UNIVERSIDAD TECNOLÓGICA DE PANAMÁ

FACULTAD DE INGENIERÍA CIVIL


LICENCIATURA EN INGENIERÍA CIVIL
DEPARTAMENTO DE MECÁNICA ESTRUCTURAL
PUENTES Y ESTRUCTURAS ESPECIALES

PROYECTO No 2

DISEÑO DE HOSPITAL
REP 2021

UBICACIÓN

SAN ANTONIO – PANAMÁ

PROFESOR:
Ing. Edwin Lewis

ESTUDIANTES:
Mata Antonio, 8-936-1518
Ortega José, 2-735-1888
Rosario Rafael,

GRUPO:
1IC –

FECHA DE ENTREGA:
2 de noviembre, 2023

SEGUNDO SEMESTRE 2023

1
CONTENIDO

CONTENIDO
INTRODUCCIÓN...................................................................................................................................................3
UBICACIÓN............................................................................................................................................................3
CATEGORÍA DE OCUPACIÓN:..............................................................................................................................3
PROPIEDADES DE MATERIALES.........................................................................................................................5
SISTEMA RESISTENTE A CARGA LATERAL.....................................................................................................5
DIMENSIONES PRELIMINARES DE ELEMENTOS............................................................................................6
FACTOR DE IMPORTANCIA..................................................................................................................................6
ESPECTRO DE DISEÑO...........................................................................................................................................6
DESCRIPCIÓN GENERAL DEL PROYECTO........................................................................................................7
PARÁMETROS DE ACELERACIÓN DE PERÍODO CORTO Y DE PERÍODO DE 1 SEG...............................11
COEFICIENTES DE SITIO B.................................................................................................................................11
PARÁMETROS DE ESPECTRO DE RESPUESTA DE ACELERACIÓN AJUSTADOS POR COEFICIENTES
DE SITIO..................................................................................................................................................................12
PARÁMETROS DE ESPECTRO DE RESPUESTA DE ACELERACIÓN DE DISEÑO.....................................12
MÉTODO DE LA FUERZA LATERAL EQUIVALENTE....................................................................................16
ANÁLISIS DE CARGAS DE GRAVED..........................................................................................................16
DIMENSIONES DEL EDIFICIO.....................................................................................................................17
CÁLCULO DEL PESO TOTAL DEL EDIFICIO..........................................................................................17
CÁLCULO DEL PERÍODO FUNDAMENTAL APROXIMADO................................................................19
COEFICIENTE SÍSMICO................................................................................................................................19
CORTANTE BASAL..........................................................................................................................................22
CÁLCULO DE LA FUERZA LATERAL EQUIVALENTE.........................................................................22
CÁLCULO DEL CENTRO DE MASAS..........................................................................................................22

2
INTRODUCCIÓN

El presente informe tiene como objetivo dar a conocer los resultados del Proyecto “DISEÑO SE
EDIFICIO DE USO HOESPITALARIO”, el mismo fue desarrollado por un grupo de estudiantes de la
carrera de Ingeniería Civil de la Universidad Tecnológica de Panamá.
Este informe tiene la finalidad de datificar todo el proceso de diseño tomando en cuenta las
consideraciones establecidas por el profesor de la materia de Puentes. Considerando que este edificio se
desarrollara en un poblado cercano a áreas de la Ciudad de Panamá se tomara en cuenta todos los
procesos y recomendaciones que establece el REP – 2021, se evaluó los diseños sismorresistente como
primer instancia para poder desempeñar el cálculo de las diferentes partes del edificio, muy importante
dejar claro que este edificio cuenta con 7 plantas las cuales se evaluaron una por una, con su respectivo
cálculo de losas, vigas, columnas y área de elevador y escaleras.

OBJETIVO
El objetivo principal de este proyecto fue elaborar el diseño estructural del Sistema Resistente a la Carga
Lateral de un Hospital de acuerdo con lo establecido en el Reglamento Estructural Panameño 2021,
ASCE 7-05 y ACI 318-19.

UBICACIÓN
 SAN ANTONIO – PANAMÁ

CATEGORÍA DE OCUPACIÓN:
Para esté proyecto se ha considerado una ocupación de tipo HOSPITAL (categoría IV), la cual es la mas
critica de todas en el punto de amplificación de las cargas de diseño.
table 1-1 occupancy category of buildings and other structures for flood, wind, snow, earthquake,
and ice loads.

