Pr3e64 1
Pr3e64 1
Pr3e64 1
3#25(25)mm²
EPR/XLPE (90ºC) - 0,6/1KV
80 A
6 kA - Curva B QM1
32 A (174578 W)
DPS (32181 VA)
32 A
CLASSE I Up<1,4kV Iimp=45kA Imax 60 kA (10/350µs) Uc=275V
#16mm² 10 32 A QD-COND
KW.h
6 kA - Curva C (8155 W)
8155 W QD-COND EPR/XLPE (90ºC) - 0,6/1KV R+S+T
10
50 A QDIT-101
5 kA - Curva C (21729 W)
EPR/XLPE (90ºC) - 0,6/1KV KW.h
EPR/XLPE (90ºC) - 0,6/1KV R+T
50 A 10
10
50 A QDIT-102
KW.h
5 kA - Curva C (20662 W)
QDIT-301 21729 W EPR/XLPE (90ºC) - 0,6/1KV R+T
10
50 A QDIT-201
EPR/XLPE (90ºC) - 0,6/1KV KW.h
5 kA - Curva C (21729 W)
50 A EPR/XLPE (90ºC) - 0,6/1KV S+T
10
10 AL1 80 A 50 A QDIT-202
R+S+T 10 kA - Curva C KW.h
5 kA - Curva C (20662 W)
21729 W QDIT-101 EPR/XLPE (90ºC) - 0,6/1KV EPR/XLPE (90ºC) - 0,6/1KV R+S
25 4x32 A 10 ELETRODUTOS
EPR/XLPE (90ºC) - 0,6/1KV
6 kA - Curva B 50 A QDIT-301 ELETRODUTO PEAD - ENTERRADO (DIRETA)
5 kA - Curva C (21729 W)
50 A KW.h
ELETRODUTO PEAD - ENTERRADO (PISO)
DPS EPR/XLPE (90ºC) - 0,6/1KV S+T
10 4xCLASSE I Up<1,4kV Iimp=45kA Imax 60 kA (10/350µs) Uc=275V 10
#16mm²
50 A QDIT-302 ELETRODUTO DE AÇO GALVANIZADO - APARENTE (DIRETA)
QDIT-302 20662 W 5 kA - Curva C (20662 W)
KW.h ELETRODUTO DE AÇO GALVANIZADO - APARENTE (TETO)
EPR/XLPE (90ºC) - 0,6/1KV R+S
10 ELETRODUTO DE AÇO GALVANIZADO - APARENTE (MÉDIA)
EPR/XLPE (90ºC) - 0,6/1KV 32 A QDIT-401
16 A 6 kA - Curva C (33152 W) ELETRODUTO DE AÇO GALVANIZADO - APARENTE (BAIXA)
KW.h
6 EPR/XLPE (90ºC) - 0,6/1KV R+S+T
10 ELETRODUTO PVC - EMBUTIDO NA ALVENARIA (PISO)
16 A QF-1 ELETRODUTO PVC - EMBUTIDO NA ALVENARIA (ALTA)
6100 W QF-1 KW.h
6 kA - Curva C (6100 W)
EPR/XLPE (90ºC) - 0,6/1KV R+S+T ELETRODUTO PVC - EMBUTIDO NA ALVENARIA (MÉDIA)
6
ELETRODUTO PVC - EMBUTIDO NA ALVENARIA (BAIXA)
EPR/XLPE (90ºC) - 0,6/1KV EQUIPOTENCIALIZAÇÃO
EPR 0,6/ 1 kV
ELETRODUTO PVC - EMBUTIDO NO ENTREFORRO (TETO)
50 A #16
10
BEP
Esquema vertical elétrico INTERLIGAÇÃO DE PONTO EM MOBILIÁRIO OU BANCADA
20662 W QDIT-102
7° COBERTURA NOTAS DE EXECUÇÃO DO PROJETO REDE COMUM E ILUMINÇÃO
EPR/XLPE (90ºC) - 0,6/1KV ELABORADO DE ACORDO COM AS NORMAS DA ABNT (NBR 5410, 5419, 14039) NR-10 E DA CONCESSIONÁRIA LOCAL, CEB/NEOENERGIA NTD 6.0
