PREDIMENSIONAMIENTO
1° Espesor de losa aligerada aligerada bidireccional y unidireccional
Ln = 4.74 m
h= 0.119 m 0.17 m
DIRECCIÓN XX - YY
Z= 0.45 Lx=
U= 1 Ly=
S= 1.05 INTERMEDIO
N= 5
Ap= 102.024 m2
Lx-y= 30.74 m
6° Disposición de muros
6° Disposición de columnas
14 cm
25 cm
14 cm
10 cm
14 cm
VIGAS
VIGAS DE BORDE VIGAS INTERIORES
35 cm
14 cm 14 cm
b= 0.14 m
h= 0.35 m
V CH 1
CM 1757.84
CV 992.8
w 2750.64 b = 35 cm
Vc 4469.79
V CH 2
CM 1742.79
CV 984.3
w 2727.09 b = 20 cm
Vc 2263.48
V CH 3
CM 1417.71
CV 800.7
w 2218.41 b = 15 cm
Vc 1841.28
V CH 4
V CH 5
CM 1417.71
CV 800.7
w 2218.41 b = 20 cm
Vc 2351.51
IGAS INTERIORES
17 cm
14 cm
I. Análisis Sísmico
1° Períodos y modos
Case Mode Period UX UY UZ
sec
Modal 1 0.266 0.0397 0.642 0
Modal 2 0.233 0.6691 0.0207 0
Modal 3 0.187 0.0313 0.0809 0
Modal 4 0.071 0.001 0.1481 0
Modal 5 0.062 0.1586 0.0093 0
Modal 6 0.047 0.0199 0.0212 0
Modal 7 0.036 0.0021 0.0389 0
Modal 8 0.03 0.0472 0.0062 0
Modal 9 0.024 0.001 0.015 0
Modal 10 0.022 0.0062 0.0064 0
Modal 11 0.02 0.0174 0.0024 0
Modal 12 0.019 0.0002 0.0049 0
Modal 13 0.016 0.0049 0.0005 0
Modal 14 0.014 0.0011 0.0028 0
Modal 15 0.011 0.0002 0.0007 0
VERIFICACIÓN
PISO 1
Peso 1 94,637.40 kg
Área 102.024 m2
Peso/Área 927.60 kg/cm2 DEBE ESTAR ENTRE 800 - 1000 KG
EJE YY
Load Cumple <
Story Direction Drift Drift*0.85*R
Case/Combo 0.005
Story5 SISMO YY Max Y 0.001171 0.002240 SI
Story4 SISMO YY Max Y 0.001309 0.002503 SI
Story3 SISMO YY Max Y 0.001329 0.002542 SI
Story2 SISMO YY Max Y 0.001157 0.002213 SI
Story1 SISMO YY Max Y 0.000632 0.001209 SI
P VX VY
Load
Story Location
Case/Combo kgf kgf kgf
SISMO XX
Story1 Bottom 0.00 168,310.93 41,620.71
Max
SISMO YY
Story1 Bottom 0.00 41,620.71 161,056.91
Max
T MX MY
kgf-m kgf-m kgf-m
d > 0.9 Ve
Sum RY Sum RZ
0.0221 0.0606
0.3252 0.1215
0.3434 0.7414
0.3512 0.764
0.7451 0.7718
0.7857 0.915
0.7906 0.924
0.9067 0.9264
0.9101 0.9299
0.9262 0.9757
0.9801 0.977
0.9808 0.9781
0.9959 0.9781
0.9993 0.9958
1 1
Diseño MUROS XX
SISMO XX
Story1 X2 Max
Bottom 16,416.68 4,574.91 12.33
SISMO XX
Story1 X3 Max
Bottom 1,582.32 5,745.46 12.34
SISMO XX
Story1 X4 Max
Bottom 19,514.33 9,196.35 87.20
SISMO XX
Story1 X5 Max
Bottom 28,348.59 9,023.41 79.77
SISMO XX
Story1 X6 Max
Bottom 13,586.73 6,070.31 25.02
SISMO XX
Story1 X7 Max
Bottom 18,054.42 4,255.79 26.78
