1. Safety Instructions and Battery Care 1.1.15. Install the UPS away from objects that give off excessive heat and areas
that are excessively wet.
1.1. Safety Instructions
1.1.16. If liquids are spilt onto the UPS or foreign objects dropped into the unit the
1.1.1. For Parallel System installation please refer to MSII 6KVA Parallel System warranty will be null and void.
Installation Guide
1.1.17. The battery will discharge naturally if the system is unused for a long time.
1.1.2. This UPS is equipped with an EMI filter. To prevent potential leakage
current hazard, ensure that the AC main supply is securely grounded. 1.1.18. The UPS should be recharged every 2-3 months if unused. If this is not
done then the warranty will be null and void. When installed and being
1.1.3. To ensure safety in all applications where a UPS is hard wired to the used the batteries will be automatically recharged and kept in top condition.
electrical supply, ensure that the system is installed by a qualified electrical
contractor. 1.1.19. This UPS supports electronic equipment in office, telecommunication,
process-control, medical, and security applications. Non-authorized
1.1.4. The UPS has its own internal energy source (battery). Should the battery technicians are not allowed to install the UPS in the following areas.
be switched on when no AC power is available there could be voltage at a. Medical equipment directly related to human life
the output terminals. b. Elevators, subway systems, or any other equipment related to
human safety.
1.1.5. Ensure the AC utility outlet is correctly grounded. c. Public systems or critical computer systems.
1.1.6. Do not open the case as there are no serviceable parts inside. Opening 1.1.20. Do not install the UPS in an environment with sparks, smoke or hazardous
the case voids the warranty. gas.
1.1.7. Do not try to repair the unit yourself; contact your local supplier. Repairing 1.1.21. Make sure the UPS is completely turned off when moving from one place
the unit yourself voids the warranty. to another. It might cause electrical shock if the output is not cut
completely.
1.1.8. Ensure the input voltage of the UPS matches the supply voltage.
1.1.22. The UPS includes a Maintenance Bypass Switch. Please follow the
1.1.9. Use a certified input power cable with the correct plugs and sockets for the procedures strictly when switching on or off the Maintenance Bypass
appropriate system voltage. Switch.
1.1.10. To prevent any overheating of the UPS keep all ventilation openings free 1.1.23. The UPS offers a CVCF (Constant Voltage Constant Frequency) setting
from obstruction, and do not store things on top of the UPS. Keep the UPS function.
30 cm away from the wall.
a. For correct setting and wiring please contact with your local utility
agent.
1.1.11. Ensure that the UPS is installed within the proper environmental range. (0-
b. Do not set it yourself or your warranty will be void.
40C and 0-90% non-condensing humidity)
1.1.24. This UPS has been designed and constructed to protect your assets from
1.1.12. Do not install the UPS in direct sunlight. Your warranty may be void if the the wide range of power aberrations experienced on utility power lines
batteries fail. today. It is your insurance for a reliable, clean and stable voltage supply. It
is worth taking care to install the system correctly and to have it
1.1.13. Install the UPS indoors as it is not designed for installation outdoors. maintained correctly by your local dealer.
1.1.14. Dusty, corrosive and salty environments can damage any UPS.
2 3
1.1.25. SAVE THESE INSTRUCTIONS. This manual contains important 4) Do not lay tools or metal parts on top of batteries.
instructions that should be followed during installation and maintenance of
5) Disconnect charging source prior to connecting or disconnecting battery
the UPS and batteries.
terminals.
1.1.26. The UPS is intended for installation in a controlled environment. 6) Determine if battery is inadvertently grounded. If inadvertently grounded,
remove source from ground. Contact with any part of a grounded battery
1.1.27. CAUTION: A disconnect switch must be provided by others for the AC can result in electrical shock. The likelihood of such shock can be
output circuit. To reduce the risk of fire connect only to a circuit provided reduced if such grounds are removed during installation and
with branch circuit over-current protection for 30 amperes for 6 kVA and 40 maintenance (applicable to equipment and remote battery supplies not
amperes for 8 kVA (See below for 10 kVA details) rating in accordance having a grounded supply circuit).
with the National Electric Code, ANSI/NFPA 70.
