Flair 279: Easergy Range
Flair 279: Easergy Range
Flair 279: Easergy Range
Easergy range
Flair 279
Français
Détecteur de courant de défaut pour réseaux HTA souterrains
Fault passage indicator for underground MV networks
Detector de paso de falta para redes subterráneas de media tensión
Manuel utilisateur
User’s manual
Manual de usuario
English
DEFAUT
RAZ /
RESET
TEST
FAULT
BT
LV
Español
Flair 279
Sommaire Flair 279
Installation 2
Installation du boîtier 3
Installation de la signalisation extérieure 3
Installation des tores 4
Montages tritores 5
Montage monotore 5
Sortie contact sec TS 5
Français
Mise à la terre 5
Alimentation 5
Exploitation 6
Configuration des micro-interrupteurs 6
Généralités 7
Réglages 7
Test de fonctionnement 7
Test fonctionnel 7
Détection de défaut 7
Maintenance 8
Pièces détachées 8
Remplacement de la pile 8
Autodiagnostics 8
Dimensions 9
D2160073-FR-EN-ES-05 1
Installation
DE58521FR
SW1 BP1
1 LD1 LED défaut
2
3 J4
4 opt.
5
J7 6
7 LD2 LED présence BT
8
9
10
G1
OFF ON Micro-interrupteurs de configuration
J8
Fonction TEST
F2
Fonction RAZ
T
Connecteurs de pile
C F1
R TORES - CT FLASH Pile
S2 S1/3Io S1 S1 BT-LV
N PH
Relais TS
J2
Boîtier voyant extérieur
J6 J5
Arrivée tores
2 x 1,5 mm2
4 x 1,5 mm2
Entrée BT
Fig. 5
2 D2160073-FR-EN-ES-05
Installation
Installation du boîtier
PE55061
Français
Installation de la signalisation extérieure
Fig. 6 Les signalisations du Flair 279 utilisent uniquement des LEDs.
d Ne jamais utiliser un voyant à ampoule.
b Trois types de signalisations extérieures au choix :
DE58523FR
PE55062
D2160073-FR-EN-ES-05 3
Installation
Montage “type A” (standard EDF)
DE55134-279
S2 S1/3Io S1 S1
A B C
Ih = 3 Io > 20 A
J1
T1 : tore MF1
T2 : tore homopolaire 4 x 1,5 mm2
a : tresse de masse d’un câble
b : tresse de mise à la terre
T1
c : taisceau précâblé S1
S2 S1 S1 S1
d : connecteur détrompé S2
e : cosse jaune Ø 12 mm
f : mise à la terre neutre S2 des tores. Fig. 10
d c f e a
S2 S1/3Io S1 S1
Montage “type B” A B C
Ih = 3 Io ≤ 20 A J1
4 x 1,5 mm2
T1
S1
S2 S1 S1 S1 S2
Fig. 11
d c T2 e a
A B C
Montage monotore S2 S1/3Io S1 S1
J1
2 x 1,5 mm2
S2 S1
Fig. 12
T2
e a
4 D2160073-FR-EN-ES-05
Installation
Installation des tores Alimentation
Mettre en place le ou les tores sur les 220/240 V - 50/60 Hz
câbles MT selon le type de montage Nota : le câblage de la basse tension sera
choisi (cf. schémas page 6). effectué conformément aux normes de
b Montages tritores sécurité locales (NFC 15-100 en France).
v Montage “type A” (standard EDF) b Passer le câble 230 V dans le passe-
câble situé en face du coupe-circuit J5/J6.
Français
3 tores MF1 + faisceau de raccordement
pour courant de défaut phase-terre b Relier le fil de phase à la borne “PH”.
Ih u 20 A. b Relier le fil neutre à la borne “N”.
v Montage “type B” L’alimentation 230 V doit être issue
2 tores MF1 + 1 tore homopolaire + de l’aval d’un coupe-circuit HPC
faisceau de raccordement pour courant (haut pouvoir de coupure)
de défaut phase-terre Ih y 20 A. pour les montages EDF.
d Important Lorsque la BT est connectée, la LED
Monter les 3 tores dans le même sens. témoin de présence BT doit être allumée.
