Programação Metasys Extended Architecture - Dia 1
Programação Metasys Extended Architecture - Dia 1
Programação Metasys Extended Architecture - Dia 1
Dia 1
Agenda
Day 1 2
Cont'd.
uLearn é uma plataforma nova, segura e habilitada para celular que permite
assistir a vídeos de treinamento curtos da Johnson Controls que ajudarão você a
fazer seu trabalho - onde quer que esse trabalho esteja localizado!
https://jc.kzoplatform.com/library
https://my.jci.com/sites/BE/NABAS/Pages/Interactive-Workflow.aspx
Network Communication
Tecnologia de Informação
Padrões
Web – Webservices Padrão
Comunicação Peer-to-Peer
BACnet®
Standards
Network Communication
IT Standards
Padrões
Simple Object Access Protocol (SOAP)
Peer-to-Peer
BACnet®
Padrões de TI
Padrões de TI
Padrões de TI
Network Communication
Peer-to-Peer Communication
Padrões
Padrões de TI
Peer-to-Peer
BACnet®
Peer-to-Peer
Network Communication
BACnet®
“A motivação para esse padrão foi o desejo generalizado de proprietários e operadores de edifícios
por "interoperabilidade", a capacidade de integrar equipamentos de diferentes fornecedores em um
sistema coerente de automação e controle - e fazê-lo de forma competitiva.”
BACnet® Standard
BACnet® PICS
Para obter uma lista completa dos BIBBs adicionais suportados (Anexo K), consulte a
seção BIBBs® Interoperability Building Blocks (BIBBs) (Anexo K) deste documento.
Accumulator Command
Analog Input Device
Analog Output Event Enrollment
Analog Value File
Averaging Group
Binary Input Life Safety Point
Binary Output Life Safety Zone
Binary Value Multistate Value
Calendar
O site BACnet® Testing Laboratories lista os PICS da JCI para cada produto
BACnet® http://www.bacnetinternational.net/btl/
Os Laboratórios de Teste BACnet® foram estabelecidos pela BACnet®
International para apoiar atividades de testes de conformidade e
interoperabilidade
O grupo de trabalho foi formado pela BACnet® International para
supervisionar o estabelecimento do programa de certificação e listagem de
conformidade BACnet®. O grupo de trabalho é composto por membros da
BACnet® International, cujos objetivos são promover e manter a marca
comercial da BACnet®. A JCI é um membro desta organização.
O número máximo de nós por segmento deve ser 32 (conforme especificado pela
norma EIA-485). Nós adicionais podem ser acomodados pelo uso de repetidores.
Perguntas?
Labs
Responda as perguntas abaixo.
Review Questions
Q1 O protocolo SOAP usa a porta UDP 280 para comunicação..
• Verdadeiro
• Falso
• Falso
• SMTP Server
• Field Bus
• BACnet® over IP
Q5 Os objetos BACnet® Exposed para um determinado dispositivo são descritos em um documento PICS.
• True
• False
Selecionando gerenciadores
Selecionando Servidores
Endereçando a rede
Determinando a capacidade do
Escolhendo components apropriados
sistema
Protocolos
▪ LonWorks
BACnet MS/TP
▪ RS-232
Legacy N2 Bus
▪ Zettler Fire Panel (new)
Modbus RTU ▪ M-Bus
Integração Ethernet
através da porta Ethernet
BACnet/IP
Modbus TCP/IP
KNX IP
Tyco C-CURE® 9000 Access Control
Tyco Victor® Video Management
Simplex® Fire Alarm Control Unit
Cree® SmartCast Lighting Control
Molex® Lighting Control
Portas:
Duas portas RS485 para N2 ou MS/TP
Uma porta Ethernet para IP
Opcional, uma porta para LON
Limites:
até 5000 por gerenciador*
Basear o limite para por memoria RAM e CPU do gerenciador
Dispositivos por tronco N2 ou MS/TP - 100 - MS/TP é limitado a 64
se controladores non-FAC/FEC/VMA/IOM estiverem no tronco
Dispositivos por tronco LON - 255
Numero maximo de pontos N2 ou MS/TP mapeados por tronco - 1000 casa
Numero maximo de variaveis LON mapeadas - 2000
Numero maximo de disipositivos BACnet®/IP mapeados - 100
Numero maximo de SMP simultaneos - 4
NAE 55xx
2 RS485 para MS/TP ou N2
Portas:
Uma porta RS485 MS/TP, N2 ou LON
limites:
Usa 2500 objetos como referencia de limite para esse modelo de gerenciadora
100 dispostivos para troncos N2 ou MS/TP com a NAE45 e 50 para a NAE35
MS/TP é limitado a 64 se controladores non-FAC/FEC/VMA/IOM estiverem no
tronco
128 dispositivos no NAE45 e 64 no NAE35 para LON Works
Maximo de pontos mapeados por tronco MSTP ou N2 — 1000
Maximo de variaveis mapeadas por tronco LON — 1500
Maximo de dispositivos BACnet®/IP - 100
Numero maximo de clients SMP - 2
1 RS485 para
MS/TP OU N2 ou
Configurado para
LON
Portas seriais:
0 – só se comunica via Ethernet (BACnet®/IP)
Limites:
25.000 objetos. NxE85s perderão comunicação se exceder 25k objetos. Você pode
comprar uma licença adicional se precisar exceder o limite de 25k objetos.