3
4
PROPIEDADES DE MATERIALES
 Resistencia a la Compresión del Concreto a los días f’c = 5,000 psi
 Acero ASTM A706 Grado 60 fy = 60,000 psi

SISTEMA RESISTENTE A CARGA LATERAL


 Opción No.1: Marcos Especiales Momento Resistente de Concreto Reforzado

5
o Marcos Perimetrales
o Todos los Marcos
 Opción No.2: Muro de Cortante
o Zona de Elevador y Escalera
o Zona de Elevador y Escalera y Perímetro
 Opción No.3: Sistema Dual - Marcos Especiales Momento Resistente y Muro de Cortante de
Concreto Reforzado

DIMENSIONES PRELIMINARES DE ELEMENTOS


 Vigas b = 400 mm h = 600 mm
 Columnas b = 600 mm h = 600 mm
 Muro de Cortante t = 300 mm de espesor
 Losa t = 200 mm de espesor

FACTOR DE IMPORTANCIA.
El factor de importancia es definido en base a la sección 11.5 del AISC 7-05 y el mismo depende
también de uso que se le vaya a dar a la estructura o tipo de ocupación.

ESPECTRO DE DISEÑO
El espectro de diseño con los parámetros de aceleración de período corto y de período de 1 seg. Estos
valores se pueden obtener de las gráficas de aceleraciones espectrales disponibles en el REP 2014 para 1
en 2475 años.

ALCANCE
El estudiante deberá presentar un informe técnico donde se evaluarán los siguientes conceptos:
1. Categoría de Ocupación, Factor de Importancia, Espectro de Diseño (10 Puntos)
2. Cálculo de la Fuerza Sísmica – Método de la Fuerza Lateral Equivalente (10 Puntos)
3. Planteamiento de los Sistemas Resistentes a Carga Lateral (30 Puntos)
4. Control de Desplazamientos Laterales (10 Puntos)
5. Diseño Sísmico de Vigas y Columnas – Código ACI 318-19 (10 Puntos)
6. Diseño Sísmico de Muro de Cortante – Código ACI 318-19 (10 Puntos)

6
7. Sustentación Técnica ante el Profesor (20 Puntos)

Grupo Sitio Ubicación Número de Pisos


1 B San Antonio 7

Importante señalar que durante esta primera fase solo se realizaran los primeros 4 puntos
señalados.

Desarrollo del proyecto

DESCRIPCIÓN GENERAL DEL PROYECTO

El proyecto a realizarse estará ubicado en la comunidad de San Antonio, Panamá, por lo que se tomará en cuanta
el mapa sismo resistente de la republica y se ubicará la misma

Aceleraciones máximas (Ss) de sismo en Panamá

7
REP – 2021

Aceleraciones máximas (S1) de sismo en Panamá


REP – 2021

Ubicamos la comunidad asignada para tener la referencia en cuanto a las aceleraciones máximas (ss y s1) a las
resistencias del sino máximo que debemos considerar

8
Comunidad de San Antonio, Panamá
https://maps.app.goo.gl/TgVWN238AtMg6nKA7

Comunidad de San Antonio, Panamá


https://maps.app.goo.gl/TgVWN238AtMg6nKA7

Considerando la ubicación procedemos a determinar la resistencia.

9
10
Aceleraciones máximas (Ss) de sismo en Panamá
REP – 2021
Aceleraciones máximas (S1) de sismo en Panamá
REP – 2021

PARÁMETROS DE ACELERACIÓN DE PERÍODO CORTO Y DE PERÍODO DE 1 SEG

Ubicación = San Antonio

Ss = 1.02
S1 = 0.39

11
COEFICIENTES DE SITIO B

Tabla 11.4-1 para el cálculo de Coeficiente Ss

Tabla 11.4-2 para el cálculo de Coeficiente S1

Fa = 1.00 Ver Tabla 11.4-1 - ASCE 7-05


Fv = 1.00 Ver Tabla 11.4-2 - ASCE 7-05

PARÁMETROS DE ESPECTRO DE RESPUESTA DE ACELERACIÓN AJUSTADOS POR


COEFICIENTES DE SITIO

12
Coeficientes del sitio máximo ajustado considerado los parámetros de aceleración de respuesta espectral de
terremoto (MCE). La aceleración de la respuesta espectral del MCE por períodos cortos (Sws) y a 1s (Smi),
ajustados para efectos de Clase de Sitio, serán determinado por las ecuaciones.

Dónde
Ss = la aceleración de la respuesta espectral MCE mapeada en corto períodos determinados de conformidad con
la Sección 1 1.4.1
Si = la aceleración de la respuesta espectral MCE mapeada en un período de Es según lo determinado de
conformidad con la Sección 11.4.1
donde los coeficientes de sitio Fa y F se definen en las Tablas 11.4-1 y 11.4.2, respectivamente. Donde el
procedimiento de diseño simplificado.