SISMO XX
Story1 X8 Max
Bottom 22,591.55 8,586.48 36.84
SISMO XX
Story1 X9 Max
Bottom 7,567.35 5,438.85 21.93
SISMO XX
Story1 X10 Max
Bottom 62,037.86 28,725.46 18.14
SISMO XX
Story1 X11 Max
Bottom 40,517.50 17,099.38 187.42
SISMO XX
Story1 PX1 Max
Bottom 131,149.68 53,833.70 458.40
SISMO XX
Story1 PX2 Max
Bottom 101,335.86 47,682.39 64.80
4° Pg y Pm
Pg PISO 1 Pm 1PISO
P
Load
Story Pier Location Story
Case/Combo kgf
5° Resistencia al corte
Si es >= 1, 1
Si es < 1, el numero
v'm L α α t
Story Pier
Kg/cm2 m corregido cm
Story1 X1 8.1 3.23 1.31 1.00 14
Story1 X2 8.1 1.46 0.81 0.81 14
Story1 X3 8.1 1.21 0.82 0.82 14
Story1 X4 8.1 3.25 0.72 0.72 14
Story1 X5 8.1 2.54 0.90 0.90 14
Story1 X6 8.1 2 0.80 0.80 14
Story1 X7 8.1 1.35 0.70 0.70 14
Story1 X8 8.1 2.28 0.87 0.87 14
Story1 X9 8.1 2 0.69 0.69 14
Story1 X10 8.1 3.53 1.65 1.00 14
Story1 X11 8.1 3.16 0.94 0.94 14
Story1 PX1 8.1 3.16 0.82 0.82 14
Story1 PX2 8.1 1.88 0.76 0.76 14
Pm L t
Story Pier σm en Kg/cm2 0.05f`m
Kg m cm
Story1 X1 17,849.72 3.23 14 3.95 3.25
Story1 X2 10,457.17 1.46 14 5.12 3.25
Story1 X3 6,817.61 1.21 14 4.02 3.25
Story1 X4 27,277.65 3.25 14 6.00 3.25
Story1 X5 21,800.55 2.54 14 6.13 3.25
Story1 X6 18,321.15 2.00 14 6.54 3.25
Story1 X7 11,470.63 1.35 14 6.07 3.25
Story1 X8 15,309.64 2.28 14 4.80 3.25
Story1 X9 19,302.30 2.00 14 6.89 3.25
Story1 X10 19,096.32 3.53 14 3.86 3.25
Story1 X11 21,552.02 3.16 14 4.87 3.25
Story1 PX1 49,343.32 3.16 14
Story1 PX2 45,850.52 1.88 14
PISO 3
Pm L t
Story Pier sm en Kg/cm2 0.05f`m
Kg m cm
Story3 X1 10,253.80 3.23 14 2.27 3.25
Story3 X2 5,817.81 1.46 14 2.85 3.25
Story3 X3 4,104.37 1.21 14 2.42 3.25
Story3 X4 16,031.23 3.25 14 3.52 3.25
Story3 X5 11,933.61 2.54 14 3.36 3.25
Story3 X6 10,480.11 2.00 14 3.74 3.25
Story3 X7 5,497.03 1.35 14 2.91 3.25
Story3 X8 8,162.44 2.28 14 2.56 3.25
Story3 X9 11,210.40 2.00 14 4.00 3.25
Story3 X10 11,061.29 3.53 14 2.24 3.25
Story3 X11 12,847.93 3.16 14 2.90 3.25
Story3 PX1 31,062.23 3.16 14
Story3 PX2 29,226.53 1.88 14
PISO 4
Pm L t
Story Pier sm en Kg/cm2 0.05f`m
Kg m cm
Story3 X1 6,661.26 3.23 14 1.47 3.25
Story3 X2 3,746.21 1.46 14 1.83 3.25
Story3 X3 2,686.01 1.21 14 1.59 3.25
Story3 X4 10,375.98 3.25 14 2.28 3.25
Story3 X5 7,622.23 2.54 14 2.14 3.25
Story3 X6 6,675.89 2.00 14 2.38 3.25
Story3 X7 3,470.12 1.35 14 1.84 3.25