Proposito:
Mapear objetos BACnet® no Metasys®
Controladores Metasys® IP
N30s ou outros dispositivos de terceiros - BACnet®
Portas:
Uma porta como MS/TP ou N2 ou LON
Limites:
Até 2500 objetos
Dispostivos por tronco N2 ou MS/TP ou LON - 32
Maximo de pontos N2 ou MS/TP - 1000
Maximo de variaveis LON - 1500
Maximos de dispositivos BACnet®/IP - 100
Não pode ser site director de outros NCEs ou NAEs
NCE 25xx
Conexões fisicas
Portas:
0 – Só comunica via Ethernet
Limite:
25.000 objetos. Perde a comunição se passar do limite de 25k objetos. Pode
comprar licença adicional.
Proposito:
Mapear um Sistema LON Works dentro do Metasys®
Requere uma base de dados LNS e troncos LON conectados por gateways LON
Works
Portas:
Two RS-485 para NIE59, 1 RS-485 para NIE29, NIE39, NIE49
1 tronco LON para NIEx9 que suportam LON
1 tronco RS-232 disponivel para conversores RS-232 para RS-485 para Modbus
RTU
Limites:
Até 5000 objetos para NIE55 e 25000 objetos para NIE85.
Proposito:
Mapear troncos e dispositivos Modbus RTU ou TCP no Metasys®
Diversos modelos:
NIEx9 – mesmo hardwares dos NAE de versões equivalentes NAEs
NIE89 – Computador para rack que usa tronco Modbus TCP para integração.
Endereçando a rede
Endereçando a rede
Funções:
Discovery automática de dispositivos e pontos de campo dos troncos, N1 e
BACnet®
Árvore de navegação do sistema padrão para todos os usuários
Criação simples de visualizações de usuário e vários resumos, incluindo
resumos personalizados
Criação de gráficos personalizados
Administração - incluindo arquivamento de banco de dados
Programação do sistema
Endereçando a rede
Sistema Simples
NAE55
Tronco A N2 N2 N2 N2
LON LN LN LN LN
NAE55 NAE55
Trunk Trunk
A A
Trunk Trunk
B B
LON LON
NAE55
NIE55
NAE55 NAE55
3rd party
BACnet® NCM4500 NIE55
Boiler
Selecionando Servidores
Endereçando a rede
Selecionando Servidores
Endereçando a rede
Site Director
Site Director:
Dispositivo mais poderoso do site:
ADS / X
NAE85 / NIE85
NAE55 / NIE55
NAE45
NAE35
NCE25 (apenas autônomo)
Os usuários conectados podem ver todos os dispositivos e objetos no site
(assumindo a autorização da senha)
Sincronização de horário para todos os dispositivos no site
Endereçando a rede
Instalador simplificado com um clique - fornece um método mais rápido e conveniente para
instalação de ferramentas
Gerenciamento de certificados - Oferece privacidade e confiabilidade com opções de
gerenciamento de certificados integradas para regular certificados confiáveis para
mecanismos de rede da SCT
Detecção automática de relacionamentos com a descoberta de equipamentos - forneça aos
sites existentes uma configuração mais rápida da interface do usuário e da árvore de
navegação do Metasys®
Recurso de arquivamento rápido - fornece aos novos sites uma maneira rápida e
simplificada de configurar arquivos de uma planilha do Agendamento de arquivamento
rápido
Funcionalidade de arrastar e soltar - fornece a capacidade de permitir a criação em massa
de espaços e relacionamentos de equipamentos
Banco de dados de segurança e espaços e equipamentos de interface do usuário Metasys®
em Opções de gerenciamento de arquivamento - proporcionam upload e download
aprimorados de dispositivos de supervisão e download opcional de espaços e equipamentos