Passer la tresse de masse d’un câble Dans le cas contraire, vérifier le coupe-
à l’intérieur du tore. circuit de la carte.
b Connecter la pile.
b Montage monotore Avant toute utilisation du Flair 279,
1 tore homopolaire. attendre 15 s après une connexion
ou reconnexion de la pile.
d Important En absence de BT, une autonomie
La tresse de mise à la terre doit passer de 400 h est assurée par la pile.
à l’intérieur du tore.
Toutes les tresses doivent être isolées. Remarque : lors d’un long stockage,
le pack de piles peut être passivé, et de
ce fait ne pas pouvoir fournir le courant
Sortie contact sec TS nécessaire au fonctionnement du Flair.
b Connecter s’il y a lieu la sortie J3 Pour le dépassiver :
au câble correspondant. v court-circuiter ses bornes par
Rappel : Travail V point 1 une résistance 47 ohms - 3 W,
Commun V point 2 v attendre, 10 à 30 s suivant l’état
Repos V point 3 des piles, une élévation décelable
Son pouvoir de coupure est de : de la température de résistance.
v 5 A/250 V alternatif,
v 5 A/ 30 V et 0,5 A/100 V continu.
Mise à la terre
Le circuit imprimé du détecteur Flair 279
ne nécessite pas de mise à la terre.
Il satisfait en effet sans mise à la terre
aux essais de CEM (Compatibilité
ElectroMagnétique).
D2160073-FR-EN-ES-05 5
Exploitation
Configuration des micro-interrupteurs
En gras, réglages
standard EDF Seuil courant de phase Imax
SW1 Imax 1 2
225 A OFF OFF
450 A ON OFF
575 A OFF ON
700 A ON ON
Configuration de la RAZ
Rappel sur position 7 SW1 7
Si la RAZ est positionnée sur “OFF” inactive,
le défaut est mémorisé. Inactif OFF
Le voyant va clignoter pendant 2 ou 4 h Actif ON
même si le détecteur est réalimenté en BT.
A utiliser avec alimentation BT secourue.
Temps max. signalisation
SW1 8
2h OFF
4h ON
6 D2160073-FR-EN-ES-05
Exploitation
Généralités b La signalisation s’arrête, J3 passe en
Le Flair 279 doit détecter le défaut avant position “repos”.
que la protection du départ MT concerné Refermer le boîtier en engageant
ne déclenche. Pour cela : d’abord les pattes inférieures du capot
b Les seuils Ih (courant homopolaire = 3 Io) dans le socle et rabattre jusqu’au
et Imax (courant entre phases) seront clipsage.
choisis immédiatement inférieurs à ceux
Français
de la protection du départ.
Test fonctionnel
b Le temps de prise en compte du défaut Ce test comprend les contrôles de Imax,
devra être inférieur au temps total Ih, temps.
d’ouverture de la protection (relais + Vous pouvez le réaliser si vous disposez
disjoncteur). d’une valise d’essai VALTEST.
Reportez-vous à la notice correspondante.
d Si ce temps est trop court, le Flair
va signaler tous les défauts, y compris Détection de défaut
les fugitifs. Si ce temps est trop long, Le courant de défaut est détecté lorsqu’il
le disjoncteur du départ HTA risque a dépassé le seuil 3 Io ou Imax pendant
de déclencher avant le signalement une durée u au temps de prise en compte.
du défaut. La signalisation visuelle se déclenche
et le contact J3 du relais TS passe en
Réglages position “travail” pendant 3 s minimum.
Voir tableaux
page 6 : Capot ouvert, positionner les micro- La période de clignotement évolue
en gras, réglages interrupteurs de configuration SW1 selon en fonction du temps T passé en
standard EDF les tableaux de la page 6. signalisation :
v 2 s (T < 2 h)
Test de fonctionnement v 3 s (T < 3 h)
Après configuration, procéder à un test v 4 s (T < 4 h)
de fonctionnement sur les 2 possibilités Le retour à l’état de veille est fonction de
de RAZ. la programmation RAZ et de la présence
ou absence de MT.