SMS = 1.02 Ecuación 11.4-1 - ASCE 7-05


SM1 = 0.39 Ecuación 11.4-2 - ASCE 7-05

PARÁMETROS DE ESPECTRO DE RESPUESTA DE ACELERACIÓN DE DISEÑO

13
Diseño de parámetros de aceleración espectral. Diseño Parámetro de aceleración de la respuesta
espectral de un terremoto en PC cortas río y en el período de 1 s,se determinará a partir de las Ecs. 11,4-
3 y 11,4-4, respectivamente. Cuando la alternativa simplificada Se utiliza el procedimiento de diseño de
la Sección 12,14, el valor de Sps deberá determinarse de acuerdo con la Sección 12.144.8.1, y el valor
para Spa no se determinará

SDS = 0.680 Ecuación 11.4-3 - ASCE 7-05


SD1 = 0.260 Ecuación 11.4-4 - ASCE 7-05

Espectro de Respuesta de Diseño

To = 0.08 seg
Ts = 0.38 seg
Espectro de respuesta de diseño.

14
SD1 T L
Sa =
T
¿Dónde hay una respuesta de diseño y diseño?
El espectro es requerido por esta norma y el terreno específico de la situación. No se utilizan procedimientos de
movimiento, el espectro de respuesta del diseño de la curva se desarrollará como se indica en la Fig. 11.4-1 y
como sigue:
1. Para períodos menores que To, la respuesta espectral de diseño se acelera. La operación, Sa, se tomará
como está dada por la ecuación. 11.4-5:

(
Sa =S DS 0.4+ 0.6
T
T0 )
2. Para periodos mayores o iguales a To y menores o iguales lotes la aceleración de respuesta espectral de
diseño, Sa. será tomado igual a Sps

3. Para períodos mayores que Ts y menores o iguales a Ty. La aceleración de la respuesta espectral de
diseño, se tomará como dado por la ecuación. 1 14-6:
SD1
Sa =
T
4. Por periodos mayores que Tt. Sa se considerará original por (11.4-7)
SD1 T L
Sa =
T

T (seg) Sa (g) Cs

15
0 0.272 0.128
0.08 0.680 0.128 To
0.38 0.680 0.128 Ts
0.65 0.400 0.075
0.70 0.371 0.070
0.80 0.325 0.061
0.90 0.289 0.054
1.00 0.260 0.049
2.00 0.130 0.045
3.00 0.087 0.045
4.00 0.065 0.045
5.00 0.052 0.045
6.00 0.043 0.045
7.00 0.037 0.045
8.00 0.033 0.045
9.00 0.029 0.045
10.00 0.026 0.045 TL
11.00 0.021 0.045
12.00 0.018 0.045
13.00 0.015 0.045
14.00 0.013 0.045
15.00 0.012 0.045

Espectro de Respuesta de Diseño


0.800

0.700

0.600

0.500

0.400
Sa

0.300

0.200

0.100

0.000
0 2 4 6 8 10 12 14 16
T (seg)

Sa (g) Cs

16
MÉTODO DE LA FUERZA LATERAL EQUIVALENTE

ANÁLISIS DE CARGAS DE GRAVED

Datos de Losa
tLosa = 0.20 m
gConcreto = 2,400 kg/m3
Peso de la Losa: 480.00 kg/m2

Carga Muerta
Losa = 480.00 kg/m2
Paredes = 163.00 kg/m2
Baldosas = 145.00 kg/m2

17
Cielo Raso = 12.00 kg/m2
800.00 kg/m2

Carga Viva
Residencial = 390.00 kg/m2

Carga de Servicio
w= 1,190.00 kg/m2

Carga Última
wU = 1,584.00 kg/m2

Factor de Carga = 1.331092437

Relación Carga Muerta/Carga Última = 0.505

Relación Carga Viva/Carga Muerta = 0.4875

Verificación CV < CM = Satisfactorio

0.9D = 720.00 kg/m2


0.5D = 400.00 kg/m2
1.2D + 0.5L = 1,155.00 kg/m2

DIMENSIONES DEL EDIFICIO

Largo = 25.90 m
Ancho = 18.90 m
Largo Elevador = 4.90 m
Ancho Elevador = 4.20 m

CÁLCULO DEL PESO TOTAL DEL EDIFICIO

 Cálculo del Peso de Losa

Peso Propio de Losa = 800.00 kg/m2


Largo = 25.90 m
Ancho = 18.90 m
Largo Elevador = 4.90 m
Ancho Elevador = 4.20 m
Área de Losa = 468.93 m2
Peso de Losa = 375,144.00 kg