IDs de atributo definíveis pelo usuário e sintaxe de campo do item filho para definições resumidas -
fornecem recursos avançados de pesquisa no sistema
Modelos de definição de resumo personalizados - oferecem a capacidade de exibir, copiar em massa,
editar ou excluir rapidamente quaisquer extensões em pontos ou dispositivos
Links de Ajuda Sensíveis ao Contexto - Forneça uma maneira mais fácil de acessar o Sistema de
Ajuda a partir da interface do usuário
Utilitários de tronco integrados com folhas de parâmetro - fornece a capacidade de transferir CAFs
entre controladores e SCT por meio de conexões NxE Passthru, Direct Ethernet ou roteador MAP 4.2.
Além das opções de transferência de arquivos, o recurso também suporta a visualização e edição de
parâmetros do dispositivo por tronco do controlador de campo
Arquivos mestre de modelo de controlador e equipamento - fornece uma lista abrangente de pontos
comuns para gerar e adaptar facilmente definições específicas de equipamentos para o processo de
criação de equipamentos
Suporte expandido ao controlador de campo - fornece a integração e o suporte para os controladores
de campo IP
Endereçando a rede
Parametros da Network/LAN
DHCP enabled: True
IP Address: (automaticamente)
Roteador
IP Mask: (automaticamente)
IP Router
Address: (automaticamente)
...
ADS1
Endereço de IP externo:
172.16.99.255
Site 1 devices
IP addresses 192.168.1.xxx
Perguntas?
Objetivos
Após a conclusão deste laboratório, os participantes poderão executar as seguintes tarefas:
• Selecione o hardware e o software Metasys® para uma nova instalação
• Projetar uma rede Metasys®
Tempo estimado
Este exercício leva cerca de 45 minutos para ser concluído.
Contents
Atividade 1 Projetar uma Metasys®
Especificações
1. Vamos considerar um complexo de quatro edifícios de escritórios onde uma nova instalação será
montada
2. O cliente fornece todos os computadores da interface do usuário
Lista de Controladores
Controladores MS/TP LON®
VAV Controller Clg 589.47 VMA1615 731.56 (VAVLF)
VAV Htg 645.59 VMA1630 731.56
Small Air Handler 657.01 (FEC 1611) 904.60 (PRG 203-12)
Medium Air Handler 946.12 (FEC 2611) 2107.55 (PRG 400-12)
Large Air Handler 946.12 (FEC2611) 2230.15 (PRG 600)
17 points 24 points
IO Module for Large Air 690.07 (IOM37) 1655.53 (IOE400)
Handler 12 points 24 points
O instrutor designará equipes da classe para cada cenário. Reúna sua equipe e nomeie uma pessoa
encarregada de peças e preços, uma responsável por atender às especificações e uma responsável por
fazer um diagrama de rede.
1. Select the Engine types and quantities Be prepared to tell why you chose your
based on the following considerations: combination. No answer is completely wrong.
Field device count Be prepared to defend your choices.
Field point count
Total object count
Future expansion
Lowest cost (using listed cost prices)
2. Select the computer software programs Make sure you have computers to run these
and hardware: programs, if required.
SCT
ADS/ADX
MUI
MAP
3. Select the Site Director You should know that this should be the most
powerful device on the network.
4. Sketch the network on a whiteboard or You are not required to price Ethernet
flipchart provided infrastructure.
