Tyco - Rociadores (Todos) Ul
Tyco - Rociadores (Todos) Ul
Tyco - Rociadores (Todos) Ul
EX5985
Sprinklers, Automatic and Open
Page Bottom
Sprinklers, Automatic and Open
See General Information for Sprinklers, Automatic and Open
TYCO FIRE & BUILDING PRODUCTS EX5985
1400 PENNBROOK PKY
LANSDALE, PA 19446 USA
Sprinkler Identification Numbers (SIN) TY1121, TY1221, TY1281, TY1282, TY1381, TY1382, TY3101, TY3103, TY3121, TY3123, TY3210, TY3221,
TY3281, TY3282, TY3290, TY3301, TY3321, TY3322, TY3381, TY3382, TY3390, TY4101, TY4103, TY4121, TY4123, TY4210, TY4321, TY4322,
TY4801, TY4910, TY9128 Fusible Element Type.
Sprinkler Identification Numbers (SIN) TY313, TY315, TY323, TY325, TY363, TY365, TY1131, TY1151, TY1231, TY1251, TY1331, TY2131, TY2231,
TY3104, TY3105, TY3131, TY3133, TY3151, TY3153, TY3187, TY3191, TY3201, TY3204, TY3205, TY3230, TY3231, TY3250, TY3251,
TY3291,TY3296, TY3304, TY3305, TY3307, TY3331, TY3332, TY3351, TY3391, TY3431, TY3451, TY3535, TY3539, TY3555, TY3631, TY3651,
TY4131, TY4133, TY4151, TY4153, TY4191, TY4231, TY4251, TY4292, TY4232, TY4332, TY4631, TY4651, TY4831, TY4851, TY4931, TY4951,
TY5131, TY5137, TY5151, TY5153, TY5231, TY5237, TY5251, TY5332, TY5337, TY5339, TY5851, TY6137, TY6237, TY7153, TY8181, TY8191,
TY8281, TY8291, TY9181, TY9191, TY9281, TY9291 glass bulb type.
Sprinkler Identification Numbers (SIN) TY3111, TY3113, TY3211, TY3311, TY4113, TY4211, TY4811 and TY4911 are center strut type sprinklers.
Chrome plated sprinklers are identified by an unplated area where the deflector is staked to the frame and/or unplated ends of the center strut.
Telfon coated sprinklers are identified by the chrome plated operating mechanism.
Sprinkler Identification Numbers (SIN) TY3135, TY3155, TY3230, TY3235, TY3250, TY3255, TY3335, TY3337, TY3339, TY3355, TY3338, TY3357,
TY3735, TY3835, TY3935, TY5255, TY5235, TY5238, dry sprinkler glass bulb type.
Sprinkler Identification Numbers (SIN) TY3187, TY4180, TY4181, TY4182, TY2180, TY2181, TY2182 are plain brass glass bulb type attic
sprinklers.
Sprinkler Identification Numbers (SIN) TY3180, TY3181, TY3182, TY3183, TY3184, TY3185, TY5521, TY5522, TY9128 are fusible link type
sprinklers.
Sprinkler Identification Numbers (SIN) TY1189, TY2189, TY2190, TY3189, TY3190, TY2199, TY3199 are plain brass glass bulb type quick
response sprinklers for concealed spaces.
Sprinkler Identification Numbers (SIN) TY5111, TY5211, TY5811 are center strut type sprinklers.
SIN TY3261, fusible pellet type. Decorative chrome plated, white or black paint coated sprinklers are identified by uncoated levers.
Sprinkler Identification Numbers (SIN) SA1131, SA1132, SA1151, SA1152 glass bulb type.
UPRIGHT AND PENDENT STANDARD SPRAY SPRINKLERS
NOMINAL 5.6 KFACTOR
Response System Working
SIN Type Type Pressure, psig Temp Rating, °F
NOMINAL 1.4 TO 4.2 KFACTOR
NOMINAL 8.0 KFACTOR
STANDARD SIDEWALL SPRAY SPRINKLERS
+ Ordinary hazard occupancies.
++ Installation 4 to 12 in. below the ceiling.
FLUSH, RECESSED AND CONCEALED SPRINKLERS
Temp Rating, °F
Response Nom System Working
SIN Type Type KFactor Pressure, psig Cover Sprinkler
DRY SPRINKLERS
System
Working
Response Max Pressure, Temp Rating,
SIN Type Type Length, in. psig Nom KFactor F
* For ordinary hazard occupancies when installed 4 to 12 in. below ceiling.
# The 155°F sprinkler utilizes a 135°F coverplate and the 200°F sprinkler utilizes a 155°F coverplate
+ 3/4 in. NPT
CONVENTIONAL (OLD STYLE) SPRINKLERS
Response Nom
SIN Type KFactor Temp Rating, °F
STANDARD RESPONSE (SR) EXTENDED COVERAGE SPRINKLER LIGHT HAZARD
Dimension of wall on which a sidewall sprinkler is installed.