10 kVA tower Output rating Ratings of output branch circuit 1.2. Battery Care
Output No. over-current protection
No.1 (L21-N21) 5 kVA, 120 V 45 If the UPS is unused for an extended period of time it must be stored in a
No.2 (L22-N22) 5 kVA, 120 V 45 moderate climate. The batteries should be charged for twelve hours every
No.3 (L23-N22) 10 kVA, 208 V 50 three months by plugging the UPS power cord into a wall receptacle and
No.4 (L21-N22) 10 kVA, 240 V 45 turning on the input breaker on the front panel. Repeat this procedure every
1.1.28. CAUTION: To reduce the risk of fire connect the UPS only to a circuit two months under a high-temperature environment.
provided with branch circuit over-current protection for 40 amperes for 6
kVA and 70 amperes for 8/10 kVA rating in accordance with the National
Electric Code, ANSI/NFPA 70.
1.1.31. Units are considered acceptable for use in a maximum ambient 40°C
1.1.35. CAUTION– A battery can present a risk of electrical shock and high short
circuit current. The following precautions should be observed when
working on batteries:
1) Remove watches, rings, or other metal objects.
2) Use tools with insulated handles.
3) Wear rubber gloves and boots.
4 5
2. Product Introduction 2.1.12. A revolutionary battery management circuit analyzes battery discharging
status to adjust the battery cut-off point and extend battery life.
2.1. General Characteristics 2.1.13. The intelligent, temperature-controlled fan may not only extend the life of
the fan but also reduce annoying noise because of sudden fan spin. This
2.1.1. True online architecture continuously supplies your critical device with helps keep your office quiet and comfortable.
stable, regulated, transient-free, pure-sine-wave AC power.
2.1.14. When the UPS is out of order you can read the possible reason from the
2.1.2. 20 kHz PWM sine-wave topology yields excellent overall performance. LCD screen directly, which reduces unnecessary repairs.
The high crest factor of the inverter handles all high-inrush current loads
without a need to upgrade the power rating. 2.1.16 When the UPS is operated in CF50 or CF60 mode, the recommended
load connected shall be 75% of rated capacity if the input voltage is 176-
2.1.3. The multi-functional LCD/LED panel displays various states of the UPS. 280 VAC and 50% of rated capacity if the input voltage is 160-280 VAC.
The LED display shows the UPS working status, utility status and
abnormal status. The LCD display shows input/output voltage, frequency, 2.1.17 Single input System Block
load status, inner cabinet temperature, and abnormal phenomena.
2.1.5. Should the output become short-circuited, the UPS cuts the output
automatically until the short-circuit situation is removed manually.
2.1.6. Should the unit become overheated, the internal thermal switch will detect
the heat and switch to bypass mode and vice versa.
2.1.7. The fully digitalized control circuit built into the UPS allows upgrading the
functionality of the UPS as well as reaching a high-level of protection of
the UPS. Powerful communication capability enhances its ability for
remote control and monitoring.
2.1.10. Providing four different working modes (Normal, ECO, CF50 and CF60) it
may be used in a wide variety of applications.
2.1.11. The DC-start function ensures the start-up of the UPS during power
outages.
6 7
2.1.18 Dual input System Block 2.2. Symbols on the LCD Display Panel
2 Battery Low
3 Battery Abnormal
4 UPS Overloading
8 9
Parallel communication error (communication
17 Next Page 35 Er21 wire disconnected or failure to find ID1 UPS) in
Parallel System
18 Special Function Log In/Out 36 Er24 CVCF mode with Bypass input
20 Utility Input Normal LED 38 Er28 Bypass Overload Time out and cut off output
8
9
10
11
12
5 9 7 10 6 8
LCD
Green LED indicates that the UPS is able to run under redundancy mode.
Solid green LED indicates that the utility input voltage is within the window.
Also available for Rack
Flashing green LED indicates that the utility input voltage is outside the
acceptable window.
12 13
2.4. Communication Port
The communication port on the UPS provides for RS-232 communication with
the UPS software to remotely monitor the power and UPS status.
