canada) The Annunciator Control Module 16ATCS contains 8 red point active and 8 yellow point active LEDs, 16 yellow trouble LEDs, 16 momentary touch-pad switches for controlling each point, an On-line/Power LED, and a local piezo sounder with a silence/acknowledge switch for audible indication of alarm and trouble conditions at each annunciator. In Canada this module must be used to annunciate supervisory and burglary signals from associated points/zones.
AEM-16ATG* Same as the AEM-16AT, but On/Alarm LEDs are green (green On/Alarm and yellow Trouble).
17
Product Overview
but On/Alarm LEDs are green (green On/Alarm and yellow Trouble). In Canada this module may be used to annunciate notification appliance circuit activation or other output circuit/zone activation.
ACM-32AY* Same as the ACM-32A but with all LEDs yellow (yellow On/Alarm and yellow Trouble). In Canada this module must be used to annunciate supervisory and burglary signals from associated points/zones.
AEM-32Y* Same as the AEM-32A but with all LEDs yellow (yellow
On/Alarm and yellow Trouble).
AEM-32G2 Same as the AEM-32A, but On/Alarm LEDs are green (green On/Alarm and yellow Trouble).
1. In Canada the color red must be used to indicate active alarm inputs. Yellow indicates supervisory, burglary or trouble signals. Green indicates the presence of power, or an activated output. 2. In Canada the color red must be used to indicate active alarm inputs. Yellow indicates supervisory, burglary or trouble signals. Green indicates the presence of power, or an activated output.
18
acm-32A-face3.cdr
Product Overview
ABS-1B Mounts one annunciator directly to the ABS-1B without a dress plate. Note: This backbox will not support the installation of the Annunciator Key Switch or the Annunciator Phone Jack for Firefighters' Telephone.
ABS-1B
ABS-2B Mounts two annunciators directly to the ABS-2B without a dress plate. Note: This backbox will not support the installation of the Annunciator Key Switch or the Annunciator Phone Jack. ABS-2D, ABS-2DR Mounts two annunciators. This surface box can
also be mounted semi-flush. Note: This backbox will not support the installation of the Annunciator Key Switch or the Annunciator Phone Jack for Firefighters' Telephone.
ABS-1TB Mounts one annunciator. Unlike the ABS-1B and ABS-2B, the ABS-1TB has an increased depth that allows mounting of the Annunciator Phone Jack for Firefighters' Telephone and Annunciator Key Switch.
50439d2.tif
ABF-1B
abf-1-iso.wmf
ABF-4B
ABF-1B Mounts one annunciator. ABF-2B Mounts two annunciators. ABF-4B Mounts four annunciators.
ACS Manual P/N 15842:M 12/28/2006 19
abf-1-iso.wmf
Product Overview
ABF-1DB, ABF-1D
ABF-2B
Box: 9.938" (25.24 cm) Box: 9.188" (23.34 cm) Trim plate: 11" (27.94 cm) Trim plate: 10.625" (26.99 cm) Box: 9.938" (25.24 cm) Trim plate: 11.0" (27.94 cm) Box: 9.938" (25.24 cm) Door: 11.0" (27.94 cm) Box: 9.938" (25.24 cm) Door: 11.0" (27.94 cm)
ABF-4B
Box: 17.750" (45.09 cm) 2.5" (6.35 cm) Trim plate: 19.375" (49.21 cm) Box: 4.625" (11.75 cm) Door: 6" (15.24 cm) Box: 2.5" (6.35 cm) Door: 0.75" (1.9 cm)
ABF-1DB ABF-2DB
Box: 9.188" (20.80 cm) Box: 3.750" (9.53 cm) Door: 10.375" (26.35 cm) Door: 0.75" (1.9 cm)
20
ABF-1-isoview.wmf, abf-1db.wmf
ABF-1DB Mounts one annunciator behind an attractive smoked glass door with keylock.
Product Overview
ADP-4B (Shown with ACM-24AT Modules) DP-DISP Dress Panel Display provides for the cabinet mounting of one
to four annunciators, including applications where two annunciators are mounted to the right of a control panel keypad, a network annunciator, or a digital voice command keypad. The DP-DISP hinge-mounts to a CAB-4 series backbox; chassis CHS-4L or chassis CA-1 can be mounted behind it. Annunciators and expanders mount directly to threaded studs on the dress panel.
dp-disp
adp-4b-with24at.cdr
21
Product Overview
DP-DISP2 and ADP2-640 These two dress panels mount the NFS2640 and two ACS annunciators. See the NFS2-640 Installation Manual for details.
DP-DISP2 (Shown with NFS2-640 and one ACM-24AT) ABM-1 The Annunciator Blank Module is a two-sided dress plate
identical in appearance to the front panels of the ACM-16AT and AEM16AT modules on one side, and the front panels of the ACM-32A and AEM-32A modules on the other side. The blank module covers unused module positions in the annunciator backbox or dress panel.
BMP-1 Blank module dress plate is a flat, black metal plate which covers unused module positions in the annunciator backbox or dress panel and optionally provides an additional mounting position for some modules. For use with black backboxes and dress panels. VP-2B Use the VP-2B Vented Dress Panel when annunciators are to be
installed in the top row of a Notifier cabinet with the ADP-4B or ADP2640. It covers the gap between the ADP-4B and the top of the cabinet. It secures to the cabinet with two screws.
vp-2revc
AKS-1B The Annunciator Key Switch provides access security for the control switches on the ACM-24AT and ACM-16AT. The key switch kit includes a key and hardware for mounting to the trim plate of a flushmount type annunciator enclosure. Also included is an adhesive-backed Annunciator Label for use with the key switch/dress plate assembly. Note: The key switch can only be employed with a flush-mount type backbox or ABS-1TB.
22
DP-DISP2-assy-640.wmf
Product Overview
23
The standard Notifier EIA-485 circuit can drive up to 32 annunciators with expanders. One system can mix ACM-24AT, ACM-48A, ACM16AT, ACM-32A, and their expanders with other ACS devices such as LDM, TM-4, etc. An end-of-line resistor must be installed or enabled on the last ACS device on the circuit. The number of annunciators that can engage in two-way communication depends on the number of addresses available with a given fire alarm control panel. The actual number of ACS devices that can be powered in a particular system depends on the current available from the control panels power supply. Refer to the installation manual for the particular control panel for more details. For information on boosting the EIA-485 circuit signal or adding additional devices (not addresses), see the RPT-485W/RPT-485WF Installation Manual.
24
Design Considerations
NOTE:(AM2020/AFP1010 installations only) SIB-2048A/SIB-NET can support two EIA-485 circuits, each capable of spanning 6,000 feet at 16 AWG. For more details, refer to Appendix D.
Annunciator
caba3.wmf, ACM-24atface.wmf
25
Design Considerations
Receive only Annunciator set to address X and installed upstream. Full Function Receive/Transmit Annunciator set to Address X
Annunciator
Expander
26
Design Considerations
Annunciators in a backbox, powered from control panel Power Loop EIA-485 Reference
EIA-485 Circuit
A common reference connection must be made between multiple power supplies for the EIA-485 circuit to function properly!
ACM-24ATface.cdr
Figure 4.2 Using Multiple Power Supplies With the EIA-485 Circuit
caba3.wmf
27
Design Considerations
Electrical Ratings
Input Voltage: 24 VDC (must be power-limited and non-resettable). Use a regulated, power-limited, compatible power supply that is UL/ULC-Listed for Fire Protective Signaling use. Data Communications Port: EIA-485 operating at 20 Kbps (must be power-limited).
28
Design Considerations
Non-Fire Alarm Status A: On-line LED is flashing; all other LEDs are off
Number of ACM-24AT/ACM-48A modules [_____] Number of AEM-24AT/AEM-48A modules [_____] amps Number of ACM-16AT/ACM-32A modules [_____] amps X 0.016 = [_________] amps X 0.002 = [__________] X 0.040 = [__________]
Note: The 0.040 amps can be reduced to 0.030 for ACM-16AT/ACM-32A modules with Piezo Disable or Flash Inhibit modes selected. Number of AEM-16AT/AEM-32A modules [_____] amps Number of ACM-24AT/ACM-48A modules assumed to have points active simultaneously[_____] amps Number of AEM-24AT/AEM-48A modules assumed to have points active simultaneously[_____] amps Number of ACM-16AT/ACM-32A or AEM-16AT/AEM-32A modules assumed to have points active simultaneously[_____] amps Total Annunciator Standby Current amps X 0.002 = [__________]
Non-Fire Alarm Status B: On-line LED is on; other LEDs are also on
X 0.070 = [__________]
X 0.056 = [__________]
X 0.056 = [__________]
[_____]
X 0.018 = [__________]
Note: This entry assumes that all LEDs are lit simultaneously. When the alarm system specification permits, calculations can be based on a 10% alarm loading capacity. For 10% capacity, enter 10% of the total number of ACM and AEM modules multiplied by the number of remote annunciator locations, but do not enter less than one. Total Annunciator Fire-Alarm Current amps Total Annunciator Standby Current + Total Annunciator Fire-Alarm Current amps = [__________]
= [__________]
30
Expander Connectors: J3 J1 Power Supply Connectors TB2 EIA-485 Connectors TB1 ACM-24AT End of Line Resistor Switch SW29 AEM-24AT
ACM-24-reverse.wmf, AEM-24-reverse.wmf ACM-48-reverse.wmf, AEM-48-reverse.wmf
Expander Connectors: J3 J1
Power Supply Connectors TB2 EIA-485 Connectors TB1 ACM-48A End of Line Resistor Switch SW29 AEM-48A
31
Installation, Configuration, and Programming Addressing Switches Annunciator Key Switch Connector
Expander Connector J1
DIP Switches
32
AnWir_in.tif
33
Plug the two annunciator terminal blocks into the annunciator to complete communication and power circuit connections as described in Section 5.5 and Section 5.9. If using an annunciator backbox, place the annunciator/dressplate assembly into the backbox and secure with two screws.