18
 Cálculo del Peso de Vigas

gConcreto = 2,400 kg/m3


h= 0.60 m
b= 0.40 m
Peso de Vigas = 76,070.40 kg

 Cálculo del Peso de Columnas

gConcreto = 2,400 kg/m3


h= 0.60 m
b= 0.60 m
l= 3.10
n= 16
Peso de Columnas = 34,560.00 kg

19
Peso Total por Planta = 505,531.20 kg
Niveles = 7 plantas
Peso Total del Edificio = 3,538,718.40 kg
Peso Total del Edificio = 3,538.72 Ton

Tipo de Estructura = Marco de Momento Resistente de Concreto


Ct = 0.0488
x= 0.75

CÁLCULO DEL PERÍODO FUNDAMENTAL APROXIMADO


Altura del Edificio = 12.40 m
x
Ta = Cthn
Ta = 0.322 seg

COEFICIENTE SÍSMICO
 Cálculo del Coeficiente Sísmico de Respuesta

20
Ts = Sd1/Sds 0.343434343
SS = 1.98
S1 = 0.68
Fa = 1
Fv = 1
SMS = 1.98
SM1 = 0.68
SDS = 1.32
SD1 = 0.45
R= 7
I= 1

Cs = 0.189 Ecuación 12.8-2 - ASCE 7-05

TL = 10 seg

21
Cu = 1.4 seg
T= 0.451 seg
Cs = 0.143 Máximo
Cs = 0.01 Mínimo
Cs = 0.044SDSI REP 2014
Cs = 0.058
Cs = 0.143

22
CORTANTE BASAL

V= Cs W
V= 507.63 Ton

CÁLCULO DE LA FUERZA LATERAL EQUIVALENTE

Nivel Wi (Ton) h (m) hi (m) Wi*hik Cvx Fx (Ton) Vx (Ton) Mx (m-Ton)


700 508.93 3.10 21.70 16,059.74 0.509 82.61 0 0
600 508.93 3.10 18.60 13,509.69 0.428 69.49 82.61 256.08
500 508.93 3.10 15.50 11,011.07 0.349 56.64 152.09 727.57
400 508.93 3.10 12.40 8,572.89 0.272 44.10 208.73 1,374.63
300 508.93 3.10 9.30 6,208.49 0.197 31.93 252.83 2,158.39
200 508.93 3.10 6.20 3,939.74 0.125 20.26 284.76 3,041.15
100 508.93 3.10 3.10 1,810.54 0.057 9.31 305.02 3,986.73
0 508.93 3.10 0.00 0.00 0.000 0.00 314.34 4,961.18
4,071.44 61,112.17 314.34

CÁLCULO DEL CENTRO DE MASAS

Peso Propio de Columnas = 864.00 kg/m

Columnas X (m) Y (m) L (m) W (kg) W*X (kg-m) W*Y (kg-m)


1 0.00 0.00 2.50 2,160.00 0.00 0.00
2 7.00 0.00 2.50 2,160.00 15,120.00 0.00
3 11.90 0.00 2.50 2,160.00 25,704.00 0.00
4 18.90 0.00 2.50 2,160.00 40,824.00 0.00

23
5 0.00 8.00 2.50 2,160.00 0.00 17,280.00
6 7.00 8.00 2.50 2,160.00 15,120.00 17,280.00
7 11.90 8.00 2.50 2,160.00 25,704.00 17,280.00
8 18.90 8.00 2.50 2,160.00 40,824.00 17,280.00
9 0.00 12.20 2.50 2,160.00 0.00 26,352.00
10 7.00 12.20 2.50 2,160.00 15,120.00 26,352.00
11 11.90 12.20 2.50 2,160.00 25,704.00 26,352.00
12 18.90 12.20 2.50 2,160.00 40,824.00 26,352.00
13 0.00 19.40 2.50 2,160.00 0.00 41,904.00
14 7.00 19.40 2.50 2,160.00 15,120.00 41,904.00
15 11.90 19.40 2.50 2,160.00 25,704.00 41,904.00
16 18.90 19.40 2.50 2,160.00 40,824.00 41,904.00
17 0.00 25.90 2.50 2,160.00 0.00 55,944.00
18 7.00 25.90 2.50 2,160.00 15,120.00 55,944.00
19 11.90 25.90 2.50 2,160.00 25,704.00 55,944.00
20 18.90 25.90 2.50 2,160.00 40,824.00 55,944.00
43,200.00 408,240.00 565,920.00