You may use optional interfaces cards for R2E (second RS-232), RSE (RS-
485), USE (USB), DCE (Dry Contact), and SNMP. However, the R2E card, RSE
card and USE card must not be used simultaneously.
The software bundled with the UPS is compatible with many operating
systems such as Windows 98, 2000, ME, NT and XP. For other applications such
as Novell NetWare, Unix, or Linux please contact your local distributor for a proper
solution.
When the optional interface cards are used together with the onboard RS-232
port the EPO signals will get highest priority, then the SNMP/WEB card, then the
shutdown command at the DCE, R2E, RSE, and USE cards, and then finally the
onboard RS-232 port gets the lowest priority.
* : 15K/20K option
14 15
3. Installation and Operation
3.2. Selecting Installation Position
Carefully inspect the UPS for shipping damage before installation. Retain the Install the UPS in a proper environment to
packing material for future use. minimize the possibility of damage to the UPS and
to extend the life of the UPS. Please follow these
3.1. Unpacking rules:
16 17
3.4. Terminal Block Explanation ● L11-N1、B-N1: the terminal for Bypass Input to provide the power source when
the UPS is working under bypass mode
● L12-N1、R-S-T-N1: the terminal for Utility Input to provide the power source
when the UPS is working under Utility mode
● G1: the terminal for UPS Input Ground
● L21、L23、N21、L22、N22: the terminals for UPS Output
● G2: the terminal for UPS Output Ground
Remarks:
1. The maximum current for each terminal is 30 Arms for 6 kVA, 50 Arms for 10
kVA, 100 Arms for 20 kVA.
2. If the UPS is a DIM (Dual Input) type whose Utility and Bypass Sources are
the same, L11 and L12 must be shorted for the 1-phase input model, and B
and R must be shorted for the 3-phase input model.
3. If the UPS is a SIM (Single Input) type, only AC source can be supplied to the
UPS from the L12-N1 terminal for the 1-phase input model and from the R-S-
T-N1 terminal for the 3-phase input model.
4. When the isolation transformer is not installed into the tower-type UPS the
UPS output terminals will be L22-N22.
5. Use No. 6 AWG, 75C minimum copper wire and 23 lb-in Torque force when
connecting to terminal block
6. When the isolation transformer is installed into the tower-type UPS:
a. For 100/110/115/120 VAC systems you may connect as shown below.
110Vac
6KVA (Max)
18 19
● Use mounting cable ties to fix cables.
E xternal Charger
T1
10KRT model
b. Battery input
A1.
“test”
A2.
E1
“OK” in self-test
B.
E2
“Fail” in self-test
22 23
F
H
G
Voltage comes from Bypass Input.
24 25
O
J
K P
L 3.5.4.1. After the UPS completely starts up, press the key to change
the LCD display to figure Q1.
Q1
M
buzzer “On”
Q2
buzzer “Off”
26 27
3.5.4.2. Press the key to scroll through the UPS settings. The LCD
will display in sequence figure Q1 (buzzer) figure R1 (Self-test)
figure S1 (Bypass Voltage Windows) figure T (Output
Frequency Synchronization Window) figure U (Inverter Output T
Voltage) figure V1 (UPS Operation Mode) figure W (Output
Voltage Micro Tune Value) figure X (UPS Id) figure Y
(Parallel function status).
Frequency Window is +/-3 Hz.
R1
R2
V1
Self-test is “On”.
The UPS is operating in “normal mode”.
S1
V2
S2
V3
28 29
3.5.5. UPS Default Settings and their alternatives
3.5.5.1. Make sure the UPS is not “On”. Press the On and scroll down
V4
keys simultaneously for approximately three seconds. The
buzzer will sound twice, and the LCD will display figure Q1,
indicating that the UPS is in setting mode.
3.5.5.2. To scroll through the options refer to section 3.5.4.2.
The UPS is operating in “CVCF 60 Hz mode”.
3.5.5.3. Except for Buzzer (figures Q1 and Q2) and Self-test (figures R1
and R2) all of the other default settings may be changed by
pressing the scroll up key.