If using a semi-flush-mount backbox, attach door. Align the door with the dress plate, and slide the door down onto the pins on the dress plate. When positioned correctly, the door will open and close freely (see diagram in Section 3.5 Cabinet & Panel Hardware).
acm24at-aem.cdr
J3 J4 J3 J4 J3 J4 J3
acm48-aem.cdr
J4 J3
RS485-
J1
J2
J1
J2
J1
J2
J1
RS 485 +
REF
AEM-24AT
AEM-24AT
AEM-24AT
ACM-24AT
E GND
AEM-48A
ACM-48A
34
REF
RS4 85-
J2
J1
REF
J2
REF
RS48 5+
J2
J2
J2
J2
J2
P3
P3
P3
P3
AEM-16AT
AEM-16AT
AEM-16AT
ACM-16AT
AEM-32A
ACM-32A
35
+ + + + + +
In Out Out In
In Out Out In
acs_eia.cdr
Note: See Section 5.7 End of Line Resistor for EIA-485 Circuit to set on-board ELR for ACM-24AT/ACM-48A.
- +
enclosures, including the FACP backbox, must be connected to earth ground! Never use the shield for grounding purposes. Terminate the EIA485 shield at the Fire Alarm Control Panel only. When the EIA-485 shield is in conduit: Connect it to system reference (system common). The shield can enter the cabinet, but must be insulated from the cabinet (no electrical contact). Between annunciators, wire-nut multiple shields together (which can be inside of the respective enclosure, but can not contact the enclosure). When the EIA-485 shield is not in conduit: Terminate the shield at the outside of the FACP backbox (ground). Do not allow the shield to enter or even touch the cabinet. Between annunciators, wire-nut multiple shields together outside of the respective enclosures (see Figure 5.11).
See accompanying figures for power supply diagrams: Figure 5.13, Power Circuit for ACM-24AT and ACM-48A. Figure 5.14, Power Circuit for ACM-16AT and ACM-32A. For details about connections to particular control panels, see the appropriate appendix in this manual.
NOTE:All power must be turned off when connecting the 24 VDC power to the annunciator. Reapply power according to the instructions in your control panel manual.
TB2 PWR SUPPLY
+ +
TB1 N.C. Trouble Inputs N.C. Trouble Inputs Common In Common Out Power In Power Out Earth Ground
+ +
TB1
+ +
+ +
N.C. Trouble Inputs N.C. Trouble Inputs Common In Common Out Power In Power Out Earth Ground
+ +
TB1
24 VDC Power
- +
N.C. Trouble Inputs N.C. Trouble Inputs Common In Common Out Power In Power Out Earth Ground
+ +
Note: On ACM-24AT and ACM-48A, earth ground is on TB1 with the EIA-485 connection.
ACS16-32-pwr.cdr
+ 24 VDC Power
(filtered, non-resettable, listed for fire-protective signalling use)
NOTE:ACM-24AT, ACM-48A, and expanders provide a plastic protector sheet to insert with the slide-in labels. Labels should be slightly narrower than the protector sheet to allow easier insertion.
Notifiers MagniFire CD contains LabelEasea program for customizing professional slide-in labels.
Apply adhesive label onto flush-mount dress plate: If mounting the annunciator onto a flush-mount dress plate, remove backing from the adhesive-backed Annunciator Label and stick the label to the bottom of the dress plate as shown in Figure 5.16.
abf1plate.cdr, lbl15824.tif
Installation, Configuration, and Programming Connecting Annunciator Key Switch and Phone
J4
Table 5.1
Telephone Circuit
Figure 5.17 Connecting Annunciator Key Switch and Phone Jack (ACM-16AT shown)
NOTE:Connector location varies with annunciator model; see Table 5.1
Wire phone jack into telephone circuit as shown in Figure 5.17. If annunciator is last jack on telephone circuit, a resistor is required on the phone jack where shown. Resistor rating varies depending on your system configuration: If using a VCM-4RK configured for telephone operation: 4.7K Ohm. If using a FCM-1, a XP5-C, a XPC-8 or XPIQ circuit: 47K Ohm.
Turn ON for Program mode. Used to cycle LED colors for annunciator points on the ACM-24AT and all AEM-24ATs connected to it. While in this mode, communication with panel is broken and interrupt routines are disabled. Turn OFF for normal operating mode. Configures Speaker Control Mode; see Section 5.12.4 Speaker Control Mode for more details. Turn ON for Manual override of control relays: When manual override button is pressed, CBE or CCBE will be inhibited. (Not supported by all control panels; see appendix section) Turn OFF for normal operating mode Specifies the number of expanders installed; see Section 5.12.3 Configuring Number of Expander Modules. Not used; set to OFF Turn ON to set annunciator as Receive Only: Duplicates another annunciator operating at the same address; see Section 4.4 Receive/Transmit and Receive Only Configuration Turn OFF for normal operating mode (receive/transmit) Turn ON to disable piezo. Turn OFF to leave piezo in normal operating mode. Turn ON to enable Switch inhibit: Point-control switches cannot execute system control functions. Turn OFF for normal operating mode. Turn ON for Flash inhibit: Disables flashing LEDs and prohibits piezo from sounding. Turn OFF for normal operating mode. Sets LED colors on ACM-48A; see Section 5.15.2 Selecting LED Colors: ACM-48A & AEM-48A Sets LED colors on AEM-48A; see Section 5.15.2 Selecting LED Colors: ACM-48A & AEM-48A
SW28-6 SW28-7
SW28-8
Figure 5.18 Rotary Switches You can connect up to 32 devices (such as ACMs, LDMs, and AFMs) to the control panel using up to 32 unique addresses. Only one device per address can answer back.
Refer to your control panel documentation for valid addresses.
Using ACS and a UDACT on the Same Control Panel: The use of a UDACT Universal Alarm Communicator/Transmitter and an Annunciator Control System at the same annunciator address will alter the
ACS Manual P/N 15842:M 12/28/2006 41
0 1
0 1
Set the address with rotary switches SW27 and SW26 on the back of the annunciator. Turn the arrow with a small flat-head until it points to the correct digit.
SW27 Tens
SW26 Ones
J2
4
2 3
SW 26 ONE S
SW 27 TE NS
6
7 7 8
4
2 3
5 6
KE YLOCK
7 8
assignments of the trouble LEDs on ACS Points 3, 4, 5, 6, 7, and 8. Refer to the UDACT installation manual and the literature for the respective fire alarm control panel for further details.
42
For example, in a system with three channels and four speakers, where channel one has higher priority than channel two, which has higher priority than channel three, the system would be set up with one ACM-24AT board, and DIP SW32 on the ACM-24AT would be set as follows:
SW32-2 SW32-3 SW32-4 OFF ON OFF
Table 5.1
In this example, point mappings are as shown the 3 Switches per Group section of Table 5.3. If Switch 8 were pressed with no lit LEDs in the group, the output of Channel 2 would be directed to speaker circuit 3, and the point-active LED at switch P8 would flash. Configuring Switch Groups: Annunciator switches can be set in groups from one-point up to eight-points. If selecting 5-point or 7-point groups, note that there will be some unused switches; any unused points should be programmed as monitor points. Configure Speaker Control Mode with DIP switch SW32-2, SW32-3, and SW32-4 according to the point assignments shown in Table 5.2.
43
*Note: If adding an expander or expanders, the second unit starts at P25 and goes up, to a maximum of P96.
44
45
NOTE:The custom labels in this manual include labels that can be used with the various Speaker Control Mode settings.
*Note: If adding an expander or expanders, the second unit starts at P25 and goes up, to a maximum of P96.
46
4 5
6 7
47
NOTE:Switch locations are illustrated in Table 5.4. To set a DIP switch ON, push it towards the green circuit board.
Number of expanders installed None off off One on off Two off on Three on on
Figure 5.19 Using the Trouble Input on ACM-16AT and ACM-32A for Supervising Devices
ACSsuper.wmf
When not using the trouble input, jumper terminals TB1-6 and TB1-7 together. If an electrical short circuit (jumper) does not exist between terminals TB1-6 and TB1-7, the control panel will register a trouble condition.