Computers
NxEs
Trunks
Ethernet network
Switches
5. Prepare to present your design to the group Select one or more members of your team to
present your results.
Review Questions
Q1 Is SCT included when ADS/ADX software is purchased?
• Yes
• No
• No
Q3 Can a single ADS computer be used as a repository for NxEs on more than one Site?
• Yes
• No
• ADX
• MUI
• NAE55
Creating an Archive
Creating a Site
Adding a Server
Adding an Integration
Name
Identifier
Na maioria das vezes, você não pode alterar os identificadores online; você precisa excluir e
adicionar novamente. Os nomes de objetos podem ser alterados online ou offline, mas esteja
ciente dos efeitos no banco de dados HistorianDB de fazê-lo!
Site Director
Supv Device
Field Trunk
Field Device
Field Point
Perguntas?
Revisão da atividade
Com o output do da atividade 1, escolha um dos possiveis cenarios e inici
Objetivos:
Após a conclusão deste laboratório, os participantes poderão executar as seguintes tarefas:
Iniciar o SCT
Crie um novo arquivo
Criar um backup de arquivamento
Criar uma cópia de arquivo morto
Localizar arquivos de banco de dados
Adicionar um novo site
Adicionar um ADS (Application Data Server)
Adicionar um dispositivo de supervisão NAE
Tempo Estimado
Este exercício leva cerca de 120 minutos para ser concluído.
Materiais requeridos
Laptop com System Configuration Tool (SCT). Version 13.2
Metasys® UI Offline
QuickLit: https://docs.johnsoncontrols.com/bas/
Contents
Atividade 1 Abrindo o SCT
Atividade 2 Criando um novo archive
Atividade 3 Criando um backup do archive
Atividade 4 Criando uma cópia do archive
Atividade 5 Deletando um archive
Atividade 6 Imprimindo as informações de um archive
Atividade 7 Adicionando um Servidor (ADS/ADX)
Contents
Atividade 8 Configurando Email
Atividade 9 Editando emails
Atividade 10 Imprimindo Alarmes
Atividade 11 Mudando a assinatura do site director
Atividade 12 Adicionando NAEs
Atividade 13 Editando NAEs
Atividade 14 Adicionando Troncos
Atividade 15 Categorias de Objetos
2. Enter the Username and Password that Initially, by default, the Username is
you have setup MetasysSysAgent and the Password is
ChangeThi$Pa$$w0rdN0w! Passwords are
case-sensitive and the 0s are zeros not the
letter O. You will immediately have to change
the Password.
4. If there are any existing Archives, the Open You should now be looking at the main screen
Archive Wizard will list them. If this window of SCT.
opens, click Cancel to close it.
This series of SCT lab exercises will assist you in building a database for a health care project.
WeCare4U Medical Group is a fictional health care conglomerate with medical centers all over the
country. You will build the database for one building of this medical center, which will be the Acute
Care Center of the Lonestar Medical Center in Dallas, Texas. The names in the labs have been
chosen with the overall project in mind. In your student notebook materials, you will find a set of
drawings. Refer to these drawings any time to get information regarding the project design and
network information.
1. Select Item → New Archive This will open the New Archive Wizard.
2. Enter the Archive identifier of WeCare4U You have created a new database file called
and click the Create button WeCare4U.mdf, which is located in Program
Data\Johnson
Controls\MetasysIII\SQLData\archive.
6. In the Configure screen click Last While in any Wizard, you may completely
configure the object or you can finish the
Wizard and Edit later.
8. When the Create Device? prompt appears, Normally, you would go ahead and create the
click the Cancel button devices here or go on to discover the Site, but
we are going to stop for some investigation.
9. On the main screen select Since there is only one tab, you could also
Action → Refresh Current Tab to update select Action → Refresh All Tabs.
the All Items tab of the navigation panel.
11. Drag and drop the Site object into the The display frame is the right side of SCT.
display panel You could also double-click the object or
right-click it and select View.
14. Set the panel layout back to Single Panel Make sure the Site is displayed in the display
panel.
It is possible to Undock the Navigation frame. This allows the Display panel to fill the entire screen.
See below.
You need to backup periodically and protect your hard work while going through a project. This is
an important step.
It is your responsibility to back up databases.