Peso Propio de Vigas = 384.00 kg/m

Viga X (m) Y (m) L (m) W (kg) W*X (kg-m) W*Y (kg-m)


1 3.50 0.00 7.00 2,688.00 9,408.00 0.00
2 9.45 0.00 4.90 1,881.60 17,781.12 0.00
3 15.40 0.00 7.00 2,688.00 41,395.20 0.00
4 3.50 8.00 7.00 2,688.00 9,408.00 21,504.00
5 9.45 8.00 4.90 1,881.60 17,781.12 15,052.80
6 15.40 8.00 7.00 2,688.00 41,395.20 21,504.00
7 3.50 12.20 7.00 2,688.00 9,408.00 32,793.60
8 9.45 12.20 4.90 1,881.60 17,781.12 22,955.52
9 15.40 12.20 7.00 2,688.00 41,395.20 32,793.60
10 3.50 19.40 7.00 2,688.00 9,408.00 52,147.20
11 9.45 19.40 4.90 1,881.60 17,781.12 36,503.04
12 15.40 19.40 7.00 2,688.00 41,395.20 52,147.20
13 3.50 25.90 7.00 2,688.00 9,408.00 69,619.20
14 9.45 25.90 4.90 1,881.60 17,781.12 48,733.44
15 15.40 25.90 7.00 2,688.00 41,395.20 69,619.20
16 0.00 4.00 8.00 3,072.00 0.00 12,288.00
17 0.00 10.10 4.20 1,612.80 0.00 16,289.28
18 0.00 15.80 7.20 2,764.80 0.00 43,683.84
19 0.00 22.65 6.50 2,496.00 0.00 56,534.40
20 7.00 4.00 8.00 3,072.00 21,504.00 12,288.00
21 7.00 10.10 4.20 1,612.80 11,289.60 16,289.28
22 7.00 15.80 7.20 2,764.80 19,353.60 43,683.84
23 7.00 22.65 6.50 2,496.00 17,472.00 56,534.40
24 11.90 4.00 8.00 3,072.00 36,556.80 12,288.00
25 11.90 10.10 4.20 1,612.80 19,192.32 16,289.28
26 11.90 15.80 7.20 2,764.80 32,901.12 43,683.84
27 11.90 22.65 6.50 2,496.00 29,702.40 56,534.40
28 18.90 4.00 8.00 3,072.00 58,060.80 12,288.00

24
29 18.90 10.10 4.20 1,612.80 30,481.92 16,289.28
30 18.90 15.80 7.20 2,764.80 52,254.72 43,683.84
31 18.90 22.65 6.50 2,496.00 47,174.40 56,534.40
76,070.40 718,865.28 990,554.88

Peso Propio de Losa = 800.00 kg/m2


Losa X (m) Y (m) L (m) B (m) A (m2) W (kg) W*X (kg- W*Y (kg-m)
m)
1 9.45 4.00 18.90 8.00 151.20 120,960.0 1,143,072.0 483,840.00
0 0
2 3.50 10.10 7.00 4.20 29.40 23,520.00 82,320.00 237,552.00
3 15.40 10.10 7.00 4.20 29.40 23,520.00 362,208.00 237,552.00
4 9.45 15.80 18.90 7.20 136.08 108,864.0 1,028,764.8 1,720,051.20
0 0
5 9.45 22.65 18.90 6.50 122.85 98,280.00 928,746.00 2,226,042.00
375,144.0 3,545,110.8 4,905,037.20
0 0

W (kg) W*X (kg-m) W*Y (kg-m)


Total 494,414.4 4,672,216.08 6,461,512.08
0

XCM (m) YCM (m)


9.45 13.07

CÁLCULO DEL CENTRO DE RIGIDECES

kColumna = 12EI/L3
I= 0.70Ig
E= 252,350 kg/cm2
LColumna = 2.50 m
kColumna = 0.1357 Ig

Columnas b (cm) h (cm) kColumna (kg/cm)


1 60.00 60.00 146,516.43
2 60.00 60.00 146,516.43
3 60.00 60.00 146,516.43
4 60.00 60.00 146,516.43

25
5 60.00 60.00 146,516.43
6 0.00 0.00 0.00
7 0.00 0.00 0.00
8 60.00 60.00 146,516.43
9 60.00 60.00 146,516.43
10 0.00 0.00 0.00
11 0.00 0.00 0.00
12 60.00 60.00 146,516.43
13 60.00 60.00 146,516.43
14 0.00 0.00 0.00
15 0.00 0.00 0.00
16 60.00 60.00 146,516.43
17 60.00 60.00 146,516.43
18 60.00 60.00 146,516.43
19 60.00 60.00 146,516.43
20 60.00 60.00 146,516.43