1. Power up system according to your control panel instructions. 2. Set DIP switch SW32-1 to on to enter programming mode. 3. For each point, press the rubber switch to cycle red/green/yellow and select color that is appropriate for the points function (suggested: red for alarm, yellow for trouble, green for active). 4. Set DIP switch SW32-1 back to off to return to normal operation. 5. Hold down the Acknowledge/Lamp Test switch to do a lamp test and verify color selections were set correctly.
To locate these switches on the back of the annunciator, refer to Figure 5.1 and Figure 5.2. To set a DIP switch ON, push it towards the green circuit board.
49
Trouble LED Annunciator Points Annunciator Points Slide-in Labels Slide-in Labels ACM-24AT, AEM-24AT Annunciator Points
acm24-48-diagram.cdr
Point-Active LED
Pressing and quickly releasing this switch does not have a function on an expander.
50
NOTE:If annunciator is set for Flash-inhibit, this LED will be on steady for unacknowledged events.
NOTE:In Speaker Control Mode, this LED works differently; see Section 5.12.4.
51
anunc16.tif
ACM16AT Red
ACM16ATG Green
ACM16ATY Yellow
Yellow
Yellow
Yellow
52
6.2.2 AEM-16AT
Lamp Test Switch. When pressed, it lights all the LEDs on the AEM-16AT Series expander (except the On-line LED) and sounds the piezo for as long as the switch is held down. Inactive LEDs. These two LEDs are not functional on expander modules.
anunc16.tif
Point-Active LED. Flashes to indicate an active point; after being acknowledged it glows until reset. LED color varies by model number; see chart below. Trouble LED. Flashes to indicate a trouble situation. After being acknowledged it glows until reset. If communication with control panel is broken, all trouble LEDs flash. LED color varies by model number; see chart below. Control Switch. Functions as a local Lamp Test for the two LEDs dedicated to this point. Control switches can be used to execute such system functions as ACKNOWLEDGE, SIGNAL SILENCE, and SYSTEM RESET. Switches can also be used to control the states of various output circuits.
53
6.2.3 ACM-32A
Local Silence/Acknowledge Switch. Performs multiple functions: When pressed, it first lights all the LEDs on the ACM-32A Series control module (except the On-line LED) and then each expander. Piezo sounds for as long as the switch is held down. It acknowledges all status changes for both the annunciator and the expanders. Flashing LEDs will latch on solid and the piezo will be silenced.
anunc32.tif
On-line LED. Flashes green during communication with the control panel. System Trouble LED. Glows yellow for all trouble conditions in the system, including points or zones not mapped to the annunciator/expanders. Flashes if communication with control panel is broken. Point-Active LED. Flashes to indicate an active point; after being acknowledged it glows until reset. LED color varies by model number; see chart below.
ACM-32A Red
ACM-32AG Green
ACM-32AY Yellow
Note: Loss of communication with the control panel is monitored & reported by the ACM-32A. If connection between ACM-32A & AEM-32A fails, the ACM32A will show a trouble condition and the main control panel will show annunciator-point trouble.
54
6.2.4 AEM-32A
Lamp Test Switch. When pressed, it lights all the LEDs on the AEM-16AT Series expander (except the On-line LED) and sounds the piezo for as long as the switch is held down. Inactive LEDs. These two LEDs are not functional on expander modules.
anunc32.tif
Point-Active LED. Flashes to indicate an active point; after being acknowledged it glows until reset. LED color varies by model number; see chart below.
AEM-32A Red
AEM-32AG Green
AEM-32AY Yellow
Note: Loss of communication with the control panel is monitored & reported by the ACM-32A. If connection between ACM-32A & AEM-32A fails, the ACM-32A will show a trouble condition and the main control panel will show annunciatorpoint trouble.
55
A.1 Capabilities
The AFP-100 allows annunciators to be programmed by zone or by point. The EIA-485 interface will allow up to 32 annunciators with 64 points at an address, but two-way communications can occur with only one annunciator per address. The other devices must be configured as Receive Only. When the panel is programmed by zone, annunciator address 1 is available, and ACS annunciation displays the 56 software zones of the AFP-100. When the panel is programmed by point, 198 points are available. Annunciator addresses 1, 2, 3, and 4 can be used, but only address 1 is supervised. The furthest annunciator can be 6,000 feet from the fire alarm control panel (check power limitations).
CAUTION:ACS annunciators on the AFP-100 can not be used for manual control of control modules, bell circuits, or relays (except for global Silence and Drill switches).
See Section 4.3 EIA-485 Wiring Specifications for details and notes about EIA-485 requirements.
56
The power run to the annunciator need not TB4 on the AFP-100 contain a Power Supervision Relay because loss of power is inherently supervised through communication loss. This 24 VDC output is power-limited, filtered, and non-resettable.
Receive Only: Set this switch ON for each annunciator that will provide the same information as another annunciator in a different location. (When two or more annunciators hold the same address, all but one must be configured as Receive Only annunciators.) Piezo Disable: Set this switch ON to disable the piezo from sounding for any event. (The piezo will also be disabled if Flash Inhibit is ON.) Switch Inhibit: Set this switch ON to disable the point control switches on the annunciator and prevent them from executing system control functions. When inhibited, the switches will serve as local Lamp Test switches only. In addition, the Acknowledge/Lamp Test switch will function only in a local capacity unrecognized by the system. NOTE: Only the first four switches control the AFP-100. Their functions are: 1=Acknowledge 2=Signal Silence, 3=System Reset, 4=Drill. Flash Inhibit: Set this switch ON to disable the flashing of LEDs associated with unacknowledged events. Flash Inhibit also disables the piezo from sounding.
6 7
NOTE:For ACM-24AT and ACM-48A with AFP-100, set all pins on SW32 to OFF.
57
B.1 Capabilities
ACS annunciation displays the 99 software zones of the AFP-200, plus 8 system points, for a total point count of 107. Information is transmitted using only addresses 1 and 2. Up to 32 devices can be driven by the EIA485 communications output, using two unique addresses with 64 points at an address. Two-way communications can occur with only one annunciator per address; other devices on the same address must be configured as Receive Only. The furthest annunciator can be separated from the control panel by no more than 6,000 feet of wire (@16AWG); check specific current requirements for your system.
CAUTION:ACS annunciators on the AFP-200 can not be used for manual control of control modules, bell circuits, or relays (except for global Silence and Drill switches).
+ -
TB5
TB6
See Section 4.3 EIA-485 Wiring Specifications for details and notes about EIA-485 requirements.
58
acs200eia.cdr
+ acs200pwr.wmf
The power run to the annunciator need not TB1 on the AFP-200 contain a Power Supervision Relay because loss of power is inherently supervised through communication loss. This 24 VDC output is power-limited, filtered, and non-resettable.
Receive Only: Set this switch ON for each annunciator that will provide the same information as another annunciator in a different location. (When two or more annunciators hold the same address, all but one must be configured as Receive Only annunciators.) Piezo Disable: Set this switch ON to disable the piezo from sounding for any event. (The piezo will also be disabled if Flash Inhibit is ON.) Switch Inhibit: Set this switch ON to disable the point control switches on the annunciator and prevent them from executing system control functions. When inhibited, the switches will serve as local Lamp Test switches only. In addition, the Acknowledge/Lamp Test switch will function only in a local capacity unrecognized by the system. NOTE: Only the first four switches control the AFP-200. Their functions are: 1=Acknowledge 2=Signal Silence, 3=System Reset, 4=Drill. Flash Inhibit: Set this switch ON to disable the flashing of LEDs associated with unacknowledged events. Flash Inhibit also disables the piezo from sounding.
6 7
NOTE:For ACM-24AT and ACM-48A with AFP-200, set all pins on SW32 to OFF.
59
C.1 Capabilities
When installed with an AFP-300/AFP-400, ACS annunciators can be used to annunciate control panel status, addressable devices, panel modules, and software zones. The fire alarm control panel uses ACS Annunciator addresses 1 through 19 (1 through 10 when employing a UDACT). Up to 32 devices can be driven by the EIA-485 communications output, all addresses combined, with up to 64 points to an address. Two-way communications can occur with only one annunciator per address; other devices on the same address must be configured as Receive Only.
CAUTION:The panel annunciation points are divided into nine groups of 64 points. Each group can be assigned to one or more of the 19 annunciator addresses supported by the AFP-300/AFP-400. See the AFP-300/AFP-400 Programming Manual for assignment details.
TB4 on AFP-300/AFP-400
60
acs400eia.wmf
The power run to the annunciator need not contain a Power Supervision Relay because loss of power is inherently supervised through communication loss. This 24 VDC output is power-limited, filtered, and non-resettable.
