Power Quality and Grid Code Issues in Wind Energy Conversion System
Power Quality and Grid Code Issues in Wind Energy Conversion System
Power Quality and Grid Code Issues in Wind Energy Conversion System
5,900
Open access books available
145,000
International authors and editors
180M Downloads
154
Countries delivered to
TOP 1%
most cited scientists
12.2%
Contributors from top 500 universities
http://dx.doi.org/10.5772/54704
1. Introduction
The aim of the electric power system is to produce and deliver to the consumer’s electric
energy of defined parameters, where the main quantities describing the electric energy are
the voltage and frequency. During normal operation of system the frequency varies as a
result of the variation of the real power generated and consumed. At the same time, because
of voltage drops in the transmission lines and transformers it is impossible to keep the
voltage at the nominal level in all the nodes of the power system. It is also impossible to
keep an ideal sinusoidal shape of the voltage or current waveform due to the nonlinearities
in many devices use for electric energy generation, transmission and at end users. That is
why the electric power system require to keep the quantities near the nominal value[1]-[5].
Recently, the deregulated electricity market has also opened the door for customers own
distributed generation due to economical and technical benefit. The liberalization of the grid
leads to new management structures, in which the trading of energy is important. The need
to integrate the renewable energy like wind energy into power system is to minimize the
environmental impact on conventional plant of generation. The conventional plant uses
fossil fuels such as coal & petroleum products to run the steam turbines and generate the
thermal power. The fossil fuel consumption has an adverse effect on the environment and it
is necessary to minimize the polluting and exhausting fuel. The penetration of renewable
energy especially wind has been increasing fast during the past few years and it is expected
to rise more in near future. Many countries around the world are likely to experience similar
penetration level. During the last decade of the twentieth century, worldwide wind energy
capacity is doubled approximately every three years.
Today’s trends are to connect all size of generating units like wind farm,solar farm,biogas
generation and conventional source like coal,hydro,nuclear power plant in to the grid
system shown in Fig.1.0
© 2013 Mohod and Aware, licensee InTech. This is an open access chapter distributed under the terms of
the Creative Commons Attribution License (http://creativecommons.org/licenses/by/3.0), which permits
unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited.
22 An Update on Power Quality
The critical power quality issues related to integration of wind farms have been identified
by team of Riso National Laboratory and Danish Utility Research Institute, Denmark and
Electronic Research and Development Centre, India in Nov.1998 .The power quality in
relation to a wind turbine describe the electrical performance of wind energy generating
system. It reflects the generation of grid interference and the influence of a wind turbine on
power and voltage quality of grid. The issue of power quality is of great importance to the
wind turbines. There has been an extensive growth and quick development in the
exploitation of wind energy in recent years [6]-[7]. The individual units can be of large
capacity up to 5 MW, feeding into distribution network, particularly with customers
connected in close proximity. However with rapidly varying voltage fluctuations due to the
nature of wind, it is difficult to improve the power quality with simple compensator.
Advance reactive power compensators with fast control and power electronic have emerged
to supersede the conventional reactive compensator [8]-[9].
It has been suggested that today’s industrial development are related with generalized use
of computers, adjustable speed drives and other microelectronic loads. It also becomes an
increasing concern with power quality to the end customer. The presence of harmonic and
reactive power in the grid is harmful, because it will cause additional power losses and
malfunction of grid component. The massive penetration of electronically controlled devices
and equipments in low voltage distribution network is responsible for further worsening of
power-quality problem [10]-[13].
The problems are related to the load equipment and devices used in electric energy
generation. Now a days the transmission and distribution system become more sensitive to
power quality variation than those used in the past. Many new devices contain
microprocessor based controls and electronics power elements that are sensitive to many
types of disturbances. The wind turbine generating systems are the highly variable sources
of energy and wind turbine are belonging to the source of such problem.
The wind power in the electric grid system affects the voltage quality. To assess this effect,
the knowledge of about the electrical characteristic of wind turbine is needed. The electrical
characteristics of wind turbine are manufacturer’s specification and not site specification.
This means that by having the actual parameter values for a specific wind turbine the
expected impact of the wind turbine on voltage quality is important. The need for consistent
and replicable documentation of the power quality characteristics of wind turbines, the
International Electro-technical Commission (IEC) started work to facilitate for power quality
in 1996. As a result, IEC 61400-21 was developed and today most wind turbines
manufacturers provide power quality characteristic data accordingly. Wind turbines and
their power quality will be certified on the basis of measurements according to national or
international guidelines. These certifications are an important basis for utilities to evaluate
the grid connection of wind turbines and wind farms.
