R410A 60Hz
R410A 60Hz
6CVP0-01A
1. Model Names
Power Supply 8HP 10HP 12HP 14HP 16HP 18HP 20HP 22HP 24HP
3Ø, 460V, 60Hz 80DT2 100DT2 120DT2 140DT2 160DT2 180DT2 200DT2 220DT2 240DT2
3Ø, 220V , 60Hz 80BT2 100BT2 120BT2 - 160BT2 180BT2 200BT2 220BT2 240BT2
General information 1
2.2 Outdoor Units(220V)
ARUV80BT2
ARUV100BT2
ARUV120BT2
ARUN80BT2
ARUN100BT2
ARUN120BT2
ARUV160BT2
ARUV180BT2
ARUV200BT2
ARUV220BT2
ARUV240BT2
ARUN160BT2
ARUN180BT2
ARUN200BT2
ARUN220BT2
ARUN240BT2
ARUV260BT2
ARUV280BT2
ARUV300BT2
ARUV320BT2
ARUV340BT2
ARUV360BT2
ARUN260BT2
ARUN280BT2
ARUN300BT2
ARUN320BT2
ARUN340BT2
ARUN360BT2
General information 3
4. Nomenclature
ARU N 100 D T 2
Serial Number
Air Discharge Type
S:Side Discharge
T:Top Discharge
Electrical Ratings
8: 3Ø, 380 ~ 415V, 50Hz 9: 3Ø, 380V, 60Hz
A: 3Ø, 220V, 50Hz B: 3Ø, 220V, 60Hz
L: 3Ø, 380 ~ 415V, 50Hz / 3Ø, 380V, 60Hz
D: 3Ø, 460V, 60Hz
Total Cooling Capacity in Horse Power(HP) unit
EX) 10HP➞'100'
Combination of Inverter Type and
Cooling Only or Heat Pump
N: Inverter and H/P V: Inverter and C/O
B: Inverter and Heat Recovery
System with
Outdoor Unit using R410A
General information 5
Power Supply: Outdoor Unit (3Ø, 220V, 60Hz)
■ Cooling Only
8 Outdoor Unit
Power Supply: Outdoor Unit (3Ø, 220V, 60Hz)
■ Heat pump
General information 9
3.1.2 ARUV100DT2, ARUV120DT2, ARUV140DT2, ARUV160DT2,ARUV80BT2, ARUV100BT2,
ARUV120BT2
Cooling Operation
Fan Fan
Fil ter Fil ter
High Temp.
Sensor
Gas Pipe
Hot Gas
Valve
Low Temp.
s
Discharge Discharge
Temp. Temp.
Sensor(I) Sensor(C)
Con stant
Inverter
Acc umulator Speed
Comp
Comp
Sub-Cooling
Outlet Temp.
Sensor
Liquid Injection
s
Sub-Cooler
Sub-Cooling
Inlet Temp.
Sensor
Sub-Coo ling EEV
Outdoo r Uni t
Remarks
Press ure Switch SVC Valve Strainer
EEV
23 Outdoor Unit
Heating Operation
Fan Fan
Fil ter Fil ter
Outdoor
Temperature
Sensor
Outdoor Unit
HEX Temperature
Sensor
Hot Gas
Valve
Low
s
Comp Comp
Disc harge Disc harge
Temperature Temperature
Sensor Con stant Sensor
Inverter
Acc umulator Speed
Comp
Comp
Sub-cooli ng Circuit
Outlet Temperature
Sensor
Liquid Injection
s
Sub-Cooler
Sub-cooli ng Circuit
Inlet Temperature
Sensor
Remarks
Press ure Switch SVC Valve Strainer
EEV
Outdoor Unit 28
4.3 Cooling Only(3Ø, 220V)
4.3.1 ARUV80BT2, ARUV100BT2, ARUV120BT2
Outdoor Unit 34
4.4 Heat Pump(3Ø, 220V)
4.4.1 ARUN80BT2, ARUN100BT2, ARUN120BT2
35 Outdoor Unit
■ 1 Outdoor Unit - 3Ø, 220V
Power supply
1 Phase 60Hz
220V
WARNING
• Indoor Unit ground Lines are required for preventing electrical shock accident during current leakage,
Transmission disorder by noise effect and motor current leakage (without connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power supply.