1
Verde-amarelo
2 TODA A TUBULAÇÃO NÃO INDICADA TERÁ DIÂMETRO DE Ø3/4", E TODA FIAÇÃO NÃO INDICADA SERÁ DE #2,5mm².
R 54731
Cinza
Preto
S 10798 AS TOMADAS COM ALTURA NÃO ESPECIFICADA SERÃO INSTALADAS A 0.40m DO PISO ACABADO, EM ATENDIMENTO À NORMA DE ACESSIBILID
6
T 11071
Total 32181 NAS ÁREAS EXTERNAS ENTERRADOS TODOS OS ELETRODUTOS DEVERÃO SER DO TIPO CORRUGADO PEAD, E QUANDO EM SOBREFORRO O
Verde
7
PARA INSTALAÇÃO NO PISO: CAIXA DE PASSAGEM "4X4" COM ALTURA DE 65MM, CONSTITUÍDA EM LIGA DE ALUMÍNIO SILÍCIO FUNDIDO, COM A
6° CAIXA D'ÁGUA
8
PARA INSTALAÇÃO EMBUTIDA EM PAREDE OU TETO: CAIXA "4X2" (PROFUNDIDADE DE 51MM) OU 4"X4" (PROFUNDIDADE DE 46MM), CONSTITUÍD
10
Quadro de Demanda (QM1) - TÉRREO
Item Demanda (kVA) FP - FATOR DE POTÊNCIA
POTENCIA
Apartamentos (x1.20) 10.30 In' - CORRENTE CORRIGIDA QDIT-401 O CONSTRUTOR DEVERÁ FORNECER ATESTADO DE CONFORMIDADE DAS INSTALAÇÕES ELÉTRICAS, ACOMPANHADA DA RESPECTIVA ART, RE
11
Condomínio (x1.20) 2.34 Ip - CORRENTE TOTAL DE PROJETO
Cargas especiais 17.00 Ic - CORRENTE MÁXIMA DO CABO O CONSTRUTOR DEVERÁ ATENDER AS EXIGÊNCIAS DA NORMA NR-10, TANTO PARA EXECUÇÃO DOS SERVIÇOS (EPI, FERRAMENTAL, ETC) DUR
TOTAL 32.18 DISJ - CORRENTE NO DISJUNTOR 12
O CONSTRUTOR DEVERÁ MANTER ENTENDIMENTO COM A FISCALIZAÇÃO SOBRE QUAISQUER CASOS OMISSOS NOS PROJETOS.
Quadro de Cargas (QM1) - TÉRREO 13
Circuito Descrição Esquema Método Tensão Pot. total. Pot. total. Fases Pot. - R Pot. - S Pot. - T FP FCT In' Ip Seção Ic Icc Disj 4° ÁTICO
TODOS OS TRABALHOS COMPLEMENTARES DAS INFRAESTRUTURAS (ABERTURA E FECHAMENTO DE RASGOS, PINTURA E ETC.) É ENCARGO
de inst. (V) (VA) (W) (W) (W) (W) (A) (A) (mm²) (A) (kA) (A) 14
QD-COND 3F+N+T B1 380/220 V 14324 8155 R+S+T 2302 3167 2686 0.57 0.91 22.6 20.5 10 66.0 6 32
TODOS OS CABOS DEVEM SER RESISTENTES À CHAMA, SOB CONDIÇÕES SIMULADAS DE INCÊNDIO, LIVRES DE HALOGÊNIO E COM BAIXA EM
QDIT-101 2F+N+T B1 380/220 V 22377 21729 R+T 11000 10729 0.97 0.91 13.6 12.4 10 66.0 5 50 15
QF-1 3F+N+T B1 380/220 V 9763 6100 R+S+T 1600 3000 1500 0.62 0.91 15.0 13.6 6 48.0 6 16
OS DISPOSITIVOS DE PROTEÇÃO, MANOBRA E CONTROLE, INCLUINDO OS CONTROLES A ILUMINAÇÃO DE SEGURANÇA, DEVEM SER CLARAME
QDIT-401 3F+N+T B1 380/220 V 34520 33152 R+S+T 10844 10622 11686 0.96 0.91 14.3 13.0 10 66.0 6 32
16
QDIT-102 2F+N+T B1 380/220 V 21217 20662 R+T 9662 11000 0.97 0.91 13.2 12.0 10 66.0 5 50
QDIT-301 2F+N+T B1 380/220 V 22377 21729 S+T 11000 10729 0.97 0.91 13.6 12.4 10 66.0 5 50
QDIT-302 2F+N+T B1 380/220 V 21217 20662 R+S 9662 11000 0.97 0.91 13.2 12.0 10 66.0 5 50