Position “ON”
RAZ par retour BT activée Position “ON”
(micro-interrupteur 7 de SW1 sur ON) RAZ par retour BT ou courant activée :
b Ouvrir l’arrivée BT par J5/J6 b Avec MT présente :
ou par le coupe-circuit F1. immédiat après le retour BT.
b Effectuer TEST/RAZ (bouton-poussoir). b Avec MT absente :
b La signalisation externe et la LED1 v à la fin de la durée programmée,
(défaut) clignotent, la sortie relais J3 v ou par action volontaire sur TEST/RAZ,
passe en position “travail”. v ou au retour stable de la MT.
d Si pendant les 3 premières secondes Position “OFF”
le clignotement de la LED est rapide, RAZ par retour BT ou courant inactivée :
la chaîne de détection est défectueuse. b A la fin de la durée programmée.
b Ou par action volontaire sur TEST/RAZ.
b Attendre 10 s, puis refermer l’arrivée BT.
b La signalisation s’arrête, J3 passe en
position “repos”.
Position “OFF”
RAZ par retour BT inactivée :
b Effectuer TEST/RAZ.
b La signalisation externe et la LED1
(défaut) clignotent, la sortie relais J3
passe en position “travail”.
b Attendre 10 s, puis effectuer TEST/RAZ.
D2160073-FR-EN-ES-05 7
Maintenance
Références des pièces détachées
b Coupe-circuit F1 (et rechange F2) :
In : 160 mA - Un : 250 V - Pdc : 1500 A
Dimensions : 5 x 20 mm.
b Pile : C2091348 - EDF 49 43 330 - CDI 59 965
Remplacement de la pile
b Enlever la pile usagée.
b Attendre 2 mn avant de placer la nouvelle pile.
b Mettre en place la nouvelle pile et attendre 15 s.
b Lancer un test (cf. p. 7) pour vérifier que tout fonctionne.
Autodiagnostics
b Chaîne de détection
Procéder à un test de fonctionnement comme décrit page 7.
b Etat de la pile
SW1-7 en position activée et BT présente (LD2 allumée).
Effectuer TEST/RAZ, si 6 s après le déclenchement du Flair 279,
un clignotement rapide apparaît pendant 3 s, la pile est en fin
de vie.
Dans ce cas, le contact J3 ne passe en position “travail” que 9 s
après le déclenchement.
Le remplacement de la pile doit être envisagé à court terme.
8 D2160073-FR-EN-ES-05
Dimensions
PE55063
Boîtier du détecteur Flair
Dimensions : 250 x 160 x 65 mm
Poids net : 812 g
Températures stockage : – 25 °C à + 70 °C
Fonctionnement : – 25 °C à + 55 ° C
Français
N.B. : l’appareil doit être stocké avec la pile
déconnectée.
5
DE55131
Voyant à LED
30 26 20 M22 x 1
12
50
62,5
D2160073-FR-EN-ES-05 9
Flair 279 contents
Installation 2
Box installation 3
Installation of the outdoor display unit 3
Installation of CTs 4
3 CT wirings 5
1 CT wiring 5
Dry contact output (SCADA) 5
Earthing 5
Power supply 5
Operation 6
Micro-switches configuration 6
General information 7
Settings 7
Working test 7
Functional test 7
Fault detection 7
Maintenance 8
Spare parts 8
Battery change 8
English
Self-diagnostics 8
Dimensions 9
D2160073-FR-EN-ES-05 1
Installation
DE58521EN
SW1 BP1
1 LD1 Fault LED
2
3 J4
4 opt.
5
J7 6
7 LD2 Low voltage presence LED
8
9
10
G1
OFF ON Micro-switches configuration
J8
TEST function
F2
Reset function
Battery connectors
T
C F1
R TORES - CT FLASH Battery
S2 S1/3Io S1 S1 BT-LV
N PH
SCADA output relay
J2
Outdoor indicator lamp box
J6 J5
CT incoming cable
2 x 1,5 mm2
4 x 1,5 mm2
Fig. 5
2 D2160073-FR-EN-ES-05
Installation
Box installation
PE55061
Open the unit using the clips at the top of the box.
