Estudo Transformador Limitador MBII
Estudo Transformador Limitador MBII
Estudo Transformador Limitador MBII
1 DESCRIÇÃO:
2 CONCLUSÃO:
Como pode ser observado na tabela acima sem o transformador limitador, a corrente de
curto-circuito em 13.8 kV é de 19066 A > 12500 A.
# of Active Sources : 1
# of Active Motors : 1
# of Active Shunts : 18
# of Transformers : 27
Reference Temperature(°C) : 20.0
Impedance Displaying Temperature(°C) : 25.0
--------------------
Calculation Options
--------------------
Fault Phases:
Phase A for Line-Ground Fault
Phase B,C for Line-Line or Line-Line-Ground Fault
Classical Calculation:
Complex Z for X/R and Fault Current
-------------------------------------------
Bus Results: 0.5 Cycle--Symmetrical
-------------------------------------------
# of Total Buses : 17
# of Active Buses : 17
# of Total Branches : 18
# of Active Sources : 1
# of Active Motors : 0
# of Active Shunts : 0
# of Transformers : 2
Reference Temperature(°C) : 20.0
Impedance Displaying Temperature(°C) : 25.0
--------------------
Calculation Options
--------------------
Fault Phases:
Phase A for Line-Ground Fault
Phase B,C for Line-Line or Line-Line-Ground Fault
Classical Calculation:
Complex Z for X/R and Fault Current
-------------------------------------------
Bus Results: 0.5 Cycle--Symmetrical
-------------------------------------------
# of Total Buses : 22
# of Active Buses : 22
# of Total Branches : 23
# of Active Sources : 1
# of Active Motors : 0
# of Active Shunts : 1
# of Transformers : 3
Reference Temperature(°C) : 20.0
Impedance Displaying Temperature(°C) : 25.0
--------------------
Calculation Options
--------------------
Fault Phases:
Phase A for Line-Ground Fault
Phase B,C for Line-Line or Line-Line-Ground Fault
Classical Calculation:
Complex Z for X/R and Fault Current
-------------------------------------------
Bus Results: 0.5 Cycle--Symmetrical
-------------------------------------------
LT-69
MB-69
S1 S2
TR-2
TR-1
69000/13800 V
69000/13800 V
Z%: 7
Z%: 7
7000 kVA
7000 kVA
DJ-INTER
SEC-TR1 SEC-TR2
PMT1 PMT2
AL-UTM2
+1AH
2139
SALA PRINCIPAL - UTM2 SEP-13.8KV
C3-1(3X70)
C5-1(3X70)
C6-1(3X70)
C8-1(3X70)
C9-1(3X70)
C10-1(3X70)
C12
C7-1(3X70)
T1 T2 RESERVA
13800/460 V 13800/460 V
C11-1(3x300)
Z%: 5.75 Z%: 5.75 T3-P3-13.8KV T4-P4-13.8KV T5-P5-13.8KV
1250 kVA 1250 kVA
C2-3[4(1X300)]
TCLD
C4-3[4(1X300)]
BOMBA A VÁCUO
LAZER
T1-BT-460V
T2-BT-460V
SEC. T1 SEC. T2 T3 T4 T5
Miguel Burnier - SE MB1 - 69kV
Alimentador 13.8kV para sala principal UTMII
10/04/2014
ANEXO 01
GRID
CEMIG
Vs: 138 kV
LT 02
LT 01
REC302D REC304D
REC303
REC305
REC3BR1 REC3BR2 REC3BR3
Vs: 138 kV Vs: 138 kV Vs: 138 kV
REC301
REC307
REC3BR6 REC3BR5 REC3BR4
Vs: 138 kV Vs: 138 kV Vs: 138 kV
REC311
REC309
REC302
REC3BR7
Vs: 138 kV
LT SE REC - SE MBII
REC-MB2-01 REC-MB2-02
Vs: 138 kV
REC-MB2-2 REC-MB2-3
TR-01 MB2 TR-02 MB2
138/13.8 kV 138/13.8 kV
Z%: 11 Z%: 11
35000 kVA 35000 kVA
REC-MB2-4 REC-MB2-5
SEC TR-01/TR-02 MB2
Vs: 13.8 kV
ANEXO 02
GRID
CEMIG
Vs: 138000 V
LT 02
LT 01
REC304D
REC302D
REC305
REC303
REC3BR1 REC3BR2 REC3BR3
Vs: 138000 V Vs: 138000 V Vs: 138000 V
REC301 REC307
REC311
REC309
REC302
REC3BR7
Vs: 138000 V
LT 03
REC-MB2-01 REC-MB2-02
Vs: 138000 V
REC-MB2-4 REC-MB2-5
REC-MB2-6 REC-MB2-7
10/04/2014
LOAD MBI
Vs: 13800 V
55
41 ANEXO 03
Vs: 13800 V