3. Use Windows® Explorer to browse to When you perform a database restore, SCT
C:\ProgramData\Johnson will list the backup files in this folder and
Controls\MetasysIII\DatabaseFiles prompt you to select the archive to be
restored.
4. Backups require the same version of SCT Warning: There is a folder in the
and SQL, but you can also create a backup SQLData/archive called backup. This is not
by Exporting the database, which is SQL used by SCT for backup, but is used by SQL
version independent. Go to Tools → server. When SQL is going to work on a file, it
Database → Export Database automatically makes a copy and sticks it here
just in case the file is corrupted.
Leave It As Is!
You can create a duplicate copy of your Archive database for reuse on another project
2. Select your Archive and use the default You have now created another .mdf file in the
unique identifier of WeCare4U1. Click Archive directory.
Copy → Yes.
2. Select Insert → Metasys Server The Insert Metasys Server Wizard appears.
3. Select the current Metasys® version and If you are using an ADX in your network, you
click Next would still insert an ADS object. Do not insert
an ADS L-A or ADS L-E device. They are
specialty ADS systems for the European and
Asian markets.
5. Give this object the identifier ADS1 and The ADS identifier must be unique in the
click Next Archive, because it is the beginning of the
Fully Qualified Reference string for each
object in the Site.
6. In the Configure screen, change the This name will be the one referenced when
Object Name to ADS1-Acute Care using the system as opposed to the
Computer Name.
7. Select the Advanced button
9. Enter the JCI IP Address on your network Refer to the Network Riser.
drawing
If you want an alarm printer, you must have an
ADS. The printer could be attached to the
ADS or accessible from the ADS through the
network.
Before this feature can be made functional, certain information must be obtained for use in setting
up an e-mail account. The following tables outline the necessary information for your system.
4. Replace the appropriate fields in the You need a User Name and Password if the
Shared Configuration section with the server requires it, and it usually will. For the
information provided below: lab, we will skip it.
Authentication Type Specify SMTP or POP before SMTP security if the None
customer’s email system requires it.
SMTP User Name and Enter if SMTP was selected in the Authentication Type Blank
SMTP Password field.
POP Server Hostname, Enter if POP before SMTP was selected in the Blank
User name, and Password Authentication Type field.
From Email Address* This must be a legitimate email address that is [email protected]
recognized and exists on the SMTP server.
* - Minimum required information
5. Add a New Destination using the A Destination is where and what will be sent
information below via email.
7. In the Item field drop-down, select All messages are sent during the
Start Time first shift - 7:00 AM through 3:30 PM - but only
In Operator field, select >= on weekdays.
In the Value field, set the clock to
07:00:00
8. Click OK
11. Click OK
14. Click OK
17. Click OK
18. Click Save Your Event Filters should look like this:
19. Add another filter. This time use the Check your work on the next page.
following specification: Fire messages are
sent between 3:30 PM on Friday and
7:00 AM on Monday.
In Destination 1:
Add these filters (Friday afternoon):
Start Day Of Week == Friday
Start Time >= 03:30 PM
Item Category == Fire
In Destination 2:
Add these filters (Weekend):
Start Day Of Week == Saturday
Start Time >= 00:00 AM
End Day Of Week <= Sunday
End Time <= 11:59 PM
Item Category == Fire
In Destination 3:
Add these filters (Monday morning):
Start Day Of Week == Monday
Start Time >= 00:00 AM
End Time <= 07:00 AM
Item Category == Fire
1. On the Email tab, scroll down to the Use these settings to adapt the message for
Format area who is receiving it and what type of device
they are using.
2. Edit and select Message, Value, Leave all other items unchecked.
and Item Description
1. Display the ADS in the Display panel It is probably already there from the previous
lab.
3. Right-click the desired printer and select For this lab, choose any printer on your
Properties computer.
4. Copy the printer name found on the The printer name is displayed next to the
General tab printer icon. CTRL+C will copy whatever you
have highlighted.
7. Click New and paste the printer name in CTRL+V will paste whatever you have copied.
the Printer field
9. For Line Out, use 60 The customer purchased a Laser printer. For a
tractor feed printer, use 0.