• Install the main switch that can interrupt all the power sources in an integrated manner because this system consists of the
equipment utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase, momentary blackout or the power goes on and off while the prod-
uct is operating, attach a reversed phase protection circuit locally.
Running the product in reversed phase may break the compressor and other parts.
The GND terminal is a '–' terminal for the central controller, not Ground Line
Outdoor Unit 38
■ 2 Outdoor Units - 3Ø, 220V
WARNING
• Indoor Unit ground Lines are required for preventing electrical shock accident during current leakage,
Transmission disorder by noise effect and motor current leakage (without connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power supply.
• Install the main switch that can interrupt all the power sources in an integrated manner because this system consists of
the equipment utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase, momentary blackout or the power goes on and off while the
product is operating, attach a reversed phase protection circuit locally.
Running the product in reversed phase may break the compressor and other parts.
The GND terminal is a '–' terminal for the central controller, not Ground Line
39 Outdoor Unit
6.1.1 Heat Pump
■ 60Hz 460V
Unit Power Supply COMP OFM
Model
Hz Volts Voltage-range MCA MOP MSC RLA kW FLA
8HP 60 460 414~506 14.4 22.6 21.36 20.2 0.7 4.0
18HP 60 460 414~506 28.6 45.1 21.36/61 /21.36 20.2/10.4 /20.2 1.4 8.0
20HP 60 460 414~506 32.4 51.9 21.36/61 /21.36 20.2/10.4 /20.2 1.4 8.0
22HP 60 460 414~506 37.8 61.7 21.36/61 /21.36 20.2/11.5/20.2 1.4 8.0
24HP 60 460 414~506 42.1 69.3 21.36/61 /21.36 20.2/11.5/20.2 1.4 8.0
26HP 60 460 414~506 49.5 82.7 21.36/61 /21.36/61 20.2/11.5/20.2/10.4 1.4 8.0
28HP 60 460 414~506 53.3 89.5 21.36/61 /21.36/61 20.2/11.5/20.2/11.5 1.4 8.0
30HP 60 460 414~506 58.7 99.3 21.36/61 /21.36/61 20.2/11.5/20.2/11.5 1.4 8.0
32HP 60 460 414~506 62.9 106.8 21.36/61 /21.36/61 20.2/11.5/20.2/11.5 1.4 8.0
■ 60Hz 220V
Unit Power Supply COMP OFM
Model
Hz Volts Voltage-range MCA MOP MSC RLA kW FLA
8HP 60 220 198 ~242 31.1 52.8 19/125 19.2/18.7 0.7 4
10HP 60 220 198 ~242 36.2 61.9 19/125 19.2/18.7 0.7 4
12HP 60 220 198 ~242 44 76 19/125 19.2/18.7 0.7 4
16HP 60 220 198 ~242 62.2 105.6 19/125/19/125 19.2/18.7/19.2/18.7 1.4 8
18HP 60 220 198 ~242 67.3 114.7 19/125/19/125 19.2/18.7/19.2/18.7 1.4 8
20HP 60 220 198 ~242 72.4 123.8 19/125/19/125 19.2/18.7/19.2/18.7 1.4 8
22HP 60 220 198 ~242 80.2 137.9 19/125/19/125 19.2/18.7/19.2/18.7 1.4 8
24HP 60 220 198 ~242 88 152 19/125/19/125 19.2/18.7/19.2/18.7 1.4 8
26HP 60 220 198~242 112.1 192.2 19/125/19/125/19/125 19.2/18.7/19.2/18.7/19.2/18.7 2.10 12.0
28HP 60 220 198 ~ 242 113.8 195.2 19/125/19/125/19/125 19.2/18.7/19.2/18.7/19.2/18.7 2.10 12.0
30HP 60 220 198 ~ 242 118.1 203.0 19/125/19/125/19/125 19.2/18.7/19.2/18.7/19.2/18.7 2.10 12.0
32HP 60 220 198 ~ 242 123.5 212.7 19/125/19/125/19/125 19.2/18.7/19.2/18.7/19.2/18.7 2.10 12.0
34HP 60 220 198 ~ 242 128.9 222.4 19/125/19/125/19/125 19.2/18.7/19.2/18.7/19.2/18.7 2.10 12.0
36HP 60 220 198 ~ 242 134.3 232.1 19/125/19/125/19/125 19.2/18.7/19.2/18.7/19.2/18.7 2.10 12.0
Outdoor Unit 42
Notes:
1. Voltage range (Example)
Voltage supplied to the unit terminals should be within the Selection of proper circuit breaker
minimum and maximum range
➀ 10HP- Rated running current : 11.23A(460V)
2. Maximum allowable voltage unbalance between phase
is 2 % ➁ MCA = (1.25 x Load1) + Load2
3. MCA / MOP = (1.25 x 11.23) + 4.0 = 18.0A
MCA = (1.25 x Load1) + Load2 ➂ MOP = (2.25 x Load1) + Load2
MOP = (2.25 x Load1) + Load2 = (2.25 x 11.23) + 4.0 =29.2A
- Load1 : Rated running current of largest motor
(Compressor or other motor) MCA : Minimum Circuit Amperes (A)
- Load2 : any other load rated 1.0A or more MOP : Maximum rating Over current Protective device
4. Select wire spec. based on the MCA MSC : Maximum Starting Current
RLA : Rated Load Amperes (A)
5. Select proper circuit breaker as given below OFM : Outdoor Fan Motor
MCA < Selected circuit breaker ≤ MOP kW : Fan Motor rated output (kW)
6. Recommended circuit breaker is ELCB (Earth Leakage FLA : Full Load Amperes (A)
Circuit Breaker)
7. MSC & RLA are measured as the compressor only test
condition.
8. MSC values
21.36/61 : MSC of (INV. Comp) / (Const. Comp.1)
9. RLA is measured during each individual compressor test
condition.
20.2/10.4 : RLA of (INV. Comp) / (Const. Comp.1)
10. OFM is measured as the outdoor unit test condition
43 Outdoor Unit
3. Installation Space
3.1 Individual Installation
■ Basic space required
A space of at least 250mm is necessary at the back for inlet air. Taking servicing, etc. from the rear into
account, a space of about 700mm should be provided, the same as at the front.
C
Control Box
Control Box
Front Side Front Side Front Side
A A A
■ When inlet air enters from right and left sides of unit
A 700mm or more
(Control box is open/close type)
A B
B 250mm or more h
C 150mm from the wall Rear Side
B
C C
CAUTION H
Front Side
A
C C C C
A 250mm or more
(350mm or more at the coastal area.)
B 150mm from the wall A
h
than the whole height of product by (h), < Side view > < Top view >
Add (h) to , .
Rear Side Rear Side
A A
B B B B
Installation 2
■ When unit is surrounded by walls
B B B B B B
A
A
A 45° or more B B
B 200mm or more
C C
C 250mm or more
C
C
D Air guide
E Air outlet guide (Procured at the site) D 58
7.6
F 250mm or more )
F
E
372.5
390
.5
723
125
3 Installation
3.2 Collective/ Continuous Installation
Space required for collective installation and continuous installation:When installing several units, leave
space between each block as shown below considering passage for air and people.
A (Be opened)
B 900mm or more (control box is of a open/close type)
C 250mm or more
D 150mm or more
Front Side
Front Side
Rear Side
Rear Side
Rear Side Rear Side Rear Side Rear Side
Front Side
Front Side
Front Side
Rear Side
Rear Side
Rear Side
Front Side Front Side Front Side Front Side
❈ B = 1250mm or more
at the coastal area
Front Side
Front Side
Front Side
Rear Side
Rear Side
Rear Side
or strong wind area
Front Side
Front Side
Rear Side
Rear Side
Rear Side D Rear Side D Rear Side D Rear Side
Front Side
Front Side
Rear Side
Rear Side
Rear Side
Front Side
Front Side
Rear Side
Rear Side
Installation 4
5.2 Foundation for Installation
• Fix the unit tightly with bolts as shown below so that unit will not fall down due to earthquake or gust.