The power quality is defined as set of parameters defining the properties of the power
supply as delivered to user in normal operating condition in terms of continuity of supply
and characteristics of voltage, frequency.
24 An Update on Power Quality
Today the measurement and assessment of the power quality characteristics of the grid-
connected wind turbines is defined by IEC Standard 61400-21 (wind turbine system)
prepared by IEC- Technical Committee 88.
The need of power quality in wind integration system and its issues are highlighted in
further section.
2
Ih
h2
DF( for current) = (2)
I1
Sn
d 100 Ku ( k ) (3)
Sk*
Sn - Rated apparent power of wind turbine and Sk* short circuit apparent power of grid.
The voltage dips of 3% in most of the cases are acceptable. When evaluating flicker and
power variation within 95% of maximum variation band corresponding to a standard
deviation are evaluated.
occur. The maximum number of above specified switching operation within 10-minute
period and 2-hr period are defined in IEC 61400-3-7 Standard.
Voltage sag is a phenomenon in which grid voltage amplitude goes below and then returns
to the normal level after a very short time period. Generally, the characteristic quantity of
voltage sag is described by the amplitude and the duration of the sags. The IEEE power
quality standards define the voltage sag when the amplitude of voltage is 0.1–0.9 p.u. value
and its duration is between 10 ms and 1 min. A voltage sag is normally caused by short-
circuit faults in the power network or by the starting up of Induction Generator/Motors.
The bad weather conditions, such as thunderstorm, single-phase earthed faults are the causes
of voltage sags. In addition, large electric loads such as large electrical motors or arc furnaces
can also cause voltage sags during the startup phase with serious current distortion.
The adverse consequences are the reduction in the energy transfer of electric motors. The
disconnection of sensitive equipments and thus the industrial process may bring to a
standstill.
2.4. Harmonics
The harmonics distortion caused by non-linear load such as electric arc furnaces, variable
speed drives, large concentrations of arc discharge lamps, saturation of magnetization of
transformer and a distorted line current. The current generated by such load interact with
power system impedance and gives rise to harmonics. The effect of harmonics in the power
system can lead to degradation of power quality at the consumer’s terminal, increase of
power losses, and malfunction in communication system. The degree of variation is assessed
at the point of common connection, where consumer and supplier area of responsibility
meet. The harmonics voltage and current should be limited to acceptable level at the point
of wind turbine connection in the system. This fact has lead to more stringent requirements
regarding power quality, such as Standard IEC 61000-3-2 or IEEE-519. Conventionally,
passive LC resonant filters have been used to solve power quality problems. However, these
filters have the demerits of fixed compensation, large size, and the resonance itself. To
overcome these drawbacks, active filters appear as the dynamic solution.
The IEC 61000-3-6 gives a guideline and harmonic current limits. According to standard IEC
61400-21 guideline, harmonic measurements are not required for fixed speed wind turbines
where the induction generator is directly connected to grid. Harmonic measurements are
required only for variable speed turbines equipped with electronic power converters. In
general the power converters of wind turbines are pulse-width modulated inverters, which
have carrier frequencies in the range of 2-3 kHz and produce mainly inter harmonic
currents.
The harmonic measurement at the wind turbine is problem due to the influence of the
already existing harmonic voltage in the grid. The wave shape of the grid voltage is not
sinusoidal. There are always harmonics voltages in the grid such as integer harmonic of 5th
and 7th order which affect the measurements.
Power Quality and Grid Code Issues in Wind Energy Conversion System 27
Today’s variable speed turbines are equipped with self commutated PWM inverter system.
This type of inverter system has advantage that both the active and reactive power can be
controlled, but it also produced a harmonic current. Therefore filters are necessary to reduce
the harmonics.
The harmonic distortion is assessed for variable speed turbine with a electronic power
converter at the point of common connection. The total harmonic voltage distortion of
voltage is given as in (4).
40 Vh2
VTHD 100 (4)
h2 V1
Vh- hth harmonic voltage and V1 –fundamental frequency 50 Hz. The THD limit for various
level of system voltages are given in the table 1.0
40 I h2
ITHD 100 (5)
h2 I1
Where Ih - hth harmonic current and I1 –fundamental frequency (50) Hz. The acceptable level
of THD in the current is given in table 2.