10. For Printing Priority Threshold, use 70 If the Priority Threshold is set to 20, Events
reported with Priorities 0 through 19 will print
immediately (along with any Events already
buffered for printing). Any Events reported with
Priorities of 20 through 255 will be buffered
until either the Line Out or Timeout settings
have been satisfied.
13. Leave Format with the default values. Use online Help for a further description of
Save your changes. these Attributes.
3. Click Save
1. Reference the Acute Care Center Two NAEs are required. You will insert NAE1.
Network Riser drawing Then you will make a copy of NAE1 as NAE2.
7. Expand the Lonestar Site Click the plus sign (+) next to it in the
Navigation panel.
Now you will modify the Attributes of the NAEs. To learn how to set up all of the Communications
and Network Attributes, refer to the NAE Commissioning Guide (LIT-1201519).
5. Click Save
8. Verify the Object Name is NAE2 It is also possible to change an Object Name
on the Configuration screen while the object
is being created.
9. Change the Description to
Serves Floor 3&4
11. Switch back to NAE1 The left and right arrows (upper left) in the
Display panel allow you to switch between the
two NAEs.
19. In the Site section, enter the This provides the destination for alarm and
ADS Repository address as shown on event data collected by the NAE.
the network riser
3. In later labs, you will be doing this function You must add the integration object before you
in a different way, so select the Cancel can add field controllers.
button to exit the wizard
1. Bring NAE1 into the Display panel Categories help to control things, especially
user access.
2. Select the Configuration tab and click Custom category names can be changed on
Edit the Site Authorization Categories tab.
4. Set your Server and Engines to these SYSTEM - Hardware (NxEs, Field Devices)
recommendations. Set the Engine Time GENERAL - Folders
Zone to match the ADS as well. Click HVAC - Field Points, Feature Objects
Save.
Progress Check
The database should now contain the following items and features:
Archive: WeCare4U
Site: Lonestar
NAE: NAE1
NAE: NAE2
ADS: ADS1-Acute Care
Baud Rate for Serial Port Cable Config in the NAEs should be 57600
NAEs and ADS should have DHCP disabled, and each device should have a static IP address
Review Questions
Q1 A database you can copy and move to another computer would be found in the:
• ..\MetasysIII\SQLData\archive directory
• ..\MetasysIII\Databasefiles directory
• Alarm Routing
Key Topics
Overview
Overview (Cont’d.)
O Demand Limiting (DL) monitora a energia e compara o uso com uma meta
tarifária definida pelo usuário (geralmente em kW). O recurso DL derruba cargas
para evitar exceder esse limite.
Overview (Cont’d.)
Overview (Cont’d.)
Overview (Cont’d.)
Exemplo
Um chiller é inicializado e consume 300kW pela primeira hora e depois cai para 200 kW
após a primeira hora. O chiller funciona por cinco horas.
Economias
esperadas
Sliding Window
Demand / KW St+4
Pt+4
t-6 t-5 t-4 t-3 t-2 t-1 t t+1 t+2 t+3 t+4
Time (minutes)
Fixed Window
Key Topics
Demand Limiting and Load Click each topic to learn about it.
Rolling
Load Definition
Operating Modes
Key Topics
1. O medidor de pulso
acumula as diferenças
entre leituras consecutivas
do acumulador e calcula a
taxa de variação entre Isso link o objeto de
demanda como o objeto
cada leitura. Esse objeto de medidor de pulso PMO
também totaliza os pulsos
contados e os converte em
unidades de consumo.
2. Você pode colocá-lo onde
quiser, por exemplo - a
pasta Energia
3. Executa uma vez por
minuto
Ajustando Sensibilidade
Baixa
500
Média Uncontrolled Demand
Alta
480
Low Shedding (Low)
Target
460
Demand
(kW-hr)
440
400
0 1 2 3 4 5 6 7 8
Time (Hours)
Configurando Schedule
Perfil DLLR
Registra informações durante o período de rastreamento, cujo padrão é um mês
(pode ser por hora, por dia, por semana, etc.)
Perguntas?