• Use the H-beam support as a base support
• Noise and vibration may occur from the floor or wall since vibration is transferred through the installation
part depending on installation status. Thus, use anti-vibration materials (cushion pad) fully (The base pad
shall be more than 200mm.
Anti-vibration
Spring washer materials
Frame Nut Concrete Four bolt are
base required
H-Beam 3 thread ridges
75
75
200
200
100
WARNING
• Be sure to install unit in a place strong enough to withstand its weight.
Any lack of strength may cause unit to fall down, resulting in a personal injury.
• Have installation work in order to protect against a strong wind and earthquake. Any installation
deficiency may cause unit to fall down, resulting in a personal injury.
• Especially take care for support strength of the floor surface, water drain processing (processing of
water flown out from the outdoor unit during operation) and paths of the pipe and wiring when mak-
ing a base support.
• Don't use a tube or pipe for water drain in the base pan and perform water drain processing by
using the drain path. Water drain may not be done due to freezing of a tube or pipe.
Water
Drain
Path
Installation 8
6.2 Connection of High/Low Pressure Common Pipe
Slave
Outdoor Unit Slave2
Outdoor
Unit
Slave1
Outdoor
Master Unit Master
Outdoor Unit Outdoor Unit
(Front) (Side)
WARNING
After installing the pipe, clog the pipe excavation inlet of the front panel and the side panel
(Wire may be damaged due to entry of rats, animals, etc).
Installation 10
7. Refrigerant Piping System
7.1 Refrigerant Pipe Connection
7.1.1 Y Branch Method
1 Outdoor Units
Example : 5 Indoor Units connected
: Outdoor Unit
: 1st branch (Y branch)
: Indoor Units
100m
l 40m (90m : Conditional application)
15m
Master
Example : 5 Indoor Units connected
: Outdoor Unit
: 1st branch (Y branch) 10m
or less
: Indoor Units
: Downward Indoor Unit
: Connection branch pipe L150m(200m: Conditional application)
between Outdoor units:
100m
15m
13 Installation
3 Outdoor Units Slave2
Slave1
Example : 5 Indoor Units Master
connected 10m
or less
: Outdoor Unit
: 1st branch (Y branch)
: Indoor Units
: Downward Indoor Unit
: Connection branch pipe L150m(200m: Conditional application)
H 100m
between Outdoor units: l 40m(90m: Conditional application)
ARCNN30
: Connection branch pipe
between Outdoor units:
ARCNN20
h 15m
Piping length from outdoor branch to outdoor unit ≤10m, equivalent length:max 13m (for 18HP or more)
Conditional Application
To satisfy below condition to make 40 m ~ 90 m(131 ft ~295 ft) of pipe length after first branch.
1) Diameter of pipes between first branch and the last branch should be increased by one step, except pipe diameter
B,C,D is same as Diameter A
Ø6.35(1/4 inch) → Ø 9.52(3/8 inch) → Ø 12.7(1/2 inch) → Ø 15.88(5/8 inch) → Ø 19.05(3/4 inch) → Ø 22.2(7/8 inch) →
Ø 25.4*(1* inch), Ø 28.58(1-1/8 inch) → Ø 31.8*(1-1/4* inch), Ø 34.9(1-3/8 inch) → Ø 38.1*(1-1/2* inch)
* : It is not necessary to size up.
If the increased pipe size is larger than main pipe size, then increase the main(liquid,gas) pipe size as much as the
increased pipe size.
2) While calculating whole refrigerant pipe length, pipe B,C,D length should be calculated twice.