Various standards are also recommended for individual consumer and utility system for
helping to design the system to improve the power quality. The characteristics of the load
and level of power system significantly decides the effects of harmonics. IEEE standards are
adapted in most of the countries. The recommended practice helps designer to limit current
and voltage distortion to acceptable limits at point of common coupling (PCC) between
supply and the consumer.
1. IEEE standard 519 issued in 1981, recommends voltage distortion less than 5% on
power lines below 69 kV. Lower voltage harmonic levels are recommended on higher
supply voltage lines.
28 An Update on Power Quality
2. IEEE standard 519 was revised in 1992, and impose 5% voltage distortion limit. The
standards also give guidelines on notch depth and telephone interface considerations.
3. ANSI/IEEE Standard C57.12.00 and C57.12.01 limits the current distortion to 5% at full
load in supply transformer.
In order to keep power quality under limit to a standards it is necessary to include some of
the compensator. Modern solutions for active power factor correction can be found in the
forms of active rectification (active wave shaping) or active filtering.
2.5. Flickers
Flicker is the one of the important power quality aspects in wind turbine generating system.
Flicker has widely been considered as a serious drawback and may limit for the maximum
amount of wind power generation that can be connected to the grid. Flicker is induced by
voltage fluctuations, which are caused by load flow changes in the grid. The flicker emission
produced by grid-connected variable-speed wind turbines with full-scale back-to-back
converters during continuous operation and mainly caused by fluctuations in the output
power due to wind speed variations, the wind shear, and the tower shadow effects. The
wind shear and the tower shadow effects are normally referred to as the 3p oscillations. As a
consequence, an output power drop will appear three times per revolution for a three-
bladed wind turbine. There are many factors that affect flicker emission of grid connected
wind turbines during continuous operation, such as wind characteristics and grid
conditions. Variable-speed wind turbines have shown better performance related to flicker
emission in comparison with fixed-speed wind turbines.
The flicker study becomes necessary and important as the wind power penetration level
increases quickly. The main reason for the flicker in fixed speed turbines is to wake of the
tower. Each time a rotor blade passes the tower, the power output of the turbine is reduced.
This effect cause periodical power fluctuations with a frequency of about ~1 Hz. The power
fluctuation due to the wind speed fluctuation has lower frequencies and thus is less critical
for flicker. In general, the flicker of fixed speed turbines reaches its maximum at high wind
speed. Owing to smoothing effect, large wind turbine produced lower flicker than small
wind turbines, in relation to their size.
Several solutions have been proposed to mitigate the flicker caused by grid-connected wind
turbines. The mostly adopted technique is the reactive power compensation. It can be
realized by the grid-side converter of variable-speed wind turbines or the Static
synchronous compensator connected at the point of common coupling (PCC). Also, some
papers focus on the use of active power curtailment to mitigate the flicker [5].
The flicker level depends on the amplitude, shape and repetition frequency of the fluctuated
voltage waveform. Evaluating the flicker level is based on the flicker meter described in IEC
61000-4-15. Two indices are typically used as a scale for flicker emission, short-term flicker
index, Pst and long-term flicker index, Plt. Plt is estimated by certain process of the Pst values.
Power Quality and Grid Code Issues in Wind Energy Conversion System 29
It is assumed that wind turbines under study is running at normal operation; hence, the
long-term flicker index (Plt), which is based on a 120-min time interval, is equal to Pst and,
therefore, Pst is only considered in this work. The normalized response of the flicker meter
described in Figure 2.0.
10
Voltage
fluctuation
%
1
0.1
1 2 10 100
Hz
A quite small voltage fluctuation at certain frequency (8.8 Hz) can be irritable. The flicker
level (Pst ≤ 1) is a threshold level for connecting wind turbines to low voltage. The
measurements are made for maximum number of specified switching operation of wind
turbine with 10-minutes period and 2-hour period are specified, as given in (6)
S
Plt C( K ) n (6)
SK
Where plt - Long term flicker. C( K ) - Flicker coefficient calculated from Rayleigh
distribution of the wind speed. The Limiting Value for flicker coefficient is about 0.4, for
average time of 2 hours.
during off grid operation. Thus the sensitive equipments may be subjected to over/under
voltage, over/under frequency operation and other disadvantage of safety aspect. According
to IEC Standard, reactive power of wind turbine is to be specified as 10 min average value as
a function of 10-min. output power for 10%, 20% … 100% of rated power. The effective
control of reactive power can improve the power quality and stabilize the grid. Although
reactive power is unable to provide actual working benefit, it is often used to adjust voltage,
so it is a useful tool for maintaining desired voltage level. Every transmission system always
has a reactive component, which can be expressed as power factor. Thus the some method is
needed to manage the reactive power by injecting or absorbing VAr as necessary in order to
maintain optimum voltage level and enable real power flow. Until recently, this has been
especially difficult to effectively accomplish at a wind farms due to the variable nature of
wind. The suggested control technique in the thesis is capable of controlling reactive power
to zero value at point of common connection (PCC).The mode of operation is referred as
unity power factor.