Key Topics
Desliga extensão de
alarmes de ate 32 objetos
Destinado a reduzir alarmes
incômodos
Segue a ação de outro
objeto
Permite um atraso na
reativação de alarmes
Características semelhantes a um
objeto BI / BO
Não está associado a um
dispositivo de hardware físico
Pode ser usado para armazenar
um valor de saída do processo
Pode ser usado para entrada do
operador em um processo
Interlock Object
Processa valores de 2 a
12 sinais de entrada
As entradas podem ser
analógicas ou binárias
(não misturadas)
Saídas mais alta, mais
baixa e média para
analógicos
Saídas AND, OR e Média
(maioria) para Binários
Perguntas?
Key Topics
Categoria Psicrometrica
Categoria de Constantes
Overview
Math Blocks
Boolean Blocks
O intertravamento pode fazer tudo isso, exceto a trava (LTCH). No entanto, a saída
deles pode ir para vários locais.
Latching Blocks
IN
LTCH
RS
Statistical Blocks
Estas são as suas seleções de modos de The numbers correspond to the modes
caixa
Selecione o estado desejado para a
Entrada 3 - Modo 7 (Aquecimento)
Control Blocks
Sequencer Blocks
Default Checkbox:
Desabilita todas as text box os limites Make e Break e usa os valores
padrões.
Os valores padrão são definidos para que cada dispositivo fique ligado por um
período proporcional de tempo.
Proactive Checkbox:
Desabilita os limites do estagio 1
E descola os outros estagios
proporcionalmente
Make Limit:
Liga o estagio quando o valor de entrada
para o bloco atinge esse limite. O make
limit deve sempre ser maior que o
break limit.
Break Limit:
Desliga o estagio quando o valor de
entrada no bloco diminui para esse
valor. O break limit do estágio atual
deve ser maior que o make limit do
estágio anterior.
Psychrometric Blocks
Constant Blocks
OH
OL
IL IH
Clamp High:
Seleciona se (True) para fixar a saída na
Saída High (OH)
Clamp Low:
Seleciona se (True) para fixar a saída na
Saída Low (OH)
Sem fixação, o cálculo proporcional pode
ultrapassar o limite. No exemplo, a saída
é fixada em 8. Portanto, mesmo que a
entrada aumente para 12, a saída para
em 10.
Campo Descrição
Rate Limit Especifica a taxa por minuto para aumentar / diminuir a saída até que
ela corresponda à entrada.
Startup Value Especifica o valor inicial usado quando o bloco está ativado.
Simbolo Descrição
IN Input (Entrada)
EN Enabled (Habilitado)
Ativa o rate limiter. Usa uma referência de atributo de objeto binário
para EN:
0 = Enabled (Ativa o comando)
1 = Disabled (Não ativa o comando)
Timing Blocks
Sem input
Entrega as informaçãos de data e hora da rede
Timer Connections
Output Description
IN Input
RS Reset cancels the timer. Does not apply to the Minimum On or
Minimum Off timers. Uses a binary object attribute for Reset
(1.0 = Reset Active, 0.0 = Reset Inactive)
Timer Attributes
Duração
Especifica a duração da função de timer em segundos. O intervalo é de 5 a
86.400 segundos.
Configuração
Tipos de timer:
Pulso
On Delay
Off Delay
Minimum On
Minimum Off
Delay Blocks
Attribute Blocks
Input Block
PHHWS OA-T
Present Value
Input Ref
REL
Output Block
Key Topics
Overview
Example of a Subsystem
Perguntas?
Session Overview
The session starts with a PowerPoint presentation, accompanied by a demonstration and a discussion led
by the instructor on adding LCT objects to an SCT archive using SCT, and followed by a lab completed by
the students.
Objectives
After successful completion of this lab, you will be able to:
Use LCT to create a control process diagram
Create LCT control processes to follow a given sequence of operations
Utilize the NAE Simulator to verify LCT control process operation
Required Materials:
Acute Care Center drawings
PC with SCT installed on it
Archive created with SCT labs
While in the simulation mode, you can override MS/TP controller inputs and outputs but you cannot
override any N2 inputs or outputs. This means that you will have to use BVs and AVs in place of any
N2 inputs/outputs when creating a control system
Contents
Activity 1 Creating Folders and Variables to Support LCT
Activity 2 Creating a Control System
Activity 3 Launching LCT
Activity 4 Edit Mode
Activity 5 Creating the Heating Start Process
Activity 6 Check if At Least One of the Air Handling Units is Running
Activity 7 Simulate the Process
Activity 8 Creating Another Process
Activity 9 Creating the Cooling Enable Process
Activity 10 Viewing the Print Preview
You will create a process to start the hot water system when it is cold outside, and there is at least
one Air-Handling unit running. Since you will be creating multiple processes during the next three
labs, you will need a folder for each process.