For this (fig. 6):
b Push the clips outwards (A) separating the base
from the cover (B) and,
b Fix the base with the screws.
Green
Common
Red
v a standard outdoor box (fig. 7), wall mounting with two 4 mm
diameter screws,
v an indicator lamp to be screwed in for thin walls y 6 mm (fig. 8),
v an anti-vandalism box (fig. 9).
or b mount the anti-vandalism box:
v drill a 12 mm Ø hole in the wall for the light guide
Common Red
to pass through,
v install the light guide, mount the fixing lug, locking it against
English
Fig. 7
the guide, position the unit.
The end of the light guide must be level with the outside wall.
If necessary, cut the external side of the stud and surface
the cut edge with abrasive (size grading 400).
DE55132
v drill the mounting hole and fix the lug (plug + screw).
Connection
A double-strand conductor or telephone cable with a 2.5 mm2
section can be used for a maximum length of 178 m.
Fig. 8 b Respect the polarities indicated on the Flair 279 box
and on the display unit.
b Check that the display unit is operating correctly
Fixing bracket by simulating a fault on the detector and opening
the low voltage (see tests, page 7).
If the indicator lamp does not flash, either the polarities
have not been respected or the LED is faulty.
DE55133
D2160073-FR-EN-ES-05 3
Installation
“Type A” wiring
DE55134-279
S2 S1/3Io S1 S1
A B C
Ih = 3 Io > 20 A
J1
T1: MF1 CT
T2: earth CT 4 x 1,5 mm2
a: cable earthing strap
b: earthing strap
T1
c: pre-wired bundle S1
S2 S1 S1 S1
d: polarised connector S2
e: yellow 12 mm Ø socket
f: neutral earthing S2 for CTs. Fig. 10
d c f e a
S2 S1/3Io S1 S1
“Type B” wiring A B C
Ih = 3 Io ≤ 20 A J1
4 x 1,5 mm2
T1
S1
S2 S1 S1 S1 S2
Fig. 11
d c T2 e a
A B C
1-CT wiring S2 S1/3Io S1 S1
J1
2 x 1,5 mm2
S2 S1
Fig. 12
T2
e a
4 D2160073-FR-EN-ES-05
Installation
Installation of CTs Power supply
Install the CT(s) on the medium voltage 220/240 V - 50/60 Hz
cables according to the type of wiring Note: low voltage wiring is carried out in
chosen (see diagrams on page 6). accordance with local safety standards.
b 3-CT wiring b Insert the 230-V cable into the cable
v “Type A” wiring bushing located opposite circuit breaker
Three MF1 CTs + connection bundle J5/J6.
for phase-earth fault current Ih u 20 A. b Connect the phase conductor to
v “Type B” wiring connector “PH”.
Two MF1 CTs + earth CT + connection b Connect the neutral wire to
bundle for phase-earth fault current connector “N”.
Ih y 20 A. The 230-V power must be supplied
d Important downstream of a HPC (high breaking
Mount the three CTs in the same direction. capacity) circuit breaker for EDF wiring.
Put the cable earthing strap inside the CT. When the low voltage is connected,
the low voltage presence indicator LED
b 1-CT wiring must be lit. If this is not the case,
One earth CT. check the board circuit breaker.
b Connect the battery.
d Important Whenever using the Flair 279,
The earthing strap must go inside the CT.
English
wait 15 s after connecting
All straps must be insulated. or reconnecting the battery.
If there is no low voltage, the battery
ensures autonomous operation
Dry contact output (SCADA)
for 400 hours.
b If necessary, connect output J3
to the corresponding cable. Remark: in case of long stocking,
Note: Work V point 1 the battery pack might get “passivated”,
Common V point 2 and therefore not be able to provide
Reset V point 3 the current needed by the Flair.