61
Receive Only: Set this switch ON for each annunciator that will provide the same information as another annunciator in a different location. (When two or more annunciators hold the same address, all but one must be configured as Receive Only annunciators.) Piezo Disable: Set this switch ON to disable the piezo from sounding for any event. (The piezo will also be disabled if Flash Inhibit is ON.) Switch Inhibit: Set this switch ON to disable the point control switches on the annunciator and prevent them from executing system control functions. When inhibited, the switches will serve as local Lamp Test switches only. In addition, the Acknowledge/Lamp Test switch will function only in a local capacity unrecognized by the system. NOTE: Only the first four switches control the AFP-300/AFP-400. Their functions are: 1=Acknowledge 2=Signal Silence, 3=System Reset, 4=Drill. Flash Inhibit: Set this switch ON to disable the flashing of LEDs associated with unacknowledged events. Flash Inhibit also disables the piezo from sounding.
6 7
NOTE:See Section 5.12.1 DIP Switch Summary: ACM-24AT, ACM-48A and Section 5.12.4 Speaker Control Mode for details about SW32 on ACM-24AT and ACM-48A.
62
Annunciator Display
Control Panel Status and Zones 1-56 Zones 57-99, NAC Ckts 1-4 and 16 Special Zones Intelligent Modules 101 to 164 Intelligent Modules 201-264 (AFP-400 only) Intelligent Modules 165-196 and 265-296 (AFP-400 only) Detectors 101 to 164 on SLC loop 1 Detectors 201-264 on SLC loop 2 (AFP-400 only) Detectors 165-196 and 265-296 (AFP-400 only) Panel Output Circuit Modules (64 points) Programmable annunciator group A; requires VeriFire 400 software to program Programmable annunciator group B; requires VeriFire 400 software to program Annunciator Not Installed At Address
* or 0
Do not respond to any status change that is not within its ACS Selection Group. This includes system alarm or system trouble. Do mask status changes for point number 1 of the start address selection. Do not respond to System Reset, Acknowledge, or Alarm Silence. Do not use the battery saving feature (100 mA battery load)
63
D.1 Capabilities
When installed with an AM2020/AFP1010, annunciators can be programmed to annunciate the status of addressable devices, software zones, and several system control functions: Devices Photo, Ion, and Heat Intelligent Detectors Monitor and Control Modules Addressable Manual Pull Stations Refer to the appropriate FACP manuals for more information. Software Zones 1-240 System Controls Acknowledge/Step (the ACK/STEP key) Signal Silence System Reset Lamp Test XP Series Transponder System Power and Audio Supply Supervision XP Series Form-C Alarm and Trouble Relays Control, Monitor, and Relay Module Circuits
64
EIA-485 Circuit 2
+ -
P5 on AM2020 SIB-2048A/SIB-NET
See Section 4.3 EIA-485 Wiring Specifications for details and notes about EIA-485 requirements.
Note: 1. EIA-485 circuit rated 5.5 VDC max., 60 mA max. 2. If using the SIBs resistor switch, refer to the AM2020/AFP1010 manual.
acs2020eia.cdr
+ -
The AM2020/AFP101 0 must include an intelligent Serial Interface Board (SIB-2048A/SIBNET). Up to two EIA-485 circuit loops may be connected to the SIB as shown in the accompanying illustration.
65
+ TB2 TB3
TB3 on MPS-24A
The power run to the annunciator does not require a Power Supervision Relay. Loss of power is inherently supervised through a Communications loss. This 24 VDC output is supervised, power-limited, filtered, and non-resettable.
A(xx) P(yy)
Annunciator address In the range of 1-32, as set on the annunciators rotary decimal switches. Annunciator Points per Module
ACM-24AT, Points 1-24 First AEM-24AT, Points 2548 AEM-48A Points 4964 Second AEM-24AT, Points 4964 Note: Points 65-72 are not used
NOTE:When using the NCA to annunciate points on the AM2020/AFP1010 over the network, enable state reporting in the AM2020/AFP1010 panel for control module points and NONA/NOA module points; refer to the NCA Manual for instructions. 66 ACS Manual P/N 15842:M 12/28/2006
acs2020pwr.cdr
4 5
6 7
NOTE:See Section 5.12.1 DIP Switch Summary: ACM-24AT, ACM-48A and Section 5.12.4 Speaker Control Mode for details about SW32 on ACM-24AT and ACM-48A.
67
the DIP switches on the annunciator must be set as follows. The switch numbers given below are for SW28 on the ACM-24AT, and for the 8-pin DIP switch on the ACM-16AT and ACM-32A.
Switch # 1 2, 3 ACM-24AT and ACM-48A ACM-16AT and ACM-32A Function Manual override: Set switch OFF for this application. Expanders installed: Set these switches according to how many expanders are installed at the address. See Section 5.12.3 Configuring Number of Expander Modules for ACM-24AT/ACM-48A; see Section 5.13.3 Configuring Number of Expander Modules for ACM-16AT/ACM-32A. Not used; set to OFF Receive Only: Set switch accordingly Piezo Disable: When the annunciator and AMG-1 are not located adjacent to the AM2020/AFP1010, as in this application, the piezo must sound and the switch must be set to OFF. Switch Inhibit: Set this switch ON to disable the point control switches on the annunciator and prevent them from executing system control functions. When inhibited, the switches will serve as local Lamp Test switches only. In addition, the Acknowledge/Lamp Test switch will function only in a local capacity unrecognized by the system. Flash Inhibit: Set switch to the OFF position for this application. Eight-Point Shift: Set to OFF.
4 5 6
This remote annunciator must be programmed to annunciate the status of all points in the system, either by device/module, or by grouping points into software zones and annunciating the status of those zones. Every point in the system must be represented by at least one annunciator point at each remote location.
NOTE:More than one monitor-type device may be programmed to a single annunciator point. This multiple-mapping of initiating devices will operate the point active and trouble LEDs of an annunciator point with Boolean OR functionality.
68
Dip Switch
Switch # 1 2, 3 ACM-24AT Function ACM-16AT Function Manual override: Set switch OFF for this application Expanders installed: Set these switches according to how many expanders are installed at the address. See Section 5.12.3 Configuring Number of Expander Modules for ACM-24AT/ACM-48A; see Section 5.13.3 Configuring Number of Expander Modules for ACM-16AT/ACM-32A. Not used; set to OFF Eight-Point Shift: Set to OFF. Receive Only: Set switch OFF for this application. Piezo Disable: Set this switch ON for this application unless the annunciator and AMG-1 are not located adjacent to the AM2020/AFP1010. In that case, the piezo must sound and the switch must be set to OFF. Switch Inhibit: Set this switchOFF for this application. Flash Inhibit: Set this switch ON for this application.
4 5 6
7 8
When configured as outlined in Speaker and Telephone Mode, the ACM24AT or ACM-16AT will function as follows: All new conditions (except telephone call-in) The piezo will not sound and LEDs will not flash. Telephone call-in: The piezo will sound and both the point active and trouble LEDs for the respective telephone point will flash. Pressing the telephone point switch on the ACM-24AT or ACM-16AT will silence the piezo and illuminate LEDs steadily. The AM2020/AFP1010 will indicate telephone circuit connection by turning off the trouble LED.
CAUTION:The AM2020/AFP1010 Control-By-Event will not override the manual control setting of the ACM-24AT or ACM-16AT module. To return the annunciator to Automatic Mode, press the Manual Override switch again (toggle action). Set the DIP switches on a Manual Override annunciator as follows.The switch numbers given below are for SW28 on the ACM-24AT, and for the 8-pin DIP switch on the ACM-16AT.
Dip Switch:
Switch # 1 2, 3 ACM-24AT Function Manual override: Set ON for this application. Expanders installed: Set these switches according to how many expanders are installed at the address. See Section 5.12.3 Configuring Number of Expander Modules for ACM-24AT/ACM-48A; see Section 5.13.3 Configuring Number of Expander Modules for ACM-16AT/ACM-32A. Not used; set to OFF Eight-Point Shift: Set to OFF. Receive Only: Set this switch OFF for this application. Piezo Disable: Set this switch ON for this application unless the annunciator and AMG-1 are not located adjacent to the AM2020/AFP1010. In that case, the piezo must sound and the switch must be set to OFF. Switch Inhibit: Set this switch OFF for this application. Flash Inhibit: Set this switch OFF for this application. ACM-16AT Function
4 5 6
7 8
70
Point Type
Not used
Indicates alarm status of detector Indicates active status of software zone Indicates System Alarm Not used
Not used
Not used
ACK/STEP 1
Indicates System Trouble Indicates Signals Silence Indicates System Trouble Not used
ACK/STEP key
71
NOTE:Control Switches marked not used will still function as local LAMP TEST switches for their respective LEDs.
1. In older systems, if the monitor module or XPM-8 circuit is programmed as a supervisory point (SPSU), illumination of the trouble LED will occur for both trouble and supervisory conditions. The exact status of the point (trouble versus supervisory condition) can be read at the AM2020/AFP1010 control panel. Prior to software release M2.8, supervisory points do not activate the point active LEDs of an annunciator. 2. With the AM2020/AFP1010, the functions of ACK/STEP, SIGNAL SILENCE, SYSTEM RESET and LAMP TEST may be assigned (mapped) to multiple annunciator points.