Story3 X8 5,347.47 2.28 14 1.68 3.25
Story3 X9 7,151.61 2.00 14 2.55 3.25
Story3 X10 6,977.51 3.53 14 1.41 3.25
Story3 X11 8,377.24 3.16 14 1.89 3.25
Story3 PX1 20,029.61 3.16 14
Story3 PX2 18,896.64 1.88 14
PISO 5
Pm L t
Story Pier sm en Kg/cm2 0.05f`m
Kg m cm
Story5 X1 3,244.46 3.23 14 0.72 3.25
Story5 X2 1,765.65 1.46 14 0.86 3.25
Story5 X3 1,296.56 1.21 14 0.77 3.25
Story5 X4 4,726.78 3.25 14 1.04 3.25
Story5 X5 3,546.53 2.54 14 1.00 3.25
Story5 X6 2,932.33 2.00 14 1.05 3.25
Story5 X7 2,057.43 1.35 14 1.09 3.25
Story5 X8 2,633.11 2.28 14 0.82 3.25
Story5 X9 3,133.25 2.00 14 1.12 3.25
Story5 X10 2,774.35 3.53 14 0.56 3.25
Story5 X11 3,876.71 3.16 14 0.88 3.25
Story5 PX1 8,171.11 3.16 14
Story5 PX2 8,076.75 1.88 14
CONTROL DE FISURACIÓN
∑Vm1= 238,695.98 Kg
VE= 212,644.29 Kg
Cortante dinámico escalado relacion 1.122513001 se comporta inelasti
2° Fuerzas de corte para un SISMO MODERADO
T M2 M3 Load
Story Pier
kgf-m kgf-m kgf-m Case/Combo
P
Load
Pier Location
Case/Combo kgf
X1 Pm Bottom -17849.72
X2 Pm Bottom -10457.17
X3 Pm Bottom -6817.61
X4 Pm Bottom -27277.65
X5 Pm Bottom -21800.55
X6 Pm Bottom -18321.15
X7 Pm Bottom -11470.63
X8 Pm Bottom -15309.64
X9 Pm Bottom -19302.3
X10 Pm Bottom -19096.32
X11 Pm Bottom -21552.02
PX1 Pm Bottom -49343.32
PX2 Pm Bottom -45850.52
Pg Vm Vc
Kg Kg Kg
16,062.57 27,622.74
9,207.53 8,835.33
6,049.54 7,045.82
24,533.76 18,995.17
19,067.37 17,318.48
16,165.36 12,741.95
9,866.16 7,660.69
13,312.49 14,352.24
17,028.49 11,694.74
16,947.37 36,948.04
19,428.24 21,287.66
44,834.60 33,978.22
40,889.98 20,214.89
ENTONCES
Entonces
Load P
Pier Case/Com Location
bo kgf
X1 Pm Bottom -13933.95
X2 Pm Bottom -7971.61
X3 Pm Bottom -5469.02
X4 Pm Bottom -21675.81
X5 Pm Bottom -16590.9
X6 Pm Bottom -14391.56
X7 Pm Bottom -7839.72
X8 Pm Bottom -11501.81
X9 Pm Bottom -15283.26
X10 Pm Bottom -15063.41
X11 Pm Bottom -17227.75
PX1 Pm Bottom -41077.74
PX2 Pm Bottom -38396.54
Load P
Pier Case/Com Location
bo kgf
X1 Pm Bottom -10253.8
X2 Pm Bottom -5817.81
X3 Pm Bottom -4104.37
X4 Pm Bottom -16031.23
X5 Pm Bottom -11933.61
X6 Pm Bottom -10480.11
X7 Pm Bottom -5497.03
X8 Pm Bottom -8162.44
X9 Pm Bottom -11210.4
X10 Pm Bottom -11061.29
X11 Pm Bottom -12847.93
PX1 Pm Bottom -31062.23
PX2 Pm Bottom -29226.53
Load P
Pier Case/Com Location
bo kgf
