Profi S Link - E
Profi S Link - E
Profi S Link - E
0 Content
0
0.1 Document-History ........................................................................................... 0-2
0.2 Trademarks ..................................................................................................... 0-2
1 Quickstart
1.1 Summary......................................................................................................... 1-1
1.2 Communication network ................................................................................. 1-1
1.3 PG5 Hardware settings of the stations connected to Profi-S-Bus .................. 1-2
1.4 Online settings ................................................................................................ 1-3
1.4.1 Configuration of the Profi-S-Link ................................................................... 1-3
1.4.2 Configuration of the online settings of the CPU’s.......................................... 1-5
2 Technical characteristics
2.1 General ........................................................................................................... 2-1
2.2 Profi-S-Bus interface ....................................................................................... 2-1
2.3 Ethernet interface............................................................................................ 2-2
2.4 Standard Ethernet accessories ....................................................................... 2-3
2.5 LED’s .............................................................................................................. 2-3
2.6 Default parameters ......................................................................................... 2-3
3 Networking possibilities
4 Troubleshooting
5 Appendix
5.1 Icons ............................................................................................................... 5-1
5.2 Product and documentation concept .............................................................. 5-1
5.3 Technical support ............................................................................................ 5-2
5.4 Workshops, training literature ......................................................................... 5-3
5.5 Reliability and safety of electronic controllers ................................................. 5-3
5.6 About ourselves .............................................................................................. 5-4
Addresses of SAIA-Burgess companies ......................................................... 5-5
0.1 Document-History
0
Document-No. Edition Modification Publication Remarks
26/834 PE1 15.05.2004 31.05.2004 Preliminary Edition
E1 01.07.2004 Published Edition
0.2 Trademarks
1 Quickstart
1.1 Summary
1
Profi-S-Link is an Ethernet to Profibus Gateway that supports programmation and
supervision of the new generation of PCD-CPU’s with Profi-S-Bus protocol, like
the PCD2.M480 or the PCD3.Mxxxx.
This manual describes how to establish communication between the software tool
PG5 and the PCD-CPU’s that are connected via Profi-S-Bus.
Profi-S-Link
PG5 + IP: 192.168.12.130 Profi-S-Bus
Supervision Profi-S-Bus station 3 station 11
S-Bus station 11
Profi-S-Bus
station 12
Ethernet S-Bus station 12
Profi-S-Bus
Profi-S-Bus station 13
S-Bus station 13
Ethernet network
Profi-S-Bus network
Select the hardware type of the PCD-CPU. Only the latest PCD-CPU’s (PCD2.M480
and PCD3.Mxxxx) support Profi-S-Bus. The PCD2.M480 for instance supports up to
3 Profi-S-Bus ports.
i
The PCD’s have a Profi-S-Bus and a S-Bus address. To avoid confusion we recom-
mend to use the same address for both, even though they are independent.
After defining the hardware settings, download them into the PCD
memory with the button Download. If the download was not success-
full, a dialogue window appears with the message: No response. Verify the online
settings. Only the PGU on S-Bus, USB channels allow to communicate with a PCD 1
independent of its harware settings.
In the online settings select the button Setup, then Profi-S-Link settings.
i
The buttons Download and Save store the parameters of Profi-S-Link in a file which
belongs to the common files of the project. This file has the name of the channel.
If several Profi-S-Links are present in the same PG5 project, we recommend to de- 1
fine a new channel for each Profi-S-Link using the menu Tools, Channels of the PG5
Project Manager.
A dialogue window shows the list of the Profi-S-Link hardware available only on
the local Ethernet subnet. For configuration select the desired Profi-S-Link with the
mouse and press OK.
The active Profi-S-Link is shown in the header of the following window. The next
selection of one of the buttons Download, Upload and Firmware does not show this
list, these commands use the last selected (active) Profi-S-Link. To change the active
Profi-S-Link, call the stations list with the button Life List.
If the Profi-S-Link is brand new (Address 0.0.0.0 per default) or is not lo-
cated in the local subnet, you can temporarily define an IP address to
communicate with the Profi-S-Link for the download and the upload of the settings.