72
Appendix E: NFS2-640 (UL 9th), NFS320 (UL 9th) and NFS-640 Systems (UL 8th)
!
WARNING: NFS-640 has not been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864 9th Edition. Operation of this product with products tested for UL 864 9th Edition has not been evaluated and may not comply with NFPA 72 and/or the latest edition of UL 864. These applications will require the approval of the local Authority Having Jurisdiction (AHJ). WARNING: NFS-320 and NFS2-640 have been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864 9th Edition. Operation of these products with products not tested for UL 864 9th Edition has not been evaluated and may not comply with NFPA 72 and/or the latest edition of UL 864. These applications will require the approval of the local Authority Having Jurisdiction (AHJ).
E.1 Capabilities
ACS annunciators communicate with the control panel on the ACS Mode interface: TB11 on the CPU-320 or CPU2-640, TB13 on the CPU-640. The ACS Mode interface can annunciate control panel, zone, detector, module, and circuit status. The 832 panel annunciation points are divided into 13 fixed ACS Selection Groups (labeled A to M) of 64 points; these are detailed in the panel's programming guide (see Section 1.3 Related Documentation for part numbers). There are also ten programmable annunciator groups which are programmed using VeriFire Tools software. You can assign each ACS Selection Group to one or more of the 32 annunciator addresses supported by the control panel. This fire alarm control panel can use ACS annunciator addresses 132 without a UDACT and ACS annunciator addresses 119 with a UDACT. Up to 32 devices can be driven by the EIA-485 communications output, all addresses combined. Two-way communications can occur with only one annunciator per address; other devices on the same address must be configured as Receive Only. Use the ACS Mode Interface to remotely use control panel functions (Acknowledge, Alarm Silence, Alarm Activate, and System Reset) from a remote location. The ACS Mode interface can also activate NACs, panel circuits, and control modules from remote locations.
73
NFS2-640 (UL 9th), NFS-320 (UL 9th) and NFS-640 Systems (UL 8th)
TB10 CPU2-640/CPU-320
TB11
For more information on annunciator operation and FACP programming under various specific applications, refer to the NFS2-640 and NFS-320 documents referenced in Section 1.3, Related Documentation, on page 10.
See Section 4.3 EIA-485 Wiring Specifications for details and notes about EIA-485 requirements.
TB13 on NFS-640
TB7 on NFS-640
74
acs640pwr.wmf
Configuring Annunciators for NFS-320, NFS2-640, and NFS-640NFS2-640 (UL 9th), NFS-320
The power run to the annunciator does not require a Power Supervision Relay. Loss of power is inherently supervised through a Communications loss. This 24 VDC output is supervised, power-limited, filtered, and nonresettable.
Receive Only: Set this switch ON for each annunciator that will provide the same information as another annunciator in a different location. (When two or more annunciators hold the same address, all but one must be configured as Receive Only annunciators.) Piezo Disable: Set this switch ON to disable the piezo from sounding for any event. (The piezo will also be disabled if Flash Inhibit is ON.) Switch Inhibit: Set this switch ON to disable the point control switches on the annunciator and prevent them from executing system control functions. When inhibited, the switches will serve as local Lamp Test switches only. In addition, the Acknowledge/Lamp Test switch will function only in a local capacity unrecognized by the system. NOTE: Only the first four switches control the NFS-640. Their functions are: 1=Acknowledge 2=Signal Silence, 3=System Reset, 4=Drill. Flash Inhibit: Set this switch ON to disable the flashing of LEDs associated with unacknowledged events. Flash Inhibit also disables the piezo from sounding.
6 7
NOTE:See Section 5.12.1 DIP Switch Summary: ACM-24AT, ACM-48A and Section 5.12.4 Speaker Control Mode for details about SW32 on ACM-24AT and ACM-48A.
75
NFS2-640 (UL 9th), NFS-320 (UL 9th) and NFS-640 Systems (UL 8th)
This fire alarm control panel's Programming Manual provides a complete listing of the points within the ACS Selection Groups and instructions on programming the panel for addressable annunciators.
ACS Selection Group A B C D E F G H I J K L M 1 2 3 4 5 6 7 8 9 0 Annunciator Display 8 Systems points + Zones 1-56 Zones 57-99, 8 F zones, 4 NAC Loop 1, Modules 1-64 Loop 2, Modules 1-64 Loop 1, Modules 65-128 Loop 2, Modules 65-128 Loop 1 - Modules 129-159, 2 unused points Loop 2 - Modules 129-159, 2 unused points Loop 1, Detectors 1-64 Loop 2, Detectors 1-64 Loop 1, Detectors 65-128 Loop 2, Detectors 65-128 Loop 1 - Detectors 129-159, 2 unused points Loop 2 - Detectors 129-159, 2 unused points Panel circuits 1-1 to 8-8 (64) Programmable Annunciator Group #1 * Programmable Annunciator Group #2 * Programmable Annunciator Group #3 * Programmable Annunciator Group #4 * Programmable Annunciator Group #5 * Programmable Annunciator Group #6 * Programmable Annunciator Group #7 * Programmable Annunciator Group #8 * Programmable Annunciator Group #9 * Programmable Annunciator Group #10 *
Do not respond to any status change, including system alarm or system trouble, that is not within its ACS Selection Group. Do mask status changes for point number 1 of the start address selection. Do not respond to System Reset, Acknowledge, or Alarm Silence. Do not use the battery saving feature (100 mA battery load).
76
Appendix F: System 500 Systems: ACM-16AT and ACM-32A Only (UL 8th)
!
WARNING: System 500 has not been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864 9th Edition. Operation of this product with products tested for UL 864 9th Edition has not been evaluated and may not comply with NFPA 72 and/or the latest edition of UL 864. These applications will require the approval of the local Authority Having Jurisdiction (AHJ).
F.1 Capabilities
When installed with a System 500, ACM-16AT, ACM-32A and expanders can annunciate the status of initiating and notification circuits, relays, and several system control functions. Up to 32 devices can be connected to the EIA-485 communications output, all addresses combined, with up to 64 points to an address. Two-way communications can occur with only one annunciator set to address 1; other devices must be configured as Receive Only. Check battery calculation tables for power limitations. Each annunciator LED is automatically assigned to one and only one system point: Circuits IZ-4/IZ-4A/IZ-8 Initiating Device Circuits (alarm and trouble) IC-4/ICE-4/ICR-4L Notification Appliance Circuits (activation and trouble) CR-4/CRE-4/CR-4L Control Relays (activation and trouble) TC-2/TC-4 circuits (activation and trouble) System Controls Acknowledge Signal Silence System Reset Activate Notification Circuits 1 and 2, the Remote Signalling Municipal Tie circuit, and the Alarm Relay.
77
Power-limited and supervised. 6,000 feet maximum distance (@16 AWG) between the control panel and the furthest annunciator. Use twisted pair cable with a characteristic impedance of approximately 120 ohms. EIA-485 circuit rated 5.5 VDC max., 60 mA max.
NOTE:System Trouble and Module Failure will also occur if the normally closed supervisory path between TB1 Terminals 6 and 7 on the annunciator is opened (or the jumper has not been installed).
WARNING: Cut JP1 to make this circuit non-resettable. Do not use this connection to simultaneously power four-wire detectors and annunciators. See the System 500 Manual for location of JP1.
No more than 200 mA current can be drawn from these power-limited terminals in standby or alarm. The power run to the annunciator does not require a Power Supervision Relay because loss of power is inherently supervised through a Communications loss. This 24 VDC output is filtered, regulated, powerlimited, and non-resettable.
78
Configuring the ACS for System 500System 500 Systems: ACM-16AT and ACM-32A Only (UL
When not using the trouble input on annunciator or expander, jumper terminals TB1-6 and TB1- 7 together.
( - ) Common TB2-2
Mps24b_Inver.cdr
6 7
CB1 TB1
EARTH AC NEUT
AC HO T
R55 1 2 3 4 6 7 8
P2
TB2
+ 24 VRES ET
CO MM ON +24 VP OW ER CO MM ON
BATT +
B ATT -
TB3
P3
ACM-16AT & AEM-16AT Circuit Type ACM-32A & AEM-32A Red LED IZ-4, IZ-4A, IZ-8, IZ8CS, IZ-8CS4 circuit IC-4/ICE-4, ICR-4L circuit CR-4/CRE-4, CR-4L circuit TC-2, TC-4 circuit Indicates alarm status of circuit3 Indicates Activation Yellow LED Indicates trouble status of circuit Indicates trouble status of circuit Indicates trouble status of relay Indicates trouble status of relay Indicates System Trouble Control Switch2 Not used
Indicates Activation
Indicates Activation
Indicates that signals SIGNAL SILENCE have been silenced Not used Indicates Supervisory condition Indicates trouble status of circuit SYSTEM RESET Not used
Annunciator Point #5
Indicates that Notification Circuit #1 has been activated Indicates that Notification Circuit #2 has been activated Indicates that Remote Signalling Municipal Tie has been activated
Controls Notification Circuit #1 Controls Notification Circuit #2 Controls Remote Signalling Municipal Tie Controls Alarm Relay
Annunciator Point #6
Annunciator Point #7
Annunciator Point #8
80
NOTE:Control Switches marked not used will still function as local LAMP TEST or local ACKNOWLEDGE switches for their respective points.