X1 Pm Bottom -6661.26
X2 Pm Bottom -3746.21
X3 Pm Bottom -2686.01
X4 Pm Bottom -10375.98
X5 Pm Bottom -7622.23
X6 Pm Bottom -6675.89
X7 Pm Bottom -3470.12
X8 Pm Bottom -5347.47
X9 Pm Bottom -7151.61
X10 Pm Bottom -6977.51
X11 Pm Bottom -8377.24
PX1 Pm Bottom -20029.61
PX2 Pm Bottom -18896.64
Load P
Pier Case/Com Location
bo kgf
X1 Pm Bottom -3244.46
X2 Pm Bottom -1765.65
X3 Pm Bottom -1296.56
X4 Pm Bottom -4726.78
X5 Pm Bottom -3546.53
X6 Pm Bottom -2932.33
X7 Pm Bottom -2057.43
X8 Pm Bottom -2633.11
X9 Pm Bottom -3133.25
X10 Pm Bottom -2774.35
X11 Pm Bottom -3876.71
PX1 Pm Bottom -8171.11
PX2 Pm Bottom -8076.75
Diseño MUROS YY
SISMO YY
Story1 PY2 Max
Bottom 28,783.72 14,254.79 167.20
SISMO YY
Story1 Y1 Max
Bottom 19,653.28 5,338.29 150.96
SISMO YY
Story1 Y2 Max
Bottom 15,911.04 19,562.95 15.09
SISMO YY
Story1 Y3 Max
Bottom 19,639.22 16,526.24 16.39
SISMO YY
Story1 Y4 Max
Bottom 52,909.31 35,769.26 140.80
SISMO YY
Story1 Y5 Max
Bottom 13,581.99 32,521.21 97.15
SISMO YY
Story1 Y6 Max
Bottom 23,269.93 19,012.68 7.53
SISMO YY
Story1 Y7 Max
Bottom 40,175.29 18,489.08 8.83
4° Pg y Pm
Pg PISO 1 Pm 1PISO
P
Load
Story Pier Location Story
Case/Combo kgf
5° Resistencia al corte
Si es >= 1, 1
Si es < 1, el numero
v'm L α α t
Story Pier
Kg/cm2 m corregido cm
Story1 PY1 8.1 3.26 0.66 0.66 14
Story1 PY2 8.1 1.04 0.48 0.48 14
Story1 Y1 8.1 2.12 0.65 0.65 14
Story1 Y2 8.1 3.02 1.34 1 14
Story1 Y3 8.1 2.6 1.18 1 14
Story1 Y4 8.1 4.72 1.18 1 14
Story1 Y5 8.1 4.74 1.02 1 14
Story1 Y6 8.1 2.64 0.99 0.99 14
Story1 Y7 8.1 2.66 0.96 0.96 14
PISO 1
sm en
Pm L t
Story Pier Kg/cm2 0.05f`m
Kg m cm
Story1 PY1 49174.41 3.26 14 10.77 3.25
Story1 PY2 30035.82 1.04 14 20.63 3.25
Story1 Y1 15744.96 2.12 14 5.30 3.25
Story1 Y2 18183.87 3.02 14 4.30 3.25
Story1 Y3 18083.87 2.6 14 4.97 3.25
Story1 Y4 26469.81 4.72 14 4.01 3.25
Story1 Y5 37534 4.74 14 5.66 3.25
Story1 Y6 22439.03 2.64 14 6.07 3.25
Story1 Y7 24419.68 2.66 14 6.56 3.25
PISO 2
Story Pier Pm L t sm en 0.05f`m
Kg m cm Kg/cm2
Story2 X1 39,960.29 3.26 14 8.76 3.25
Story2 X2 24,867.68 1.04 14 17.08 3.25
Story2 X3 12,485.28 2.12 14 4.21 3.25
Story2 X4 14,164.43 3.02 14 3.35 3.25
Story2 X5 14,021.24 2.60 14 3.85 3.25
Story2 X6 19,738.36 4.72 14 2.99 3.25
Story2 X7 29,017.39 4.74 14 4.37 3.25
Story2 X8 17,474.21 2.64 14 4.73 3.25