A+Bx2+Cx2+Dx2+a+b+c+d+e ≤ 1,000 m
3) Length of pipe from each indoor unit to the closest branch (a,b,c,d,e) ≤ 40m
4) [Length of pipe from outdoor unit to the farthest indoor unit 5 (A+B+C+D+e)]
- [Length of pipe outdoor unit to the closest indoor unit 1 (A+a)] ≤ 40m
Installation 14
➲ Refrigerant pipe diameter from branch to branch (B,C,D)
Downward Indoor Unit total capacity Liquid pipe Gas pipe
[kW(Btu/h)] [mm(inch)] [mm(inch)]
<22.4(76,400) Ø9.52(3/8) Ø19.05(3/4)
< 33(112,600) Ø9.52(3/8) Ø22.2(7/8)
< 47(160,400) Ø12.7(1/2) Ø28.58(1-1/8)
< 71(242,300) Ø15.88(5/8) Ø28.58(1-1/8)
< 104(354,900) Ø19.05(3/4) Ø34.9(1-3/8)
• * : Assume equivalent piping length of Y branch to be 0.5m, that of header to be 1m, calculation
purpose.
• ** : To apply Conditional Application
Upward Outdoor Unit Liquid pipe Gas pipe Upward Outdoor Unit Liquid pipe Gas pipe
total capacity [HP] [mm(inch)] [mm(inch)] total capacity [HP] [mm(inch)] [mm(inch)]
8 Ø9.52(3/8) Ø19.05(3/4) 16(220V) Ø12.7(1/2) Ø28.58(1-1/8)
10 Ø9.52(3/8) Ø22.2(7/8) 18, 20, 22, 24 Ø15.88(5/8) Ø28.58(1-1/8)
12~16 Ø12.7(1/2) Ø28.58(1-1/8)
18~22 Ø15.88(5/8) Ø28.58(1-1/8)
24 Ø15.88(5/8) Ø34.9(1-3/8) Upward Outdoor Unit Liquid pipe Gas pipe
total capacity [HP] [mm(inch)] [mm(inch)]
26~34 Ø19.05(3/4) Ø34.9(1-3/8)
8 Ø9.52(3/8) Ø19.05(3/4)
36 Ø19.05(3/4) Ø41.3(1-5/8)
10 Ø9.52(3/8) Ø22.2(7/8)
12, 14, 16(460V) Ø12.7(1/2) Ø28.58(1-1/8)
15 Installation
7.1.2 Header Method
1 Outdoor Unit
Example : 6 Indoor Units connected
: Outdoor Unit
: 1st branch
: Indoor Units
: Sealed piping
L 150m
H 100m
40m
15m
2 Outdoor Units
Slave
Example : 6 Indoor Units connected Master
: Outdoor Unit
10m
: Header branch or less
: Indoor Units
: Sealing
: Connection branch pipe L 150m
between Outdoor units:
H 100m
40m
ARCNN20
15m
Installation 16
3 Outdoor Units Slave2
Slave1
Example : 6 Indoor Units connected Master
: Outdoor Unit
10m
: Header branch or less
: Indoor Units
: Sealing
: Connection branch pipe
L150m
between Outdoor units:
H 100m
ARCNN30 l 40m
• * : Assume equivalent piping length of Y branch to be 0.5m, that of header to be 1m, calculation purpose
• Indoor Unit should be installed at lower position than the header.
• Piping length from outdoor branch to outdoor unit ≤ 10m, equivalent length : max 13m
(for 18HP or more)
17 Installation
7.1.3 Combination of Y branch/header method
H 100m
: Sealed piping
L 150m
40m
h 15m
Branch pipe can not be used after header
: Y branch
10m
: Indoor Unit or less
: Connection branch pipe
between Outdoor units:
ARCNN20
: Header
H 100m
: Sealed piping
L 150m
40m
h 15m
Installation 18
3 Outdoor Units Slave2
Slave1
Example : 5 Indoor Units connected Master
: Outdoor Unit
: 1st branch(Y branch) 10m
: Y branch or less
: Indoor Unit
: Connection branch pipe
between Outdoor units:
ARCNN30
H 100m
: Connection branch pipe L 150m
between Outdoor units: L40m
h 15m
ARCNN20
: Header
: Sealing
• * : Assume equivalent pipe length of Y branch to be 0.5m, that of header to be 1m, calculation purpose
• Indoor Unit should be installed at lower position than the header.