QDIT-301 QDIT-302 QUALQUER INSTALAÇÃO DEVE SER INSPECIONADA E ENSAIADA, DURANTE A EXECUÇÃO E/OU QUANDO CONCLUÍDA, ANTES DE SER COLOCAD
17
QDIT-201 2F+N+T B1 380/220 V 22377 21729 S+T 11000 10729 0.97 0.91 13.6 12.4 10 66.0 5 50
QDIT-202 2F+N+T B1 380/220 V 21217 20662 R+S 9662 11000 0.97 0.91 13.2 12.0 10 66.0 5 50
QUALQUER SOLUÇÃO DIFERENTE DA APRESENTADA EM PROJETO DEVERÁ SER SUBMETIDA A EQUIPE DE ENGENHARIA/PROJETISTA QUE O D
TOTAL 189391 174578 R+S+T 54731 60789 59059 18
3° ANDAR 20
TODAS AS CONEXÕES DE ELETRODUTOS, CAIXAS E CONDULETES SERÃO FEITOS COM ROSCA OU PARAFUSOS DE APERTO, COM UTILIZAÇÃO
AS CONEXÕES DOS CONDUTORES AOS COMPONENTES ELÉTRICOS DEVEM SER EFETUADAS ATRAVÉS DE TERMINAIS DE COMPRESSÃO APRO
22
QDIT-201 QDIT-202 OS EQUIPAMENTOS DE ILUMINAÇÃO INSTALADOS EM LOCAIS MOLHADOS OU ÚMIDOS DEVEM SER ESPECIALMENTE MONTADOS/INSTALADOS
23
QUALQUER INTERFERÊNCIA COM A ESTRUTURA DETECTADA EM OBRA E NÃO PREVISTA EM PROJETO DEVERÁ SER RELATADA AO PROJETIST
25
2° ANDAR
O ESQUEMA DE ATERRAMENTO PROJETADO É O TN-S, CONFORME CEB/NEOENERGIA NTD 6.01 E 6.07
26
TODOS OS EQUIPAMENTOS UTILIZADOS NA EDIFICAÇÃO DEVERÃO SER ATERRADOS CONFORME INDICADO NOS MANUAIS DOS FABRICANTE
29
1° ANDAR 32 O FIO NEUTRO NÃO PODERÁ SER ATERRADO APÓS TER PASSADO PELO INTERRUPTOR DR
Modelo 3D:
AL1
Quadro Descrição Esquema Tensão Pot. total. Pot. - R Pot. - S Pot. - T Demanda Total Demanda - R Demanda - S Demanda - T Seção Disj Conduto Setor/Cidade: BRASILIA-DF
(V) (W) (W) (W) (W) (VA) (VA) (VA) (VA) (mm2) (A) Endereço: [ENDEREÇO]
QD-COND 3F+N+T 380/220 V 8155 2302 3167 2686 11274 3577 4517 3181 10 32 Proprietário: [CLIENTE]
Autor do Projeto: LUCAS OLIVEIRA GUEDES CFT-072.717.081-38
QDIT-101 2F+N+T 380/220 V 21729 11000 0 10729 5371 2640 0 2731 10 50
QF-1 3F+N+T 380/220 V 6100 1600 3000 1500 8073 2551 3000 2521 6 16
QDIT-401 3F+N+T 380/220 V 33152 10844 10622 11686 8285 2715 2709 2861 10 32 PROPRIETÁRIO CPF/CNPJ
QM1 3F+N 380/220 V 174578 54731 60789 59059 32181 10311 10798 11071 25 80
AUTOR DO PROJETO CFT-072.717.081-38
QDIT-102 2F+N+T 380/220 V 20662 9662 0 11000 5092 2452 0 2640 10 50
QF-ELEV1 3F+N+T 380/220 V 5250 1750 1750 1750 8930 2977 2977 2977 6 16 CREA
RESPONSÁVEL TÉCNICO PELA OBRA
Conteúdo:
QDIT-202 2F+N+T 380/220 V 20662 9662 11000 0 5092 2452 2640 0 10 50 ELE Esquema Vertical
7 /8
QM/CM
-
Arquivo: Data de Emissão Inicial: Desenho: Escala: Unidade: Etapa do Projeto: Rev:
PRO-ELE-ESQ-VERTICAL-07-TER 29/03/2023 LUCAS GUEDES 1:50 Centímetro BÁSICO 0
FORMATO A0 - INTERNO: 1049 x 821 mm.
EXTERNO: 1189 x 841 mm. Esta planta somente poderá ser utilizada se plotada colorida, a partir de um arquivo .PDF