It has a breaking capacity of: In order to “depassivate”:
v 5 A/250 V AC, v short-circuit its terminals through
v 5 A/30 V and 0.5 A/100 V DC. a 47 Ohms - 3 W resistor,
v wait 10 to 30 s, according to the battery
state, for a detectable increase
Earthing of the resistor temperature.
The printed circuit of the Flair 279 indicator
does not require an earth connection.
It satisfies the CEM (ElectroMagnetic
Compatibility) tests without an earth
connection.
D2160073-FR-EN-ES-05 5
Operation
Micro-switches configuration
In bold, factory
settings Imax phase current threshold
SW1 Imax 1 2
225 A OFF OFF
450 A ON OFF
575 A OFF ON
700 A ON ON
RESET configuration
Position 7 reminder SW1 7
If the RESET is positioned to inactive “OFF”,
the fault is stored. Inactive OFF
The indicator lamp will flash for two or four Active ON
hours even if the indicator is once again
supplied with low voltage.
To be used with emergency low voltage Max. signalling time
power supply. SW1 8
2h OFF
4h ON
6 D2160073-FR-EN-ES-05
Operation
General information of the cover onto the base and pushing it
The Flair 279 must detect the fault before down until it snaps on.
the relevant medium voltage output
protection can be triggered.
Functional test
For this: This test includes Imax, Ih and time
b The Ih (homopolar current = 3 lo) checks.
and Imax (current between phases) This test can be performed with
thresholds are chosen to be immediately a VALTEST portable testing unit.
below the output protection thresholds. Please refer to the relevant manual.
b The fault processing time should be
shorter than the total on-period
Fault detection
of the protection (relay + circuit breaker). The fault current is detected when
it exceeds the 3 Io or Imax threshold
d If the set time is too short, the Flair for a duration u the processing time.
will trigger for all faults, including The visual signal is triggered and
transient faults. If the set time is too long, contact J3 of SCADA output moves
the Flair will not signal the fault. into “work” position for 3 s minimum.
The flashing period changes according
to the signalling time T:
Settings v 2 s (T < 2 h)
With the cover open, position the SW1 v 3 s (T < 3 h)
English
configuration micro-switches according v 4 s (T < 4 h)
to the tables on page 6. The return to standby state depends
on the RESET programming and
Working test on the presence or absence of MV.
After configuration, perform an operational
test on the two possibilities of RESET. “ON” position
RESET by activated LV or current return:
“ON” position b With MV:
RESET by activated low voltage return: immediately after the LV return.
b Open the low voltage incoming cable b Without MV:
with J5/J6 or the F1 circuit breaker. v at the end of the duration programmed,
b Perform TEST/RESET. v by activating TEST/RESET voluntarily,
b The outdoor display unit and LED1 v or at the stable return of the MV.
(fault) flash, relay output J3 moves into
“work” position. “OFF” position
RESET by inactivated LV or current return:
d If the LED flashes quickly for the first b At the end of the duration programmed.
three seconds, the detection chain is
b Or by activating TEST/RESET
faulty.
voluntarily.
b Wait 10 seconds, then close the low
voltage incoming cable.
b The signalling stops, J3 moves into
“rest” position.
“OFF” position
RESET by inactivated low voltage return:
b Perform TEST/RESET.
b The outside display unit and LED1
(fault) flash, relay output J3 moves into
“work” position.
b Wait 10 s, then perform TEST/RESET.
b The signalling stops, J3 moves into
“rest” position.
Shut the box by latching the lower lugs
D2160073-FR-EN-ES-05 7
Maintenance
Spare part references
b Fuse F1 (and replacement F2):
In: 160 mA - Un: 250 V - Pdc: 1500 A
Dimensions: 5 x 20 mm.
b Battery: C2091348 - EDF 49 43 330 - CDI 59 965
Battery replacement
b Remove the used battery.
b Wait two minutes before inserting the new battery.
b Insert the new battery and wait 15 s.
b Start the test (see p. 7) to check that it is operating correctly.
Self-diagnostics
b Detection chain
Perform an operational test as described on page 7 according.
b Battery status
SW1-7 in activated position and low voltage present (LD2 lit).