Marco X kx (kg/cm) Y (m) kx Y (kg/cm -


m)
1 586,065.72 0.00 0.00
5 586,065.72 25.90 15,179,102.02
1,172,131.4 15,179,102.02
3

YCR (m) = 12.95

Marco Y ky (kg/cm) X (m) ky X (kg/cm -


m)
1 732,582.14 0.00 0.00
4 732,582.14 7.00 5,128,075.01
1,465,164.2 5,128,075.01
9

XCR (m) = 3.50

ex (m) = XCR - XCM


ex (m) = -5.95

ey (m) = YCR - YCM


ey (m) = -0.12

Dx = 18.90 m
Dy = 25.90 m

26
exd = ex0 + 0.05Dx eyd = ey0 + 0.05Dy
exd = -5.01 m eyd = 1.18 M

MOMENTO TORSIONAL POR NIVEL

Mtx = Vxeyd Mty = Vyexd

Nivel Vx (Ton) Vy (Ton) exd (m) eyd (m) Mtx (m-Ton) Mty (m-Ton)
700 0.00 0.00 5.01 1.18 0.00 0.00
600 82.61 82.61 5.01 1.18 97.14 413.44
500 152.09 152.09 5.01 1.18 178.86 761.23
400 208.73 208.73 5.01 1.18 245.46 1044.70
300 252.83 252.83 5.01 1.18 297.32 1265.40
200 284.76 284.76 5.01 1.18 334.87 1425.23
100 305.02 305.02 5.01 1.18 358.70 1526.65
0 314.34 314.34 5.01 1.18 369.65 1573.26

FACTORES DE DISTRIBUCIÓN POR CORTANTE Y TORSIÓN

Torsión de
Planta
Ft
Traslación -0.02
ky
kx (Ton/cm
Marco (Ton/cm) ) Fd x' (m) y' (m) kxy' kyx' kxy'2 kyx'2 0.02
-
X1 586.07 0.50 -12.95 7,589.55 98,284.69
X5 586.07 0.50 12.95 7,589.55 98,284.69
-0.01
0.03
Y1 732.58 0.50 -3.5 -2,564.04 8,974.13
11,281.7
Y4 732.58 0.50 15.4 7 173,739.18
1172.13 1465.16 196,569.37 182,713.31

27
Marco X1
Cortante de
Diseño
Vx Vy Mtx (m- Mty (m- Vdx Vtx Vty Vx Vx+0.30Vty 0.30Vx+Vty
0 (Ton) (Ton) Ton) Ton) Fd (Ton) Ft (Ton) (Ton) (Ton) (Ton) (Ton)
700 0.00 0.00 0.00 0.00 0.50 0.00 0.02 0.00 0.00 0.00 0.00 0.00
600 82.61 82.61 97.14 413.44 0.50 41.30 0.02 1.94 8.27 43.25 45.73 21.25
500 152.09 152.09 178.86 761.23 0.50 76.05 0.02 3.58 15.23 79.63 84.20 39.12
1044.7
400 208.73 208.73 245.46 0 0.50 104.37 0.02 4.91 20.90 109.28 115.55 53.69
1265.4
300 252.83 252.83 297.32 0 0.50 126.41 0.02 5.95 25.32 132.36 139.96 65.03
1425.2
200 284.76 284.76 334.87 3 0.50 142.38 0.02 6.70 28.52 149.08 157.64 73.24
1526.6
100 305.02 305.02 358.70 5 0.50 152.51 0.02 7.18 30.55 159.69 168.85 78.46
1573.2
0 314.34 314.34 369.65 6 0.50 157.17 0.02 7.40 31.48 164.57 174.01 80.85

Marco X5
Cortante de
Diseño
Vx Vy Mtx (m- Mty (m- Vdx Vtx Vty Vx Vx+0.30Vty 0.30Vx+Vty
Nivel (Ton) (Ton) Ton) Ton) Fd (Ton) Ft (Ton) (Ton) (Ton) (Ton) (Ton)
700 0.00 0.00 0.00 0.00 0.50 0.00 0.02 0.00 0.00 0.00 0.00 0.00
600 82.61 82.61 97.14 413.44 0.50 41.30 0.02 1.94 8.27 43.25 45.73 21.25
500 152.09 152.09 178.86 761.23 0.50 76.05 0.02 3.58 15.23 79.63 84.20 39.12
1044.7
400 208.73 208.73 245.46 0 0.50 104.37 0.02 4.91 20.90 109.28 115.55 53.69
1265.4
300 252.83 252.83 297.32 0 0.50 126.41 0.02 5.95 25.32 132.36 139.96 65.03
1425.2
200 284.76 284.76 334.87 3 0.50 142.38 0.02 6.70 28.52 149.08 157.64 73.24
1526.6
100 305.02 305.02 358.70 5 0.50 152.51 0.02 7.18 30.55 159.69 168.85 78.46
1573.2
0 314.34 314.34 369.65 6 0.50 157.17 0.02 7.40 31.48 164.57 174.01 80.85