Story2 X9 19,135.95 2.66 14 5.14 3.25
PISO 4
Story Pier Pm L t sm en 0.05f`m
Kg m cm Kg/cm2
Story4 PY1 19504.21 3.26 14
Story4 PY2 11799.63 1.04 14
Story4 Y1 6009.56 2.12 14 2.02 3.25
Story4 Y2 6696.68 3.02 14 1.58 3.25
Story4 Y3 6685.42 2.6 14 1.84 3.25
Story4 Y4 9415.22 4.72 14 1.42 3.25
Story4 Y5 13333.31 4.74 14 2.01 3.25
Story4 Y6 8247.39 2.64 14 2.23 3.25
Story4 Y7 9086.39 2.66 14 2.44 3.25
PISO 5
Story Pier Pm L t sm en 0.05f`m
Kg m cm Kg/cm2
Story5 PY1 8740.8 3.26 14
Story5 PY2 4667.18 1.04 14
Story5 Y1 2802.43 2.12 14 0.94 3.25
Story5 Y2 3111.85 3.02 14 0.74 3.25
Story5 Y3 3147.94 2.6 14 0.86 3.25
Story5 Y4 5038.66 4.72 14 0.76 3.25
Story5 Y5 5872.97 4.74 14 0.89 3.25
Story5 Y6 3778.87 2.64 14 1.02 3.25
Story5 Y7 4153.72 2.66 14 1.12 3.25
CONTROL DE FISURACIÓN
7° la verificación del agrietamiento diagonal en los entrepisos superiores; y,
PRIMER PISO
R=4.25
Story Pier V2 Vm Vc 0.55Vm Cumple?
kgf Kg Kg Ve≤ 0.55Vm
Story1 PY1 25,747.30 0.00 35,053.48 0.00 si
Story1 PY2 7,127.40 0.00 11,182.71 0.00 si
Story1 Y1 2,669.15 11,114.72 0.00 6,113.10 si
Story1 Y2 9,781.48 26,648.46 0.00 14,656.65 si
Story1 Y3 8,263.12 21,102.97 0.00 11,606.63 si
Story1 Y4 17,884.63 37,072.65 0.00 20,389.96 si
Story1 Y5 16,260.61 34,991.33 0.00 19,245.23 si
Story1 Y6 9,506.34 19,387.95 0.00 10,663.37 si
Story1 Y7 9,244.54 19,445.80 0.00 10,695.19 si
169763.86 46236.187
∑Vm1= 216,000.05 Kg
VE= 212,643.67 Kg
relacion 1.016 se comporta inelasticam
2° Fuerzas de corte para un SISMO MODERADO
T M2 M3 Load
Story Pier
kgf-m kgf-m kgf-m Case/Combo
P
Load
Pier Location
Case/Combo kgf
Pg Vm Vc
Kg Kg Kg
43,766.28 35,053.48
26,615.99 11,182.71
14,348.08 11,114.72
15,945.37 26,648.46
15,929.56 21,102.97
23,437.98 37,072.65
33,176.75 34,991.33
19,876.53 19,387.95
21,607.16 19,445.80
cumple Pm 2PISO
ENTONCES
sm≥
0.05f`m ?
SI SI LLEVA REFUERZO HORIZONTAL CONTINUO
Story
SI SI LLEVA REFUERZO HORIZONTAL CONTINUO
SI SI LLEVA REFUERZO HORIZONTAL CONTINUO Story2
SI SI LLEVA REFUERZO HORIZONTAL CONTINUO Story2
SI SI LLEVA REFUERZO HORIZONTAL CONTINUO Story2
NO NO LLEVA REFUERZO HORIZONTAL CONTINUO Story2
SI SI LLEVA REFUERZO HORIZONTAL CONTINUO Story2
SI SI LLEVA REFUERZO HORIZONTAL CONTINUO Story2
SI SI LLEVA REFUERZO HORIZONTAL CONTINUO Story2
Story2
1/4" CADA 2 HILADAS Story2
cumple Pm 3PISO
ENTONCES
sm≥
0.05f`m ?