1. If the Eight-Point Shift (DIP switch # 4) is set ON, the eight control panel functions will be shifted out of annunciator points 1 through 8. Those eight points will annunciate the first module. 2. These control switches are active only if all of these conditions are set: Receive Only (DIP Switch # 5) is set to OFF. Switch Inhibit (DIP Switch # 7) is set to OFF. 3. With Software P/N #S500R4.0 or higher installed in the System 500, the manner in which IZ-8, IZ-8CS, and IZ-8CS4 circuits programmed as supervisory are annunciated depends upon whether Mode 1 or Mode 2 is selected. 4. ICR-4L and CR-4L circuits are annunciated as points 41-44 when installed behind the middle module or points 49-52 when installed behind the right-hand side module. 5. Annunciator Point #7 yellow LED indicates Municipal Tie Trouble if no UDACT is installed. It will annunciate Low Battery Ground Fault if a UDACT is installed in the system.
81
Appendix G: System 5000 Systems: ACM-16AT and ACM-32A Only (UL 8th)
!
WARNING: System 5000 has not been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864 9th Edition. Operation of this product with products tested for UL 864 9th Edition has not been evaluated and may not comply with NFPA 72 and/or the latest edition of UL 864. These applications will require the approval of the local Authority Having Jurisdiction (AHJ).
G.1 Capabilities
When installed with a System 5000, the ACS can annunciate the status of initiating and notification circuits, relays, and several system control functions. Each annunciator LED is automatically assigned to one and only one system point. Circuits IZM-8 Initiating Device Circuits (alarm and trouble) ICM-4/ICE-4 Notification Appliance Circuits (trouble)* CRM-4/CRE-4 Control Relays (trouble)* TCM-2 circuits (trouble)* TCM-4 circuits (trouble)* VCM-4/DCM-4 circuits (trouble)* AIM-200 zones (alarm and trouble) *Indication of output circuit activation can be obtained by programming the control panel for OUTPUT STATUS. System Controls Acknowledge Signal Silence System Reset Activate Notification Circuits 1 and 2, the Remote Signalling Municipal Tie circuit, and the Alarm Relay.
82
Providing Power to Annunciators System 5000 Systems: ACM-16AT and ACM-32A Only (UL
the system must be operating under control panel software with U4 ROM part number 73085 or higher. Loss of communication results in System Trouble and Module Failure indications at the control panel.
NOTE:System Trouble and Module Failure will also occur if the normally closed supervisory path between TB1 Terminals 6 and 7 on the annunciator is opened (or the jumper has not been installed).
The EIA-485 circuit that drives the annunciator must be power-limited and connected as illustrated in Figure G.1.
EIA-485 (-) (+) EIA-485
CPU-5000.TIF
TB2 on CPU-5000
Power-limited and supervised. 6,000 feet maximum distance (@16 AWG) between the control panel and the furthest annunciator. Use twisted pair cable with a characteristic impedance of approximately 120 ohms. EIA-485 circuit rated 5.5 VDC max., 60 mA max.
+ TB2 TB3
MPS-24B Main Power Supply. Cut JP1 on MPS-24B to make the circuit non-resettable and connect the power run for the ACS to MPS24B TB2 Terminals 1 (+) and 2 (-) as shown in the accompanying illustration (filtered, power-limited, 200 milliamps max).
ACS Manual P/N 15842:M 12/28/2006
24 VDC
+ TB2 TB3
acs5000pwr.cdr
83
WARNING: Cut JP1 on MPS-24B to make this circuit nonresettable. Do not use this connection to simultaneously power four-wire detectors and annunciators. See the System 5000 Manual for location of JP1.
Points 97-128, annunciated by either the second and third expanders of the second ACM-16AT, or by an AEM-32A.
CPU-5000
NOTE:Without invoking the Eight-Point-Shift, the first eight points would be dedicated to control panel functions, not circuits of the first module. (See Configuring the ACS for This Control Panel.)
84
Configuring the ACS for System 5000 System 5000 Systems: ACM-16AT and ACM-32A Only
6 7
ACM-16AT & AEM-16AT Circuit Type ACM-32A & AEM-32A Red LED ICM-4/ICE-4 circuit Indicates Activation3 Yellow LED Indicates trouble status of circuit Indicates trouble status of relay Indicates trouble status of relay Indicates trouble status of circuit Indicates System Trouble Indicates signals have been silenced Not used Control Switch2 Controls Notification Circuit4 Controls Relays4 Remote Switch Functions4 Not used ACKNOWLEDGE SIGNAL SILENCE SYSTEM RESET
CRM-4/CRE-4 circuit
Indicates Activation3
TCM-2, TCM-4 Indicates Activation3 VCM-4, DCM-4 circuit AIM-200 zone5 Indicates alarm status of circuit 1 Indicates Annunciator Point #1 System Alarm Annunciator Point #2 Annunciator Point #3 Annunciator Point #4 Annunciator Point #5 Not used Not used Not used
Indicates Supervisory Not used condition Controls Notification Circuit #1 Controls Notification Circuit 2 Controls Remote Signalling Municipal Tie Controls Alarm Relay
Indicates that Indicates trouble Notification Circuit 1 has status of circuit been activated Indicates that Notification Circuit 2 has been activated Indicates that the Remote Signalling to Municipal Tie has been activated Indicates trouble status of circuit Indicates trouble status of circuit7
Annunciator Point #6
Annunciator Point #7
Annunciator Point #8
Indicates that the Alarm Indicates AC Fail Relay has been activated
2.
3. 86
AIM-200 Point Annunciation System 5000 Systems: ACM-16AT and ACM-32A Only (UL 8th) 4. 5. 6. These control switches require that the system be programmed for Output Control. The ACS annunciates the eight AIM-200 software zones only, except as described below. With Software P/N#S5000R7.0 or higher installed in the System 5000, the manner in which IZM-8 circuits programmed as supervisory are annunciated depends upon whether Mode 1 or Mode 2 is selected. Annunciator Point #7 yellow LED indicates Municipal Tie Trouble if no UDACT is installed. It will annunciate Low Battery/Ground Fault if a UDACT is installed in the system.
7.
Annunciator Address 1
8 control panel points (control panel point shift not an option). 8 unusable points (redundant AIM-200 points). 48 points mapped to the next six modules installed in the System (which can also be AIM-200s for annunciation of their eight software zones).
Annunciator Address 2
Intelligent Detectors, addressed 1-64, on the AIM-200 installed next to the control panel.
Annunciator Address 3
Addressable Modules, addressed 1-64, on the AIM-200 installed next to the control panel.
ACS Manual P/N 15842:M 12/28/2006 87
aim200point.cdr
System 5000 Systems: ACM-16AT and ACM-32A Only (UL 8th) AIM-200 Point Annunciation
Annunciator Address 4
Intelligent Detectors, addressed 65-96, followed by Addressable Modules, addressed 65-96, on the AIM-200 installed next to the control panel. The control panels programming manual provides programming instructions for this option. Refer to program choice AIM(256).
NOTE:AIM-200 detector and module addresses 97, 98, and 99 may be used, but cannot be point-annunciated.
88
89
For NCA-2 connections, see Appendix J, NFS-3030 Systems (UL 8th), NFS2-3030 Systems (UL 9th), and NCA-2 Systems (UL 9th), on page 93.
I.1 Capabilities
ACS annunciators communicate with the control panel on the ACS Mode interface (TB3 on the NCA). Annunciators can be programmed to annunciate the status of addressable devices, software zones, system control functions or shadowing ACS points mapped to an AM2020/AFP1010. The NCA supports up to 96 points per annunciator address. The ACS devices can be programmed as either 64 or 96 points depending on which ACS series is being used. Up to 32 devices can be driven by the EIA-485 communications output, all addresses combined. Two-way communications can occur with only one annunciator per address; other devices on the same address must be configured as Receive Only.
TB3 on NCA
TB1 on NCA
90
acsNCApwr.cdr
EARTH
+ + +
COMMON
+24V POWER
+
+
EIA-485 wiring is connected to TB3 of the NCA (ACS Mode interface) as shown in the accompanying illustration. See Section 4.3 EIA-485 Wiring Specifications for details and notes about EIA-485 requirements.
acsNCAeia.cdr
annunciators may also be powered directly from the power supply that is powering the NCA, using the power-limited non-resettable 24VDC terminal. (See the NCA Manual for details.) The power run to the annunciator does not require a Power Supervision Relay. Loss of power is inherently supervised through a Communications loss. This 24 VDC output is supervised, power-limited, filtered, and nonresettable.