Perform TEST/RESET, if six seconds after the Flair 279
is triggered, there is rapid flashing for three seconds, the battery
is at the end of its life. In this case, contact J3 only moves
into “work” position nine seconds after the triggering.
Battery replacement must be planned in the short term.
8 D2160073-FR-EN-ES-05
Dimensions
PE55063
Flair detector box
Dimensions: 250 x 160 x 65 mm
Net weight: 812 g
Temperatures storage: – 13°F to + 158°F
Operation: – 13°F to + 131°F
N.B.: the unit must be stored with
the battery disconnected.
English
Standard LED indicator lamp box
5
DE55131
30 26 20 M22 x 1
12
50
62,5
D2160073-FR-EN-ES-05 9
Tabla Flair 279
Instalación 2
Instalación de la caja 3
Instalación de la caja externa de señalización 3
Instalación de los sensores 4
Montajes con 3 sensores 5
Montaje con 1 sensor 5
Salida contacto seco TS 5
Conexión a tierra 5
Alimentación 5
Explotación 6
Micro-interruptores de configuración 6
Generalidades 7
Ajustes 7
Test de funcionamiento 7
Test funcional 7
Detección de fallas 7
Mantenimiento 8
Piezas de recambio 8
Sustitución de la pila 8
Auto-diagnósticos 8
Dimensiones 9
Español
subterráneas o aéro-subterráneas. Este manual se ha elaborado
con objeto de contestar a todas las preguntas que pueda
plantearse sobre sus indicadores luminosos.
Léalo atentamente. No dude en ponerse en contacto con nosotros
en caso de dudas.
D2160073-FR-EN-ES-05 1
Instalación
DE58521ES
SW1 BP1
1 LD1 LED indicador de fallas
2
3 J4
4 opt.
5
J7 6
7 LD2 LED testigo de presencia de BT
8
9
10
G1
OFF ON Micro-interruptores de configuración
J8
Función TESTO
F2
Función PAC
Conectores de pila
T
C F1
R TORES - CT FLASH Pila
S2 S1/3Io S1 S1 BT-LV
N PH
Relés TS
J2
Caja de señalización externa
J6 J5
Entrada BT
Fig. 5
2 D2160073-FR-EN-ES-05
Instalación
Instalación de la caja
PE55061
Español
una falla en el indicador mediante y abertura de la BT
(cf. tests página 7).
DE55133
D2160073-FR-EN-ES-05 3
Instalación
Montaje de “tipo A”
DE55134-279
S2 S1/3Io S1 S1
A B C
Ih = 3 Io > 20 A
J1
T1: sensor de corriente MF1
T2: sensor de tierra 4 x 1,5 mm2
a: trenzado de masa de un cable
b: trenzado de conexión a tierra
T1
c: haz precableado S1
S2 S1 S1 S1
d: conector con ranura indexada S2
e: terminal amarillo Ø 12 mm
f: conexión a tierra neutra S2 de los Fig. 10
sensores de corriente.
d c f e a
S2 S1/3Io S1 S1
Montaje de “tipo B” A B C
Ih = 3 Io ≤ 20 A J1
4 x 1,5 mm2
T1
S1
S2 S1 S1 S1 S2
Fig. 11
d c T2 e a
A B C
Montaje con un sensor S2 S1/3Io S1 S1
J1
2 x 1,5 mm2
S2 S1
Fig. 12
T2
e a
4 D2160073-FR-EN-ES-05
Instalación
Instalación de los sensores Alimentación
Coloque el o los sensores de corriente 220/240 V - 50/60 Hz
en los cables MT según el tipo de montaje Nota: el cableado de baja tensión
escogido (cf. esquemas de las página 6). se efectuará de acuerdo con las normas
b Montajes con tres sensores de seguridad locales.
v Montaje de “tipo A” b Pase el cable 230 V por el pasacables
3 sensores de corriente MF1 situado enfrente del cortacircuito J5/J6.