3.5.5.4. Figures S1 and S2 indicate the bypass input acceptable window. It
W can be 184-260 VAC or 195-260 VAC.
3.5.5.5. Figure T indicates the bypass frequency window of the Inverter
Output. The acceptable setting values are ±3 Hz and ±1 Hz.
3.5.5.6. Figure U indicates the acceptable Inverter Output Voltage.
Output Voltage Adjustment (-3% to 3%) Possible values are 200, 208, 220, 230, or 240 VAC.
3.5.5.7. Figures V1, V2, V3 and V4 indicate the operation modes of the
UPS. Possible values are Online, Eco (Economical) mode, fixed
50 Hz Output, and fixed 60 Hz Output.
3.5.5.8. Figure W indicates the adjustment of the Inverter Output, which
may be set to 0%, +1%, -1%, +2%, -2%, +3%, or -3%.
X
3.5.5.9. Figure X indicates the position of the UPS when the UPS is in
Parallel mode. Possible positions are 1, 2, 3, and 4. The position
must be 1 if the UPS is not in Parallel mode.
3.5.5.10. Figure Y indicates the parallel function status. “P 01” indicates
UPS position in parallel mode
that the parallel function is disabled, and “P 02” indicates that the
parallel function is enabled.
3.5.5.11. After changing settings you must scroll to the “save” screen
(figure Z) and then press the enter key to save all of your
Y changes. Then the LCD will display figure AA to indicate
completion of the setting changes. To cancel your changes rather
than save them press and hold the “OFF” key for five
seconds. The LCD displays figure AA directly, which indicates that
The parallel function is disabled.
your changes were canceled.
30 31
3.5.8. Maintenance Bypass Mode
3.5.8.1. Maintenance Bypass Mode is for UPS maintenance only. Only
authorized technicians are allowed to perform the following
procedures. If there is any damage during unauthorized execution
AA of these procedures your warranty will be void immediately.
3.5.8.1.1. Press the Off key for approximately five seconds. The LCD will
display figure B, and the UPS output will be in bypass mode.
The UPS is locked.
3.5.8.1.2. Remove the cover of the CAM Switch (Maintenance Bypass Switch),
3.5.5.12. Turn Off the Utility Input breaker. then turn on the CAM Switch to “Bypass” mode. In the upper right-hand
3.5.5.13. Your setting changes are now complete. corner of the LCD a sign will appear.
3.5.8.1.3. Turn off the UPS Utility breaker as well as the Bypass Input Breaker. You
3.5.6. Troubleshooting when the UPS is Off Due to Unknown Reasons may proceed with UPS maintenance now.
3.5.6.1. If there is a serious abnormal condition the UPS will lock itself in 3.5.8.1.4. When you are done with UPS maintenance put the UPS back into
the “OFF” position as shown in figure AA, and an “abnormal” normal working mode as explained in section 3.5.1.4. Then return the
message will appear on the LCD. CAM switch to “INV” mode, replace the cover, and repeat sections 3.5.1.5
3.5.6.2. After three seconds all messages will be locked except Bypass to 3.5.1.8. The UPS will switch back to inverter mode.
3.5.8.1.5. You must perform section 3.5.8.1.1 before section 3.5.8.1.2. If you skip
messages (LED and LCD ). If the Utility is abnormal
section 3.5.8.1.1 the UPS will alert for ten seconds to warn that the
after the UPS is locked the LED will be extinguished and procedure is abnormal and may damage the UPS due to uncertain utility
the LCD will appear on the LCD. status. The UPS will switch back to Inverter mode immediately if you turn
3.5.6.3. To release the UPS lock proceed as follows: the CAM switch back to “INV”.
3.5.6.3.1. Check the recorded error messages.
3.5.6.3.2. Check the error messages in section 2.2 to help troubleshoot the
problem. For further help consult your local distributor.
3.5.6.3.3. Press the Off key for five seconds. A buzzer will sound twice.
3.5.6.3.4. Turn Off the Utility Input breaker.
3.5.6.3.5. Even if the UPS lock problem is solved now, consult with your local
distributor to make sure that the error condition is resolved.