A(xx) P(yy)
Annunciator address In the range of 1-32, as set on the annunciators rotary decimal switches. Annunciator Points per Module
ACM-24AT, Points 1-24 First AEM-24AT, Points 25-48 AEM-48A, Points 49-96* Second AEM-24AT, Points 49-72* Third AEM-24AT, Points 73-96*
*Note: Points 65-96 are not used unless ACS device is programmed for 96 points. First Second Third ACM-16AT, AEM-16AT, AEM-16AT, AEM-16AT, Points 1-16 Points 17-32 Points 33-48 Points 49-64 ACM-32A, Points 1-32 AEM-32A, Points 33-64
NOTE:When using the NCA to annunciate points on the AM2020/AFP1010 over the network, enable state reporting in the AM2020/AFP1010 panel for control module points and NONA/NOA module points; refer to the NCA Manual for instructions.
91
4 5
6 7
NOTE:See Section 5.12.1 DIP Switch Summary: ACM-24AT, ACM-48A and Section 5.12.4 Speaker Control Mode for details about SW32 on ACM-24AT and ACM-48A.
92
Appendix J: NFS-3030 Systems (UL 8th), NFS2-3030 Systems (UL 9th), and NCA-2 Systems (UL 9th)
!
WARNING: NFS-3030 has not been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864 9th Edition. Operation of this product with products tested for UL 864 9th Edition has not been evaluated and may not comply with NFPA 72 and/or the latest edition of UL 864. These applications will require the approval of the local Authority Having Jurisdiction (AHJ). WARNING: NFS2-3030 and NCA-2 have been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864 9th Edition. Operation of these products with products not tested for UL 864 9th Edition has not been evaluated and may not comply with NFPA 72 and/or the latest edition of UL 864. These applications will require the approval of the local Authority Having Jurisdiction (AHJ).
For NCA connections, see Appendix I, NCA Systems (UL 8th), on page 90.
J.1 Capabilities
When installed with NFS-3030/NFS2-3030 or NCA-2, annunciators can be programmed to annunciate the status of addressable devices, general zones, logic zones, and several system control functions: Devices Intelligent Detectors Monitor and Control Modules Addressable Manual Pull Stations Wireless Devices Panel Circuit Modules (NFS-3030 only)
NOTE:Refer to the appropriate FACP manuals for more information.
Zones Logic Zones System Controls Acknowledge Signal Silence System Reset
ACS Manual P/N 15842:M 12/28/2006 93
NFS-3030 Systems (UL 8th), NFS2-3030 Systems (UL 9th), and NCA-2 Systems (UL 9th)
Lamp Test Drill Disable Monitor Control Telephone XP Series Transponder System Power and Audio Supply Supervision XP Series Form-C Alarm and Trouble Relays Control, Monitor, and Relay Module Circuits
94
3030-acs-TB7.wmf
A(xx) P(yy)
Annunciator address In the range of 1-32, as set on the annunciators rotary decimal switches.
95
NFS-3030 Systems (UL 8th), NFS2-3030 Systems (UL 9th), and NCA-2 Systems (UL 9th)
4 5
6 7
NOTE:See Section 5.12.1 DIP Switch Summary: ACM-24AT, ACM-48A and Section 5.12.4 Speaker Control Mode for details about SW32 on ACM-24AT and ACM-48A.
96
NFS-3030
4 5 6 7
This remote annunciator must be programmed to annunciate the status of all points in the system, either by device/module, or by grouping points into logic zones and annunciating the status of those zones. Every point in the system must be represented by at least one annunciator point at each remote location.
NOTE:More than one monitor-type device may be programmed to a single annunciator point. This multiple-mapping of initiating devices will operate the point active and trouble LEDs of an annunciator point with Boolean OR functionality.
97
NFS-3030 Systems (UL 8th), NFS2-3030 Systems (UL 9th), and NCA-2 Systems (UL 9th)
Dip Switch
Switch # 1 2, 3 ACM-24AT Function ACM-16AT Function Manual override: Set switch OFF for this application Expanders installed: Set these switches according to how many expanders are installed at the address. See Section 5.12.3 Configuring Number of Expander Modules for ACM-24AT/ACM-48A; see Section 5.13.3 Configuring Number of Expander Modules for ACM-16AT/ACM-32A. Not used; set to OFF Eight-Point Shift: Set to OFF. Receive Only: Set switch OFF for this application. Piezo Disable: Set this switch ON for this application unless the annunciator and AMG-1 are not located adjacent to the NFS-3030/NFS23030/NCA-2. In that case, the piezo must sound and the switch must be set to OFF. Switch Inhibit: Set this switchOFF for this application. Flash Inhibit: Set this switch ON for this application.
4 5 6
7 8
When configured as outlined in Speaker and Telephone Mode, the ACM-24AT or ACM-16AT will function as follows: All new conditions (except telephone call-in) The piezo will not sound and LEDs will not flash. Telephone call-in: The piezo will sound and both the point active and trouble LEDs for the respective telephone point will flash. Pressing the telephone point switch on the ACM-24AT or ACM-16AT will silence the piezo and illuminate LEDs steadily. The NFS-3030/NFS23030/NCA-2 will indicate telephone circuit connection by turning off the trouble LED.
The state of the each annunciator point will remain the same as before. The output circuits can now be controlled via their point switches.
CAUTION:The NFS-3030/NFS2-3030/NCA-2 Control-By-Event will not override the manual control setting of the ACM-24AT or ACM-16AT module. To return the annunciator to Automatic Mode, press the Manual Override switch again (toggle action). Set the DIP switches on a Manual Override annunciator as follows.The switch numbers given below are for SW28 on the ACM-24AT, and for the 8-pin DIP switch on the ACM-16AT.
Dip Switch:
Switch # 1 2, 3 ACM-24AT Function Manual override: Set ON for this application. Expanders installed: Set these switches according to how many expanders are installed at the address. See Section 5.12.3 Configuring Number of Expander Modules for ACM-24AT/ACM-48A; see Section 5.13.3 Configuring Number of Expander Modules for ACM-16AT/ACM-32A. Not used; set to OFF Eight-Point Shift: Set to OFF. Receive Only: Set this switch OFF for this application. Piezo Disable: Set this switch accordingly. Switch Inhibit: Set this switch OFF for this application. Flash Inhibit: Set this switch OFF for this application. ACM-16AT Function
4 5 6 7 8
99
NFS-3030 Systems (UL 8th), NFS2-3030 Systems (UL 9th), and NCA-2 Systems (UL 9th)
ACM-24AT or ACM-16AT Module and AEM-24AT or AEM-16AT Expanders Point Type ACM-48A or ACM-32A Module & AEM-48A or AEM-32A Expander Active LED Control Module XPC Circuit XPR Circuit XPIQ Speaker and Telephone/Strobe Circuits XP5-C Circuit Monitor Module XPM Circuit Intelligent Detector Logic Zone Trouble LED Control Switch Indicates on/off Indicates trouble Turns module on/off status of module or status of module or circuit circuit
Indicates trouble Not used Indicates alarm status of module or status of module or circuit circuit Indicates alarm status of detector Indicates active status of logic zone Indicates System Alarm Not used Not used Not used Indicates trouble status of detector Not used Not used Not used
Indicates System Trouble Indicates Signals Silence Not used Not used
ACKNOWLEDGE key SIGNAL SILENCE key SYSTEM RESET key LAMP TEST key
* NOTE:With the NFS-3030/NFS2-3030/NCA-2, the functions of ACKNOWLEDGE, SIGNAL SILENCE, SYSTEM RESET and LAMP TEST may be assigned (mapped) to multiple annunciator points.