1. Open your SCT archive Wecare4U This might be an excellent time to do a backup
of the archive.
2. Select Insert → Folder
The simulator can only command binary and analog variables so you will need to create these
variables.
8. You will now add four BV objects, which will Name them SF1-S, SF2-S, and so on.
simulate the four SF-S objects for this
process
Logic Connector Tool (LCT) is a graphic process-diagramming tool within SCT. LCT is used to create
control processes that are executed by the NAE. LCT control process diagrams are housed within a
Control System object. The Control System object must be created first. Then, you can launch LCT
by displaying the Control System object.
3. In the Identifier screen, change the It should show up under that folder. If it does
identifier to Heating Start not, refresh your tab.
1. Display the Heating Start Control System This launches LCT in the display frame. There
object should be a blank work area with a tool bar of
icons. This is the View Mode.
2. Move the mouse pointer over each icon to To understand what the tool icons do, refer to
display the function briefly Help → Metasys Help → Logic Connector
Tool → Logic Connector Tool Concept →
Toolbar.
Q1 What is the difference between the Edit mode and the View mode?
1. Click the Edit icon to enter the Edit Mode The Edit icon is now a Save icon.
3. Select the library buttons at the left of the Only one group may be exposed at a time.
work area one at a time to expose the
groups of logic blocks
4. Select the Lines Grid icon to expose a This will help you line-up the blocks for a
blue line grid across the work area neater diagram. You can turn it off when you
are done.
Start with a relational operator. Is the Outside Air Temp less than 50° F (10° C)?
3. Select the Attributes library, and drag an Notice that it is already defined
Input Ref block to the work area to the left
of the less than [<] block
13. Add a floating constant, change it to 50 and The value passed into the REL input will be
connect it to the REL (reliability input) to used as the failsoft value when the object
the OA-T goes unreliable. When the object returns to
reliable, the output of the object will be normal.
15. Right-click and select Hide Now the line disappears and the number 1 is
inserted
4. Select the Attributes library, and drag an Notice that it is already defined for the BV1.
Input Ref blocks to the work area
11. Select the Attributes library, and drag an Notice that it is already defined.
Output Ref block to the work area
13. Accept the default 16-command priority This means it will not overcome schedules or
operator overrides, but will overcome operator
commands.
Your diagram should look something like the
one below.
The input creates references to prevent the lines from crossing. You could also hide the lines.
The simulator can only simulate one NAE; therefore, objects that are coming from other NAEs
cannot be simulated. When the processes are running normally, this is not a problem.
3. Display the Heating Start control system The control process should appear. Notice
that there are output values on the logic
blocks.
4. Double-click the OA-T input reference,
adjust the value to 60, and then click Send To 15.5° C (59° F) (Metric Units)
6. Double-click the BV1 (which is simulating If you want your values to process faster,
supply fan 1 status) reference block, just click the refresh icon.
command it to Active (on), and then
click Send
The next process is for a cooling enable. Start by adding a folder for this process.
3. Select Insert → Object You will also need a couple of BV objects for
this process.
4. In the Select Object Type screen,
select BV
8. Highlight CH1ENABLE
You will create a process to start the chilled water system when it is warm outside and there is at least
one Air-Handling unit running. (Refer to the Chiller Control section of the sequence of operations on the
chilled water system drawing.) This process is very similar to the one you just created for the hot water
system. In fact, you can copy the hot water system process and make some minor revisions.
New AND
Old AND
If you wanted to print a process, you could click anywhere in the display frame and select the print icon.
For the lab, just do a print preview.
2. Select Item → Print Preview to see how Your computer must have at least one printer
the printout would look installed.
Progress Check
The database should now include the following LCT Control System objects:
Heating Start
Cooling Start