Marco X1 Marco X5
Nivel Vx (Ton) Fx (Ton) Vy (Ton) Fy (Ton)
700 45.73 45.73
45.73 45.73
600 38.47 38.47

28
84.20 84.20
500 31.35 31.35
115.55 115.55
400 24.41 24.41
139.96 139.96
300 17.68 17.68
157.64 157.64
200 11.22 11.22
168.85 168.85
100 5.16 5.16
174.01 174.01
0 0

Marco Y1
Cortante de
Diseño
Vx Vy Mtx (m- Mty (m- Vdy Vtx Vty Vy Vy+0.30Vtx 0.30Vy+Vtx
Nivel (Ton) (Ton) Ton) Ton) Fd (Ton) Ft (Ton) (Ton) (Ton) (Ton) (Ton)
700 0.00 0.00 0.00 0.00 0.50 0.00 0.01 0.00 0.00 0.00 0.00 0.00
600 82.61 82.61 97.14 413.44 0.50 41.30 0.01 0.66 2.79 44.10 44.29 13.89
500 152.09 152.09 178.86 761.23 0.50 76.05 0.01 1.21 5.15 81.19 81.56 25.57
1044.7
400 208.73 208.73 245.46 0 0.50 104.37 0.01 1.66 7.06 111.43 111.93 35.09
1265.4
300 252.83 252.83 297.32 0 0.50 126.41 0.01 2.01 8.55 134.97 135.57 42.50
1425.2
200 284.76 284.76 334.87 3 0.50 142.38 0.01 2.26 9.63 152.02 152.69 47.87
1526.6
100 305.02 305.02 358.70 5 0.50 152.51 0.01 2.42 10.32 162.83 163.56 51.27
1573.2
0 314.34 314.34 369.65 6 0.50 157.17 0.01 2.50 10.64 167.80 168.55 52.84

Marco Y5
Cortante de
Diseño
Vx Vy Mtx (m- Mty (m- Vdy Vtx Vty Vy Vy+0.30Vtx 0.30Vy+Vtx
Nivel (Ton) (Ton) Ton) Ton) Fd (Ton) Ft (Ton) (Ton) (Ton) (Ton) (Ton)
700 0.00 0.00 0.00 0.00 0.50 0.00 0.01 0.00 0.00 0.00 0.00 0.00
600 82.61 82.61 97.14 413.44 0.50 41.30 0.01 0.66 2.79 44.10 44.29 13.89
500 152.09 152.09 178.86 761.23 0.50 76.05 0.03 5.32 22.64 98.69 100.29 34.93
1044.7
400 208.73 208.73 245.46 0 0.50 104.37 0.03 7.30 31.07 135.44 137.63 47.93
1265.4
300 252.83 252.83 297.32 0 0.50 126.41 0.03 8.84 37.64 164.05 166.71 58.06
1425.2
200 284.76 284.76 334.87 3 0.50 142.38 0.03 9.96 42.39 184.77 187.76 65.39
1526.6
100 305.02 305.02 358.70 5 0.50 152.51 0.03 10.67 45.41 197.92 201.12 70.05
1573.2
0 314.34 314.34 369.65 6 0.50 157.17 0.03 11.00 46.80 203.97 207.26 72.19

29
Marco Y1 Marco Y4
Nivel Vx (Ton) Fx (Ton) Vy (Ton) Fy (Ton)
700 44.29 44.29
44.29 44.29
600 37.26 55.99
81.56 100.29
500 30.37 37.34
111.93 137.63
400 23.64 29.08
135.57 166.71
300 17.12 21.06
152.69 187.76
200 163.56 13.36
163.56 201.12
100 4.99 6.14
168.55 207.26
0 0