19 Installation
7.2 Connection between outdoor and outdoor unit
■ Example of Pipe Connection between Outdoor
7.2.1 Pipe Connection between Outdoors
CAUTION
Apply oil trap between outdoor unit installed Higher level and outdoor unit installed lower level.
Oil may be accumulated in stopped outdoor unit.
Less than 2m
23 Installation
7.2.3 In case pipe length between outdoors is 2m or more.
When the piping length between Branch of Outdoor units or between Branch and outdoor units.
Is 2 m or more, prepare a oil trap 200 mm or more as shown below) on the gas pipe line location.
Less than 2 m from branch.
Oil Trap
200mm
or more
Less than 2m
2m or more
2m or more 2m or more
Oil is accumulating in
outdoor units when
system stops
Installation 24
7.3 The amount of Refrigerant
The calculation of the additional charge should take into account the length of pipe.
A Additional charge (kg(lb)) Ex 10HP
Outdoor Unit a : ø6.35(1/4), 10m
B Product Charge(kg(lb))
Indoor Unit b : ø6.35(1/4), 10m
= Total liquid pipe (m): Ø22.2mm(7/8inch) x 0.354(kg/m) A : ø9.52(3/8), 40m c : ø6.35(1/4), 10m
B : ø9.52(3/8), 20m d : ø6.35(1/4), 10m
+ Total liquid pipe (m): Ø19.05mm(3/4inch) x 0.266(kg/m)
C : ø9.52(3/8), 20m e : ø6.35(1/4), 10m
+ Total liquid pipe (m): Ø15.88mm(5/8inch) x 0.173(kg/m)
A
+ Total liquid pipe (m): Ø12.7mm(1/2inch) x 0.118(kg/m) C X
Total amount(kg) = A + B
CAUTION If a negative result is obtained from Additional Charge = A x 0.061 + B x 0.061 + C x 0.061
the calculation, no refrigerant needs + (a+b+c+d+e) x 0.022 + CF
to be added. = 40 x 0.061 + 20 x 0.061 + 20 x 0.061
+ (10 x 5) x 0.022 + (0) (CF)
= 5.98(kg)
• 460V
HP 8 10 12 14 16 18 20 22 24 26 28 30 32
8 8 8 8 8 8+8 8+8 8+8 8+8 8+8 8+8 8+8 8+8
Product Charge kg(lbs) (17.6) (17.6) (17.6) (17.6) (17.6) (17.6+17.6) (17.6+17.6) (17.6+17.6) (17.6+17.6) (17.6+17.6) (17.6+17.6) (17.6+17.6) (17.6+17.6)
-1 0 1 2 3 -1 0 1 2 3 4 5 6
CF kg(lbs) (-2.2) (0) (2.2) (4.4) (6.6) (-2.2) (0) (2.2) (4.4) (6.6) (8.8) (11.0) (13.2)
• 220V
HP 8 10 12 16 18 20 22 24
Product Charge kg(lbs) 8(17.6) 8(17.6) 8(17.6) 8+8(17.6+17.6) 8+8(17.6+17.6) 8+8(17.6+17.6) 8+8(17.6+17.6) 8+8(17.6+17.6)
CF kg(lbs) -1(-2.2) 0(0) 1(2.2) -2(-4.4) -1(-2.2) 0(0) 1(2.2) 2(4.4)
HP 26 28 30 32 34 36
Product Charge kg(lbs) 8+8+8(17.6+17.6+17.6) 8+8+8(17.6+17.6+17.6) 8+8+8(17.6+17.6+17.6) 8+8+8(17.6+17.6+17.6) 8+8+8(17.6+17.6+17.6) 8+8+8(17.6+17.6+17.6)
CF kg(lbs) -2(-4.4) -1(-2.2) 0(0) 1(2.2) 2(4.4) 3(6.6)
25 Installation
7.4 Distribution Method
7.4.1 Line Distribution
Header
27 Installation
7.5 Refrigerant pipe fitting
7.5.1 Caution
1. Use the following materials for refrigerant piping.
• Material: Seamless phosphorous deoxidized copper pipe
• Wall thickness : Comply with the relevant local and national regulations for the designed pressure 3.8MPa. We
recommend the following table as the minimum wall thickness.