For each CPU in the PG5 project verify the parameters of the Profi-S-Bus channel:
�������
2 Technical characteristics
2.1 General
Profi-S-Bus
interface RDY/RUN LED
(D-Sub)
Link LED
Ethernet interface
(RJ45)
cable length: 3 m
General data
Operating temperature 0 °C...+50 °C
Degree of protection IP 20
Dimensions (LxWxH) 65x48x16 mm
Weight approx. 140 g with cable
Minimum PG5 Version 1.3.100
Profi-S-Bus connector
Pin Signal Meaning
1 - not used
2 DGND Data and supply voltage reference
3 RxD/Txd-P Receive / transmit data-P
4 - not used
5 DGND Data and supply voltage reference
6 - not used
7 VP 24 V power supply (coming from the PCD)
8 Rxd/TxD-N Receive / transmit data-N
9 Shield- Housing / shield
Due to its compact dimensions, the Profi-S-Link is not protected against supply volt-
ages with inverse polarity.
RJ45 connector
Pin Signal Meaning
1 TX+ Transmit data
2 TX- Transmit data
3 RX+ Receive data
4 - not used
5 - not used
6 RX- Receive data
7 - not used
8 - not used
For configuration purposes we recommend a point to point connection. For this rea-
son you get with every Profi-S-Link the following accessories:
2.5 LED’s
IP Address 0.0.0.0
IP Baudrate auto negotiation
Profi-S-Bus Baudrate 1.5 MBaud,
Profi-S-Bus Station number 0
Profile SNet
Highest station address 126
Slot time 3000 bits
Min Tsdr 150 bits
Max Tsdr 980 bits
Quiet time 0 bit
Setup time 240 bits
Gap update factor 50
Max retry limit 1
Target rotation time 2021 bits
i
We recommend to use the DP profile, it allows to change data faster than with Snet
profile. The SNet profile is necessary to support the PCD3 RIO’s, this is why it is the
default setting.
Remember that all participants on a Profibus network (and therefore as well on Profi-
S-Bus networks) must contain identical timing settings.
3 Networking possibilities
PC Link
PG5 + IP 192.168.12.130
Supervision
connection 1
conn. 2
PC Link
IP 192.168.12.129
conn. 3
Ethernet Profi-S-Bus
i
Remember that PCD’s can only have one full protocol communication at a time (for
programming and debugging).
4 Troubleshooting
Problem:
The Life List shows no Profi-S-Link but with PG5 it is possible to go online with the
PCD.
Possible reason:
The Profi-S-Link is probably not in the same local Ethernet subnet. The Life List
does only display the Profi-S-Links in the local subnet. 4
Problem:
The Profi-S-Link doesn’t communicate after loading the settings or being put to the
supply voltage.
Possible reason:
Problem:
Possible reason:
5 Appendix
5.1 Icons
i
In manuals, this symbol refers the reader to further information in this manual or
other manuals or technical information documents.
Explanations beside this sign are valid only for the Saia-Burgess PCD Classic
ic
serie.
ss
la
C
Explanations beside this sign are valid only for the Saia-Burgess PCD xx7 serie.
7
xx
Any questions that you cannot answer by referring to the documentation will be dealt
with promptly and reliably for you by the Saia® PCD Support Team. The team is
based in Switzerland and can be reached by
phone: +41 26 672 71 11 or by
E-Mail: [email protected]
The addresses of Saia-Burgess sales companies and agents for other sales areas
can be found under http://www.saia-burgess.com
5.4 Workshops, training literature
If all these points are taken into consideration, the SAIA PCD will provide you with a
modern, safe programmable controller to control, regulate and monitor your installa-
tion with reliability for many years.
5.6 About ourselves
With full technical knowledge of all system elements and with quality-oriented busi-
ness processes, SBC is equipped to provide unique, custom solutions regarding
range of use, functionality, openness, flexibility, reliability and price.
These core competencies, combined with innovative strength, a broad product range
and a readiness to implement special customer requests rapidly, have made SBC the
attractive, competitive partner of choice for a large number of international customers.