+ haz de conexión para corriente b Conecte el hilo de fase al borne “PH”.
de defecto fase-tierra Ih u 20 A. b Conecte el hilo neutro al borne “N”.
v Montaje de “tipo B” La alimentación 230 V debe estar situada
2 sensores de corriente MF1 después de un fusible HPC (alta potencia
+ 1 sensor de corriente a tierra de corte) para los montajes EDF.
+ haz de conexión para corriente Cuando la BT está conectada, el LED
de defecto fase-tierra Ih y 20 A. testigo de presencia de BT debe estar
d Importante encendido. Si no es así, compruebe
Monte los 3 sensores de corriente el fusible de la tarjeta.
en el mismo sentido. b Conecte la pila.
Pase el trenzado de masa de un cable Cada vez que utilice Flair 279,
por dentro del sensor. espere 15 s tras una conexión
o reconexión de la pila.
b Montaje con un sensor Cuando no hay BT, la pila garantiza
1 sensor de corriente a tierra. una autonomía de 400 h.
d Importante Nota: después de quedar sin funcionar
El trenzado de conexión a tierra debe la batería puede ser “pasivada”, en este
pasar por dentro del sensor laminado. caso no dara el corriente suficiente para
Todos los trenzados deben estar aislados. el funcionamiento del Flair.
Para poner in orden de marcha la batería:
v hacer un corte-circuito entra sus bornes
Salida contacto seco TS con una resistencia de 47 Ohms - 3 W,
b Conecte, si es necesario, la salida J3 v esperar 10 o 30 s según el estado
al cable correspondiente. de la batería una elevación sensible
Nota: Trabajo V punto 1 de la temperatura de la resistencia.
Común V punto 2
Español
Reposo V punto 3
Su poder de corte es de:
v 5 A/250 V alterna,
v 5 A/ 30 V y 0,5 A/100 V continua.
Conexión a tierra
El circuito impreso del indicador Flair 279
no requiere conexión a tierra.
Supera, sin conexión a tierra,
las pruebas de CEM (Compatibilidad
ElectroMagnética).
D2160073-FR-EN-ES-05 5
Explotación
Micro-interruptores de configuración
In bold, factory
settings Umbral corriente de fase Imax
SW1 Imax 1 2
225 A OFF OFF
450 A ON OFF
575 A OFF ON
700 A ON ON
Configuración de la PAC
Nota sobre la posición 7 SW1 7
Si la PAC se coloca en “OFF” inactivo, el defecto
se memoriza. Inactivo OFF
El piloto luminoso parpadea durante 2 o 4 h, Activo ON
incluso si el indicador vuelve a alimentarse
con BT.
Se utiliza con alimentación de BT ininterrumpida. Tiempo máx. señalización
SW1 8
2h OFF
4h ON
6 D2160073-FR-EN-ES-05
Explotación
Generalidades Cierre la caja acoplando primero las
Flair 279 debe detectar el defecto patillas inferiores de la cubierta en la base
antes de que la protección inicial MT y repliegue hasta que se grape.
correspondiente se active. Para ello:
b Se seleccionarán los umbrales Ih
Test funcional
(corriente homopolar = 3 Io) y Imax Este test incluye los controles de Imax,
(corriente entre fases) inmediatamente Ih y tiempo.
inferiores a los de la protección inicial. Puede realizarlo si dispone de una maleta
b El tiempo de integración del defecto de prueba VALTEST.
debe ser inferior al tiempo total de Remítase al manual correspondiente.
apertura de la protección (relé + disyuntor).
Detección de fallas
d Si el tiempo es muy bajo, el Flair La corriente de defecto se detecta cuando
va a detectar todos los defectos, supera el umbral 3 Io o Imax durante un
incluyendo los defectos transitorios. periodo de tiempo u al tiempo
Si el tiempo es muy largo, el Flair de integración.
no va a parpadear. La señalización visual se activa y el
contacto J3 del relé TS pasa a la posición
“trabajo” durante 3 s como mínimo.