Marco X1 Marco X4
Nivel h (m) hi (m) Fx (Ton) Mx (m-Ton) Nivel h (m) hi (m) Fx (Ton) Mx (m-Ton)
700 3.10 21.70 45.73 0 700 3.10 21.70 44.29 0
600 3.10 18.60 38.47 141.76 600 3.10 18.60 37.26 137.31
500 3.10 15.50 31.35 402.76 500 3.10 15.50 30.37 390.14
400 3.10 12.40 24.41 760.96 400 3.10 12.40 23.64 737.11
300 3.10 9.30 17.68 1194.84 300 3.10 9.30 17.12 1,157.37
200 3.10 6.20 11.22 1683.51 200 3.10 6.20 163.56 1,630.73
100 3.10 3.10 5.16 1718.29 100 3.10 3.10 4.99 2,611.12
0 3.10 0.00 0.00 2746.39 0 3.10 0.00 0.00 3,606.99

Marco Y1 Marco Y4
Nivel h (m) hi (m) Fy (Ton) My (m-Ton) Nivel h (m) hi (m) Fy (Ton) My (m-Ton)
700 3.10 21.70 44.29 0.00 700 3.10 21.70 44.29 0.00
600 3.10 18.60 37.26 137.31 600 3.10 18.60 55.99 137.31
500 3.10 15.50 30.37 390.14 500 3.10 15.50 37.34 448.20
400 3.10 12.40 23.64 737.11 400 3.10 12.40 29.08 874.85
300 3.10 9.30 17.12 1157.37 300 3.10 9.30 21.06 1391.64
200 3.10 6.20 163.56 1630.73 200 3.10 6.20 13.36 1973.70
100 3.10 3.10 4.99 2611.12 100 3.10 3.10 6.14 2597.18
0 3.10 0.00 0.00 3606.99 0 3.10 0.00 0.00 3239.70

30
CALCULO Y DISEÑO DE LOS ACEROS EN VIGAS Y COLUMNAS
Es un acero de calidad estructural de alta resistencia y baja aleación con la adición de microaleantes (Niobio o
Vanadio) se desarrollaron estos aceros de alta resistencia, haciéndolos más seguros en su comportamiento
mecánico y lográndose una reducción en el consumo específico desde el punto de vista estructural.
Se utiliza cuando se desea disminuir los espesores en diseño gracias a su mayor resistencia comparada con la
lámina A-36.

Ventajas:
Ductilidad y Homogeneidad
Soldabilidad
Conformidad
Relación resistencia / peso

Aplicaciones:
El acero A572 Gr 50 es empleado en la construcción de estructuras metálicas. Dentro de las principales
aplicaciones están plataformas para la industria petrolera, puentes, torres de energía, torres para comunicación,
herrajes eléctricos, señalización y edificaciones remachadas, atornilladas o soldadas.

Dimensiones que comercializamos

Espesores Desde 2,5 mm hasta 101,6 mm.

Formatos 6×20, 8×20 y 8×40 pies.

(Cortamos a medidas especiales de acuerdo a sus


necesidades).
Compañía General de Aceros es su proveedor de confianza en láminas A-572 Grado 50 y otros aceros para
diferentes aplicaciones. Póngase en contacto con nosotros para una cita o cualquier consulta técnica.

DISEÑO DE LAS VIGAS


Se Realizó un Análisis De forma Manual aplicando SUPERPSICIÓN Para Obtener los Desplazamientos Elásticos
en cada Nodo (Piso) del Sistema Estructural

31
Acero Superior

 Barras Necesarias

 Barras Establecidas

Acero Inferior

32
 Barras Necesarias

 Barras Establecidas

33
DISEÑO DE LAS COLUMNA
Calculo de Momentos Probables

Aplicación de Combinaciones de cargas con consideraciones del ACI318-19 section 5.3 / ASCE 7-05 Section
12.4

Acero Inferior

DIAGRAMA PARA FUERZAS AXIAL EN CARGAS MUERTAS

34
Como podemos apreciar en este diagrama se ampliaron cargas muerta a la columna dándonos un diagrama de las
fuerza resultantes.
DIAGRAMA PARA FUERZAS AXIAL EN CARGAS VIVAS

35
Como podemos apreciar en este diagrama se ampliaron cargas vivas a la columna dándonos un diagrama de las
fuerza resultantes.
DIAGRAMA PARA CARGAS DE SISMO

DIAGRAMA PARA CORTANTE EN CARGAS MUERTAS

36
DIAGRAMA PARA CORTANTE EN CARGAS VIVAS

DIAGRAMA PARA SISMO

37
DIAGRAMA PARA MOMENTO EN CARGAS MURTAS

DIAGRAMA PARA MOMENTO EN CARGAS VIVAS

38
DIAGRAMA PARA SISMO

DIAGRAMA DE TENSIÓN MÁXIMA

39
DIAGRAMA DE TENSIÓN MÍNIMA

DIAGRAMA DE LA DEFORMACIÓN ESTRUCTURAL

40
41