Outer diameter 6.35 9.52 12.7 15.88 19.05 22.2 25.4 28.58 31.8 34.9 38.1 41.3
[mm(inch)] (1/4) (3/8) (1/2) (5/8) (3/4) (7/8) (1) (1-1/8) (1-1/4) (1-3/8) (1-1/2) (1-15/16)
Minimum thickness 0.8 0.8 0.8 0.99 0.99 0.99 0.99 0.99 1.1 1.21 1.35 1.43
[mm(inch)] (0.03) (0.03) (0.03) (3.25) (0.04) (0.04) (0.04) (0.04) (0.04) (0.05) (0.05) (0.06)
2. Commercially available piping often contains dust and other materials. Always blow it clean with a dry inert gas.
3. Use care to prevent dust, water or other contaminants from entering the piping during installation.
4. Reduce the number of bending portions as much as possible, and make bending radius as big as possible.
5. Always use the branch piping set shown below, which are sold separately.
Header
Y branch
4 branch 7 branch 10 branch
ARBLN01620 ARBLN03320 ARBL054 ARBL057 ARBL1010
ARBLN07120 ARBLN14520 ARBL104 ARBL107 ARBL2010
6. If the diameters of the branch piping of the designated refrigerant piping differs, use a pipe cutter to cut the
connecting section and then use an adapter for connecting different diameters to connect the piping.
7. Always observe the restrictions on the refrigerant piping (such as rated length, difference in height, and pip-
ing diameter).
Failure to do so can result in equipment failure or a decline in heating/cooling performance.
8. A second branch cannot be made after a header. (These are shown by .)
A A
A To Outdoor Unit
B Sealed Piping
9. The Multi V will stop due to an abnormality like excessive or insufficient refrigerant. At such a time, always
properly charge the unit. When servicing, always check the notes concerning both the piping length and the
amount of additional refrigerant.
10. Never use refrigerant to perform an air purge. Always evacuate using a vacuum pump.
11. Always insulate the piping properly. Insufficient insulation will result in a decline in heating/cooling perfor-
mance, drip of condensate and other such problems.
12. When connecting the refrigerant piping, make sure the service valves of the Outdoor Unit is completely
closed (the factory setting) and do not operate it until the refrigerant piping for the Outdoor and Indoor Units
has been connected, a refrigerant leakage test has been performed and the evacuation process has been
completed.
13. Always use a non-oxidizing brazing material for brazing the parts and do not use flux. If not, oxidized film
can cause clogging or damage to the compressor unit and flux can harm the copper piping or refrigerant oil.
Installation 28
8.2 DIP Switch Setting
8.2.1 Location of setting Switch
Main PCB
SW01B SW02B
(DIP S/W) (DIP S/W)
7 - Segment
SW02V
Auto addressing
Installation 38
■ Checking according to dip switch setting
1. You can check the setting values of the Master outdoor unit from the 7 segment LED.
The dip switch setting should be changed when the power is OFF.
2. It checks whether the input is properly performed without the bad contact of the dip switch or not
CAUTION
Product may not properly operate if the relevant DIP switch is not properly setup.
Model Code
3Ø 220V 3Ø 460V
Model Code Unit (HP) Model Code Unit (HP)
150 8 171 8
151 10 172 10
152 12 173 12
174 14
175 16
39 Installation
ENGINEERING PRODUCT DATA BOOK
R410A 50/60Hz
6CVP0-01A
P/No.: MFL55028401
Air Conditioner
20 Yeouido-dong, Yeongdeungpo-gu,
Yeouido P.O.Box 335 Seoul,
150-721, Korea.
http://www.lgeaircon.com