Ajustes El periodo de parpadeo varia en función
Con la cubierta abierta, coloque los micro- del tiempo T pasado en señalización:
interruptores de configuración SW1 de v 2 s (T < 2 h)
acuerdo con los cuadros de la página 6. v 3 s (T < 3 h)
v 4 s (T < 4 h)
Test de funcionamiento La vuelta al estado de espera depende
Tras la configuración, realice una prueba de la programación PAC y de la presencia
de funcionamiento en las 2 posibilidades o ausencia de MT.
de la PAC.
Posición “ON”
Posición “ON” PAC mediante retorno de BT o del
PAC mediante retorno de BT activada: corriente activada:
b Abra la llegada BT por J5/J6 o mediante b Con MT presente:
el fusible F1. inmediato tras la vuelta BT.
b Efectúe TEST/PAC. b Con MT ausente:
b La señalización externa y el LED1
Español
v al final del periodo de tiempo
(falla) parpadean, la salida relé J3 vuelve programado,
a la posición “trabajo”. v o mediante acción voluntaria
d Si durante los 3 primeros segundos en TEST/PAC,
el parpadeo del LED es rápido, la cadena v o a la vuelta estable de la MT.
de detección está averiada.
Posición “OFF”
b Espere 10 s y cierre la llegada de BT. PAC mediante vuelta BT o del corriente
b La señalización se para, J3 vuelve desactivada:
a la posición “reposo”. b Al final del periodo de tiempo
Posición “OFF” programado.
PAC mediante vuelta BT desactivada: b O mediante acción voluntaria
b Efectúe TEST/PAC. en TEST/PAC.
b La señalización externa y el LED1
(falla) parpadean, la salida relé J3 vuelve
a la posición “trabajo”.
b Espere 10 s y cierre la llegada de BT.
b La señalización se para, J3 vuelve
a la posición “reposo”.
D2160073-FR-EN-ES-05 7
Mantenimiento
Referencias de las piezas de recambio
b Fusible F1 (y recambio F2):
In: 160 mA - Un: 250 V - Pdc: 1500 A
Dimensiones: 5 x 20 mm.
b Pila: C2091348 - EDF 49 43 330 - CDI 59 965
Sustitución de la pila
b Retire la pila gastada.
b Espere 2 min antes de colocar la pila nueva.
b Coloque la pila nueva y espere 15 s.
b Inicie un test (cf. página 7) para comprobar que todo
funciona bien.
Auto-diagnósticos
b Cadena de detección
Realice una prueba de funcionamiento como se describe
en la página 7.
b Estado de la pila
SW1-7 en posición activada y BT presente (LD2 encendido).
Efectúe TEST/PAC, si 6 s después de la activación de Flair 279
aparece un parpadeo rápido durante 3 s, la pila está gastada.
En este caso, el contacto J3 sólo se coloca en posición “trabajo”
9 s después de la activación.La pila debe sustituirse a corto plazo.
8 D2160073-FR-EN-ES-05
Dimensiones
PE55063
Caja del indicador de fallas Flair
Dimensiones: 250 x 160 x 65 mm
Peso neto: 812 g
Temperaturas almacenamiento:
– 25 °C a + 70 °C
Funcionamiento: – 25 °C a + 55 ° C
N.B.: el aparato debe almacenarse
con la pila desconectada.
Español
Caja de indicadores anti-vandalismo
5
DE55131
30 26 20 M22 x 1
12
50
62,5
D2160073-FR-EN-ES-05 9
Schneider Electric Industries SAS
Schneider Electric Telecontrol En raison de l’évolution des normes et du matériel, les caractéristiques
839 Chemin des Batterses indiquées par les textes et les images de ce document ne nous engagent
Z.I. Ouest qu’après confirmation par nos services.
01700 St Maurice de Beynost As standards, specifications and designs change from time to time,
Tel.: +33 (0)4 78 55 13 13 please ask for confirmation of the information given in this publication.
Fax: +33 (0)4 78 55 50 00
Debido a la evolución de las normas y del material, las características
http://www.schneider-electric.com y dimensiones indicadasen el texto y las imágenes nos comprometen
E-mail: [email protected] solamente previa confirmación de nuestros servicios.
This document has been
printed on ecological paper
D2160073-FR-EN-ES-05 07-2008