(B) Dimension perpendicular to wall on which a sidewall sprinkler is installed.
* Utilizes A 135 or 165°F Coverplate.
QUICK RESPONSE (QR) EXTENDED COVERAGE SPRINKLERS LIGHT HAZARD
System Distance
Max Max Min Working Nom Below
Width Length Flow Pressure, K Ceiling
SIN Type (A) Ft (B) Ft GPM psig Factor In. Temp Rating, °F
xxxxxx
* The 155 or 160°F sprinkler utilizes a 135°F coverplate and the 200 or 212°F sprinkler utilizes a 165°F coverplate.
+ Utilizes a 135°F coverplate.
Dimension of wall on which a sidewall sprinkler is installed.
(B) Dimension perpendicular to wall on which a sidewall sprinkler is installed.
STANDARD RESPONSE (SR) EXTENDED COVERAGE SPRINKLERS ORDINARY HAZARD
+ Sprinklers are suitable for installation below noncombustible obstructed construction as described in NFPA 131999.
QUICK RESPONSE (QR) EXTENDED COVERAGE SPRINKLERS ORDINARY HAZARD
Min
Max Sprinkler
Width x Ordinary Flow Temp
Length Hazard Rate Nom Rating,
SIN Type Ft x Ft Group GPM KFactor °F
+ Sprinklers are suitable for installation below noncombustible obstructed construction as described in NFPA 131999.
CORROSION RESISTANT SPRINKLERS
Nom Coating
SIN Type KFactor Type Temp Rating, °F
HIGH TEMPERATURE, WAX COATED SPRINKLERS
Max Sprinkler
Nom Ambient Temp
SIN Type KFactor Temp, F Rating, F
INTERMEDIATE LEVEL SPRINKLERS
Response Nom
SIN* Type Type KFactor Temp Rating, °F
* These sprinklers are available with or without sprinkler guards Models G1 and G4 as covered under File MS26602.
SPRINKLERS FOR STORAGE PROTECTION (CONTROL MODE DENSITY AREA)
Response Nom
SIN Type Type KFactor Temp Rating, °F
EXTENDED COVERAGE SPRINKLERS FOR STORAGE PROTECTION (CONTROL MODE DENSITY AREA)
Max
Response Width x Length Nom
SIN Type Ft x Ft Type KFactor Temp Rating, F
These sprinklers have not been investigated for use as a Control Mode Specific Application (CMSA) sprinkler in accordance with Chapter 21 of
NFPA 13.
SPRINKLERS FOR STORAGE PROTECTION (CONTROL MODE SPECIFIC APPLICATION)
SPECIFIC APPLICATION SPRINKLERS
Attic Sprinklers
Min
Roof Flow
Response Fire Pitch Max Max Rate Nom Temp
SIN Type Risk (In./In.) Width Ft Length Ft GPM KFactor Rating, F
++ For protection of Light Hazard attic spaces of wood truss or open wood joist construction with saddle type roofs in buildings 20 to 60 ft in
width and not exceeding a protection area of 400 sq ft per sprinkler when installed in accordance with the manufacturer' s installation and
design parameter instructions.
Window Sprinklers
Min
Distance Flow
Response Fire Nom Between Rate Temp
SIN Type Risk Type KFactor Sprinklers, Ft GPM Rating, F
+ Located between Mullions and not greater than 6 ft apart.
* For use on heatstrengthened or tempered glass windows without horizontal mullions having a maximum height of 13 ft. Combustibles must
be maintained at a minimum distance of 2 in. from the glass. This may be accomplished by use of a 3 ft. pony wall or any other method
acceptable to the authority having jurisdiction when installed in accordance with the manufacturer\'s installation and design parameter
instructions.
% For use on UL certified FireLite Plus ceramic glass (by Technical Glass Products) without horizontal mullions having a maximum height of 8
ft. Combustibles are not required to be maintained at any minimum distance from the glass when the sprinklers are installed in accordance
with the manufacturer\'s installation and design parameter instructions.
Authorities having jurisdiction shall be consulted to determine the hydraulic requirements for each installation.
Concealed Space Sprinklers
Height of Space, In. Max
Response Coverage Nom Temp
SIN Type Type Min Max Area, Ft 2 KFactor Rating, F
* Minimum distance between upper and lower joists.
** Wet or Dry pipe systems using steel pipe.
+ For use in light hazard flat concealed spaces incorporating noncombustible or wood truss construction. The Manufacturers Installation and
Design Parameter Instructions should be consulted for specific installation parameters, obstruction criteria and hydraulic design requirements.
++ For use in combustible solid wood and composite wood joist construction.
% For use in attic areas outside the scope of application for the BB, SD or HIP sprinklers.
Last Updated on 20141229
© 2015 UL LLC
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's FollowUp Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's FollowUp
Service. Always look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non
misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory
with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in
the following format: "© 2015 UL LLC".