32 33
4. Troubleshooting Guide
Situation Check Items Solution
4.1. Troubleshooting red Fault LED Check the error code 1. Check for proper battery connection,
shown on the LCD. then recharge the batteries for 8 hours
If the UPS malfunctions during operation first check the following: to see whether the UPS provides
1.Er05, & backup power normally; otherwise,
a. Is the input and output wiring correct? 2.Er06, Er10, Er12, Er28 & consult your local distributor right away.
b. Is the input voltage of the utility within the input window of the UPS? 2. If CB3 is tripped, turn off the UPS
3.EPO completely and keep the CAM switch at
If problems still exist check the following for proper adjustment. Should the 4.Er11, Er33 position INV before pressing CB3. Then
problem still persist, please contact your local distributor for help. 5.Er14 remove some uncritical load at the UPS
6.Er15 output end. If there is any damage to the
7.Er16, Er27 insulation of the AC power cord, please
8.Er21 replace it with a new one.
9.Er24 3. Remove the short circuit at the EPO
10. other error code terminal.
4. Remove any objects blocking the
ventilation holes.
5. Check that the cooling fans on the rear
panel are working normally.
6. Make sure the UPS is operated
normally. If it is in CVCF mode you must
turn off and turn on the UPS again.
7. All of the parameters except ID Number
in a parallel UPS must be the same.
Please refer to section 3.5.5 to set them
again.
8. Disconnect and reconnect the RJ45
connector or set a UPS with ID=1.
9. When the UPS is in CVCF mode it is
prohibited from having bypass input.
You must turn off the UPS and bypass
input and then restart the UPS.
10. Consult your local distributor for help.
UPS fails to If the backup power time is still too short
offer battery after 8 hours of charging please contact
backup or its your local distributor for battery
backup power replacement.
time is shorter
than
calculated.
UPS locks Refer to section 3.5.6 to troubleshoot the
itself and can problem; otherwise, consult your local
not be turned distributor for help.
off.
34 35
5. Communication Software
6. Optional Interface Cards
5.1. Hardware Setup
6.1. R2E (second RS-232) card
1. Connect the male connector of the RS-232 cable to the UPS
communication port. 6.1.1. CN1 is for RS-232 DB9.
2. Connect the female connector of the RS-232 cable to a dedicated RS-232 6.1.2. For interface settings and pin
port of the attached computer. assignments please refer to section 2.4.1.
3. For optional interface cards refer to Chapter 6 for installation. 6.1.3. Installation Position: slot 1 (CHA-CN4) or
slot 2 (CHB-CN5)
5.2. Software Installation
Please refer to the software user’s manual. 6.2. RSE (RS-485) card
6.2.1. CN1 is for the terminal-resistor function. Short pins 1-2 to enable the
function. Short pins 2-3 to disable it.
6.2.2. CN2 is for RS-485. CN3 is for remote power.
6.2.3. Definition:
CN2
1 2 3 1 Ground
2 A/Data+
3 B/Data-
CN3
1 2 1 AC+
2 AC-
6.2.4. Installation Position: slot 1
36 37
6.5. SNMP Cards
6.4. DCE (Dry Contact)-B card 6.5.2. Net Agent II Internal Card
6.5.2.1. For installation
please refer to the
6.4.1. pin assignments of 10-pin terminal:
card’s user manual.
6.5.2.2. Position: slot 2 (CHB)
1 2 3 4 5 6 7 8 9 10
6.4.2. The shutdown function will be activated after +6~+25 VDC is applied
between pin 9 and pin 10 for 5 seconds.
6.4.3. The capacity of each relay contact is 40 VDC/25mA.
6.4.4. Installation Position: slot 1 (CHA-CN7) or slot 2 (CHB-CN8)
6.4.5. Flexible signal output for N.C. (Normal close) or N.O. (Normal open)
contact by shorting pins 1-2 or pins 2-3 from JP1-5
6.4.6. The shutdown function will be enabled 1 minute after blackout occurs if
pins 1-2 of both CN1 and CN6 are shorted. Otherwise the shutdown
function can be enabled only by pins 9-10 of CN3 if pins 2-3 of both CN1
and CN6 are shorted. (Refer to 6.4.2.)