Story
NO NO LLEVA REFUERZO HORIZONTAL CONTINUO Story3
NO NO LLEVA REFUERZO HORIZONTAL CONTINUO Story3
NO NO LLEVA REFUERZO HORIZONTAL CONTINUO Story3
NO NO LLEVA REFUERZO HORIZONTAL CONTINUO Story3
NO NO LLEVA REFUERZO HORIZONTAL CONTINUO Story3
NO NO LLEVA REFUERZO HORIZONTAL CONTINUO Story3
SI SI LLEVA REFUERZO HORIZONTAL CONTINUO Story3
Story3
1/4" CADA 2 HILADAS Story3
cumple Pm 4PISO
ENTONCES
sm≥
0.05f`m ?
Story
cumple Pm 5PISO
ENTONCES
sm≥
0.05f`m ?
Story
Story
Entonces
e≤ 0.55Vm
no hay agrietamiento por corte
no hay agrietamiento por corte
no hay agrietamiento por corte
no hay agrietamiento por corte
no hay agrietamiento por corte
no hay agrietamiento por corte
no hay agrietamiento por corte
no hay agrietamiento por corte
no hay agrietamiento por corte
se comporta inelasticamente
SISMO MODERADO R= 4.5
V2 M3
Location
kgf kgf-m
Load P
Pier Case/Com Location
bo kgf
PY1 Pm Bottom -19504.21
PY2 Pm Bottom -11799.63
Y1 Pm Bottom -6009.56
Y2 Pm Bottom -6696.68
Y3 Pm Bottom -6685.42
Y4 Pm Bottom -9415.22
Y5 Pm Bottom -13333.31
Y6 Pm Bottom -8247.39
Y7 Pm Bottom -9086.39
Load P
Pier Case/Com Location
bo
Load
Pier Case/Com Location
bo kgf
PY1 Pm Bottom -8740.8
PY2 Pm Bottom -4667.18
Y1 Pm Bottom -2802.43
Y2 Pm Bottom -3111.85
Y3 Pm Bottom -3147.94
Y4 Pm Bottom -5038.66
Y5 Pm Bottom -5872.97
Y6 Pm Bottom -3778.87
Y7 Pm Bottom -4153.72
DISEÑO DE ELEMENTOS DE CONFINAMIENTO
Muro = X5
I. COLUMNAS DE CONFINAMIENTO II. VIGA SOLERA
20) Ts =
Columna Rectangular L 21) As =
1) Pg = 19,067.37 kg 19,067.37 kg 22) Acero longitudinal a utilizar
2) Vu = 9,023.41 kg 9,023.41 kg Asmín
3) Mu = 25,522.45 kg-m 25,522.45 kg-m Dimensiones
4) L = 2.54 m 2.54 m h=
5) Lm = 2.54 m 2.54 m Asol =
6) Nc = 2 Columna 2 Columna Asmín
7) F = 10,048.21 kg 10,048.21 kg Asmín
8) Pc = 9,533.69 kg 9,533.69 kg
9) Pt = 0 kg 5,146.47 kg
10) T = 514.52 kg -4,631.95 kg estibos
11) C = 19,581.89 kg 19,581.89 kg
12) As = -0.14 cm2 1.23 cm2 Pt:
13) 4*3/8" = 2.85 cm2 5.70 cm2 8*3/8"
Story
14) δ = 0.80 1.00
16)
15) An = 114.92 cm2 28.29 cm2 Story1
Dimensiones
de la columna
a emplear
a= 25 cm b= 14 cm L
17) Ac = 350 cm2 504 cm2
18) An = 210 cm2 320 cm2
19) Amín= 1.75 cm2 2.52 cm2
VIGA SOLERA
4,511.71 kg
1.19 cm2
2) Acero longitudinal a utilizar
2.85 cm2
17 cm b= 14 cm
238.00 cm2
2.85 cm2
1.19 cm2
4 de 3/8"
será [] 6mm, 1 @ 5, 4@ 10, r @ 25 cm.
Load P
Pier Case/Comb Location
o kgf
Y3 Pg Bottom -15929.56