100
Notes
101
Notes
102
Index
A
ABF, ABS see Backboxes ABM-1 22 ACM-16AT 13, 31, 32, 48 Addressing 47 Color variations 16 DIP switches 47 Expanders 33, 34, 35 Keypad switches 52 LEDs 52 Supervising devices 48 ACM-24AT 13, 15, 31 Addressing 40, 41 DIP switches 40, 42, 49 Expanders 33, 34, 35 Keypad switches LEDs 48 Speaker Control Mode 42 ACM-32A 13, 18, 31, 32, 48 Addressing 47 DIP switches 47 Expanders 33, 34, 35 Keypad switches 54, 55 LEDs 54 Supervising devices 48 ACM-48A 13, 16, 31 Addressing 40, 41 DIP switches 40, 49 Expanders 33, 34, 35 Keypad switches LEDs 49 Addressing ACM-16AT, ACM-32A 47 ACM-24AT 41 ACM-48A 41 Switch locations 31 System 5000 84 Adhesive label 39 ADP-4B 21 AEM-16AT 13, 17 Keypad switches 53 LEDs 53 AEM-24AT 13, 15 DIP switches 49 LEDs 48 AEM-32A 13, 18 LEDs 55
ACS Manual P/N 15842:M 12/28/2006
AEM-48A 13, 16 DIP switches 49 LEDs 49 AFC-600 Discontinued AFP-100 13 DIP switches 57 Power connections 57 AFP1010, see AM2020/AFP1010 AFP-200 13 DIP switches 59, 62 Power connections 59 UDACT 47 AFP-300/AFP-400 13 DIP switches 62 Power connections 61 Speaker Control Mode 42 AFP-400 see AFP-300/AFP-400 AIM-200 87 AKS-1B, see Key switch AM2020 software requirements 65 AM2020/AFP1010 13, 25 Applications 67 Cabinet mounting 27 Common system annunciation 67 DIP switches 67, 69, 70, 98 Manual override 69, 98 Power connections 66 Speaker and Telephone Mode 68 Speaker Control Mode 42 Annunciator key switch, see Key switch Annunciator phone jack see Phone jack Audio functions AM2020/AFP1010 68 NFS2-3030 97 NFS-3030 97
B
Backboxes 19, 20, 27, 33 Sizes 20 Battery calculations 28, 29 BMP-1 22 Burglary systems 89
C
Cabinet mounting 27, 33 Cabinets see Backboxes, or Doors Canada, National Standard of 11 Common system annunciation AM2020/AFP1010 67
103
DL
Index
NFS-3030 96 Compatible panels 12 Configuring the ACS AFP-100 57 AFP-200 59, 62 AFP-300/AFP-400 62 AM2020/AFP1010 67 DIP switch locations 31 NCA 92 NFS-3030 96 NFS-640 75 System 500 79 System 5000 85 Connecting Expanders 33, 34, 35 Control switch 85 Functions 51, 52, 53 System 5000 85 Control switches System 500 80 Current draw calculations 29 Custom display labels 39
AFP-300/AFP-400 60 AM2020/AFP1010 65 NFS2-640 74 NFS-3030 94 NFS-320 74 NFS-640 74, 90 Shielding the circuit 36 System 500 (ACM-16AT, ACM32A only) 78 System 5000 (ACM-16AT, ACM32A only) 82 Eight-point shift 47 System 500 79, 81 System 5000 84, 85, 86 Electrical ratings 28 End of line resistor 37, 40 Expanders 33, 34, 35
F
Fire/burglary systems 89
G
Ground 37
D
DIP switches ACM-16AT, ACM-32A 32, 47 ACM-24AT 42, 49 ACM-48A, AEM-48A 49 AEM-24AT 49 AFP-100 57 AFP-200 59, 62 AFP-300/AFP-400 62 AM2020/AFP1010 67, 68, 69, 70,
I
Installation Checklist 30 Installation procedures 30 Installing Modules in System 5000 84 Installing modules in System 5000 84
K
Key switch 39, 40 Key switch connector 32 keylock connector 40 Keypad switches AM2020/AFP1010 70 NFS-3030 100
98
Configuring number of expander modules 42, 47 NCA 92 NFS2-3030 97 NFS-3030 96, 97, 99 NFS-640 75 System 500 79 System 5000 85 with AM2020/AFP1010 67 with NFS-3030 96 DP-DISP 21 Dress plates 22, 34, 39
L
Labeling 39 Lamp test switch 53, 55 LEDs 49 AM2020/AFP1010 70 Color-programmable 48, 49 Inactive 53, 55 NFS-3030 100 Point-active 51, 52, 53, 54, 55 System 500 80 System 5000 85 System Trouble 50, 51, 52, 54 Trouble 51, 52, 53 Local silence/acknowledge switch 52, 54 see also Acknowledge/Lamp Test switch
ACS Manual P/N 15842:M 12/28/2006
E
Earth ground 37 EIA-485 24, 25, 35, 36, 37 AFP-100 56 AFP-200 58
104
Index
MS
M
Manual override 50, 52, 67, 69, 96, 98 Mounting 33 multiple power supplies 27 multi-speakers 42
N
NCA 90 DIP switches 92 Speaker Control Mode 42 NCA-2 90 Speaker Control Mode 42 NFS2-3030 13, 93 Speaker and Telephone Mode 97 Speaker Control Mode 42 NFS-3030 13, 93 Applications 96 Common system annunciation 96 DIP switches 96, 99 Power connections 94 Speaker and Telephone Mode 97 Speaker Control Mode 42 NFS-640 13, 73 DIP switches 75 Selection groups 75 Speaker Control Mode 42
Point mapping 44, 45, 46 AFP-300/AFP-400 63 Point-active LEDs see LEDs Power connections 37, 38 AFP-100 57 AFP-200 59 AFP-300/AFP-400 61 AM2020/AFP1010 66 NFS-3030 94 NFS-640 74, 90 System 500 78 System 5000 83 Power Requirements 28 Program mapping AM2020/AFP1010 70 NFS2-3030 100 NFS-3030 99, 100 System 500 79 System 5000 85
R
Receive Only Annunciators 26 Receive/transmit annunciators 25 Related Documentation 10 Remote annunciation, AM2020/AFP1010
66
Remote annunciation, NCA 91 Remote annunciation, NFS-3030 95
O
On-line LED 50, 52, 54 Overview ACM-16AT 13 ACM-24AT, AEM-24AT 13, 15 ACM-32A 13, 18 ACM-48A, AEM-48A 13, 16 AEM-16AT 13, 17 AEM-32A 13, 18 Backboxes 19, 20 Color variations 16 Dress panels 22 installation procedures 30 Key switch Phone jack
S
Selection groups AFP-300/AFP-400 62 NFS-640 75 Semi-flush-mount Backboxes 20 SIB, AM2020/AFP1010 65 Slide-in labels 39 Slide-in labels, see also center pages Software requirements, AM2020 65 Speaker and telephone mode AM2020/AFP1010 67 NFS-3030 96 Speaker Control Mode 42 Specifications 24 Communication 24 Electrical Ratings 28 Power 28 Supervising devices with ACM-16AT, ACM-32A 48 Surface-Mount Backboxes 19 Switch locations 31 System 500
105
P
Phone jack 39, 40 Point annunciation AIM-200 87 AM2020/AFP1010 66 NCA 91 NFS-3030 95 NFS-640 75 System 5000 87
ACS Manual P/N 15842:M 12/28/2006
TZ
Index
ACS program mapping 79 Control switches 80 DIP switches 79 LEDs 80 Power connections 78 System 5000 85 ACS program mapping 85 Control switches 85 DIP switches 85 EIA-485 82 LEDs 85 Power connections 83 System Trouble LEDs see LEDs
T
Testing 49 Trouble LEDs see LEDs
U
UDACT ACM-16AT, ACM-32A 47 ACM-24AT, ACM-48A 41 AFP-200 47 AFP-300/AFP-400 60 NFS-640 73 System 500 81 System 5000 87
V
VeriFire 13, 14 Voice applications, AM2020/AFP1010 67 Voice applications, NFS-3030 96 VP-2, VP-2B 22
W
Wiring 33, 36, 38, 40
X
XPIQ 42
Z
Zone mapping, AFP-300/AFP-400 62
106
Limited Warranty
NOTIFIER warrants products manufactured by it to be free from defects in materials and workmanship for eighteen (18) months from the date of manufacture, under normal use and service. Products are date stamped at time of manufacture. The sole and exclusive obligation of NOTIFIER is to repair or replace, at its option, free of charge for parts and labor, any part that is defective in materials or workmanship under normal use and service. All returns for credit are subject to inspection and testing at the factory before actual determination is made to allow credit. NOTIFIER does not warrant products not manufactured by it, but assigns to the purchaser any warranty extended by the manufacturer of such products. This warranty is void if the product is altered or repaired by anyone other than NOTIFIER or as expressly authorized by NOTIFIER in writing, or is serviced by anyone other than NOTIFIER or its authorized distributors. This warranty is also void if there is a failure to maintain the products and systems in which they operate in a proper and workable manner. In case of defect, secure a Return Material Authorization form from our Return Authorization Department. This writing constitutes the only warranty made by NOTIFIER, with respect to its products. NOTIFIER, does not represent that its products will prevent any loss by fire or otherwise, or that its products will in all cases provide the protection for which they are installed or intended. Buyer acknowledges that NOTIFIER, is not an insurer and assumes no risk for loss or damages or the cost of any inconvenience, transportation damage, misuse, abuse, accident or similar incident. NOTIFIER GIVES NO WARRANTY, EXPRESS OR IMPLIED, OF MERCHANTABILITY, FITNESS FOR ANY PARTICULAR PURPOSE, OR OTHERWISE WHICH EXTENDS BEYOND THE DESCRIPTION ON THE FACE HEREOF. UNDER NO CIRCUMSTANCES SHALL NOTIFIER BE LIABLE FOR ANY LOSS OF OR DAMAGE TO PROPERTY, DIRECT, INCIDENTAL OR CONSEQUENTIAL, ARISING OUT OF THE USE OF, OR INABILITY TO USE NOTIFIERS PRODUCTS. FURTHERMORE, NOTIFIER SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF, OR AS A RESULT OF, PERSONAL, COMMERCIAL OR INDUSTRIAL USE OF ITS PRODUCTS. This warranty replaces all previous warranties and is the only warranty made by NOTIFIER. No increase or alteration, written or verbal, of the obligation of this warranty is authorized. "NOTIFIER" is a registered trademark.
Warn-NL-04-2005.fm
107
World Headquarters 12 Clintonville Road Northford, CT 06472-1653 USA 203-484-7161 fax 203-484-7118 www.notifier.com