Wind turbine generator systems (WTGS) are often located in the regions that have favorable
wind conditions and where their location is not burdensome. These regions are low
urbanized, which means that the distribution network in these regions is usually weak
developed. Such situation is typical for all countries developing a wind power industry.
The point of common coupling (PCC) of the WTGS and the power network parameter and
structure of grid is of essential significance in the operation of WTGS and its influence on
the system. WTGS can be connected to MV transmission line and to HV networks.
The WTGS connected to the existing MV transmission line, which feeds the existing
customers is presented in Figure 3.
The distance between WTGS and PCC is usually small up to a few kilometers. Such
connections are cheap as compare to other types of connection but greatly affected on
consumers load (power quality).
The location of WTGS connected to HV bus through a separate transmission line, when a
relatively large rated WTGS has to be connected in the power network, where the MV
network is weak. This type of connection are most expensive than other presented.
Power Quality and Grid Code Issues in Wind Energy Conversion System 31
MV 1
HV PCC
Loads
LV LV
Line-to-
Line 100
Voltage Lower
90
% value
of voltage
75 band
60
45
30
15
of the wind and the risk of instability due to lower degree of controllability. Many countries
in Europe and other parts of the world are developing or modifying interconnection rules
and processes for wind power through a grid code. The grid codes have identified many
potential adverse impacts of large scale integration of wind resources. The risk of voltage
collapse for lack of reactive power support is one of the critical issues when it comes to
contingencies in the power system. The low voltage ride through (LVRT) capability, which
is one of the most demanding requirement that have been included in the grid codes and
shown in Fig. 4.
It defines the operational boundary of a wind turbine connected to the network in terms of
frequency, voltage tolerance, power factor, fault ride through is regarded as the main
challenges to the wind turbine manufactures. The wind turbine should remain stable and
connected during the fault while voltage at the PCC drop to 15% of the nominal value i.e.
drops of 85% for the part of 150 msec. Only when the grid voltage fall below the curve, the
turbine is allowed to disconnected from the grid.
Significant barriers to interconnection are being perceived already with the requirements
of the new grid codes and there it is a need for a better understanding of the factors
affecting the behavior of the wind farm under severe contingencies such as voltage sags.
Wind farms using squirrel cage induction generators directly connected to the network
will suffer from the new demands, since they have no direct electrical control of torque or
speed, and would usually disconnect from the power system when the voltage drops
more than 10–20% below the rated value. In general, fulfillment of LVRT by reactive
compensation will require fast control strategies for reactive power in wind
turbines/farms with cage induction generators. The LVRT requirement, although details
are differing from country to country, basically demands that the wind farm remains
connected to the grid for voltage dips as low as 5%.
inter harmonic in the IEC 61000-3-6 are applicable to wind turbines. The inter harmonics
that are not a multiple of 50 Hz, since the switching frequency of the inverter is not constant
but varies, the harmonic will also vary. Consequently, the grid codes has been define to
specify the requirements that the wind turbines must meet in order to be connected to the
grid, including the capabilities of contributing to frequency and voltage control by adjusting
the active and reactive power supplied to the transmission system.
The first grid code was focused on the distribution level, after the blackout in the United
State in August 2003. The United State wind energy industry took a stand in developing
its own grid code for contributing to a stable grid operation. The rules for realization of
grid operation of wind generating system at the distribution network is defined as - per
IEC-61400-21.The grid quality characteristics and limits are given for references that the
customer and the utility grid may expect. According to Energy-Economic Law, the
operator of transmission grid is responsible for the organization and operation of
interconnected system. The grid code also covers some of the technical standards for
connection to the grid.
To ensure the safe operation, integrity and reliability of the grid is utmost important. It is
mentioned that reactive power compensation should ideally be provided locally by
generating reactive power as close to the reactive power consumption as possible. The
regional entity except generating stations, expected to provide local VAr
compensation/generation such that they do not draw VArs from the grid, particularly under
low-voltage condition. Indian grid code commission mentions that the charge for VArh shall
be at the rate of 25 paise/kVArh w.e.f.1.4.2010, for VAr interchanges.