38 39
6.6. Interface Card Installation 7. Replacing Batteries
To be performed by qualified personnel only
1 1. Unscrew the bottom of the front panel as indicated in Step. 1 below.
2. Remove the front panel as indicated in Step 2.
40 41
6. Rotate the battery pack handle 90 degrees as shown in Step 6.
7. Remove the battery packs from the UPS as shown in Step 7.
42 43
Audible and Visual Line Failure, Battery Low, Transfer to Bypass, System Fault
Conditions
8. Specifications
PROTECTION
Overload (with AC Mode: <105% continuously
Model 6000VA 8000VA 10000VA simulated thermal >106% ~ 120% for 1 min
INPUT tripping I-T curve) >121% ~ 150% for 10sec shut down
Voltage Window 160~280Vac* >150% immediately
Frequency 45 ~ 65 Hz
Phase/Wire Single, Line + Neutral + Ground Bypass Mode: <105% continuously
Power Factor Up to 0.99 at 100% Linear Load >106% ~ 120% for 250sec shut down
Current THD <5% at 100% Linear Load >121% ~ 130% for 125sec shut down
OUTPUT >131% ~ 135% for 50sec shut down
Voltage Window 220/230/240Vac Selectable(208/120Vac optional) >136% ~ 145% for 20sec shut down
Voltage Adjustment ±0%; ±1%; ±2%; ±3% >146% ~ 148% for 5sec shut down
Voltage Regulation ±2% >149% ~ 157% for 2sec shut down
Capacity 6000VA/5400W 8000VA/7200W 10000VA/9000W >158% ~ 176% for 1sec shut down
Rated Power Factor 0.9 Lagging >177% ~ 187% for 0.32sec shut down
Wave Form Sine Wave, THD<3%(no load to full load) >188% for 0.16sec shut down
Frequency Stability ±0.2%(Free Running) ALARMS
Frequency Regulation ±1%; ±3% Audible and Visual Line Failure, Battery Low, Transfer to Bypass, System Fault
Transfer Time 0ms Conditions
Crest Factor 3:1 PHYSICAL
Efficiency(AC to AC, Up to 91% 290 x 645 x 748mm
Normal) Dimensions (1P/1P and 3P/1P)
Efficiency(AC to AC, Up to 95% 290 x 645 x 748mm 290 x 645 x 881mm
(W x D x H)
ECO) (with Galvanic Isolated Transformer
Autonomy ~15-30 mins depending on load Option)
DC Start Yes Input/Output Hardwire
Connection
BATTERY
External Battery Plug-in & Play
Type Sealed Lead Acid Maintenance Free Sealed Lead Acid
Connection
12V/7AH Maintenance Free
Standard
12V/9AH unit 86Kg 122Kg
Quantity 20pcs Net With
Voltage 240Vdc Weight Galvanic
Recharge Time 4 hours to 90% 5 hours to 80% (Kgs) Isolated 139Kg 175Kg
DISPLAY Transformer
Status On LED + LCD Line Mode, Backup Mode, ECO Mode, Bypass Supply, option
Battery Low, Battery Bad/Disconnect, Overload, < 450W without < 600W without Isolated
Transferring with interruption & UPS Fault. Isolated Transformer Transformer at full Linear Load
Readings on LCD Input Voltage, Input Frequency, Output Voltage, Output at full Linear Load
Heat Dissipation
Frequency, Load Percentage, Battery Voltage & Inner < 615W with Isolated <1100W with Isolated Transformer
Temperature. Transformer at Full at Full Linear Load
Self-Diagnostics Upon Power-on, Front Panel Setting & Software Control, Linear Load
24-hour routine checking Leakage Current < 3mA at Full Load
ALARMS Marks CE, cUL, UL
* (160~176Vac at <75% load)
** Isolation transformer: net 53kgs for 6000VA, 8000VA ,10000VA
44 45