The wind farms must be able to run at rated voltage at a specified voltage range. The
voltage range depends on the level of the voltage on the transmission system, which varies
from country to country.
The wind farms shall have a closed loop voltage regulation system. The voltage regulation
system shall act to regulate the voltage at the point by continuous modulation of the reactive
power output within its reactive power range, and without violating the voltage step
emissions.
The wind turbine generator (WTG) shall be equipped with voltage and frequency relays for
disconnection of the wind farm at abnormal voltages and frequencies. The relays shall be set
according to agreements with the regional grid company and the system operator. Following
are the technical requirements to be fulfilled to integrate the wind generation system.
Voltage Rise (u) -The voltage rise at the point of common coupling can be approximated as a
function of maximum apparent power Smax of the turbine, the grid impedances R and X at the
point of common coupling and the phase angle . The Limiting voltage rise value is < 2%
Voltage dips (d) - The voltage dips is due to start up of wind turbine and it causes a sudden
reduction of voltage. The acceptable voltage dips limiting value is 3 %.
Flicker-The measurements are made for maximum number of specified switching operation
of wind turbine with 10-minutes period and 2-hour period are specified. The Limiting Value
for flicker coefficient is about 0.4, for average time of 2 hours
Grid frequency- The grid frequency in India is specified in the range of 47.5-51.5 Hz, for
wind farm connection. The wind farm shall able to withstand change in frequency up to
0.5Hz/sec. Thus the requirements in the Grid Code can be fulfill the technical limits of the
network.
4. Conclusion
The chapter provides the challenges regarding the integration of wind energy in to the
power systems. Today the worldwide trend of wind power penetration is increased. The
integration of high penetration level of wind power into existing power system has
significant impact on the power system operation.
The wind turbines connected to weak grids have an important influence on power system.
The weak grid is characterized by large voltage and frequency variations, which affects
wind turbines regarding their power performance, safety and allied electrical components.
The strength of the distribution system is important from the point of power quality. The
needs for consistent qualification of power quality characteristics of wind turbines, the
International Electro-Technical Commission to facilitate for power quality parameters for
various issues are presented. The latest grid code requirements are to ensure that wind
farms do not adversely affect the power system operation with respect to security of supply,
reliability and for power quality.
Author details
Sharad W. Mohod
Ram Meghe Institute of Technology & Research,Badnera-Amravart, India
Mohan V. Aware
Visvesvaraya National Institute of Technology, Nagpur, India
Power Quality and Grid Code Issues in Wind Energy Conversion System 35
5. References
[1] H. Holitinen, R.Hirvonen, “Power system requirement for wind power.”, Wind Power
in Power System, T. Ackermann, Ed. New-York, pp 143-157, Wiley, 2005
[2] R.C. Bansal, Ahmed F. Zobaa, R.K. Saket, “Some issue related to power generation
using wind energy conversion system: An overview” Int. Journal of Emerging Electric
Power System, Vol. 3, No.2, pp 1-14, 2005.
[3] J.Charles Smith, Michael R. Milligan, Edgar A. DeMeo, “Utility wind integration and
operating impact state of the art., IEEE Trans on Energy Conversion Vol.22, No.3, pp 900-
907, August 2007.
[4] Z.Sadd-Saoud, N. Jenkins, “Models for predicting flicker induced by large wind
turbines” IEEE Trans on Energy Conversion, Vol.14, No.3, pp.743-751, Sept.1999.
[5] Weihao Hu, Zhe Chen, Yue Wang and Zhan Wang “Flicker Mitigation by Active Power
Control of Variable-Speed Wind Turbines With Full-Scale Back-to-Back Power
Converters”, IEEE Trans on Energy Conversion, Vol. 24, No. 3, pp.640-648, Sept. 2009
[6] F.Zhou, G.Joos, C.Abhey. ”Voltage stability in weak connection wind farm.” IEEE PES
Gen. Meeting, Vol. 2, pp.1483-1488, 2005
[7] S.W.Mohod, M.V.Aware, “Power quality issues & its mitigation technique in wind
generation, ”Proc. of IEEE Int. Conf. on Harmonics and Quality of Power (ICHQP), pp. 1-6,
Sept. 2008
[8] S.Z. Djokic, J.V. Milanovic, “Power quality and compatibility levels: A general
approach.”, IEEE Trans on Power Delivery, Vol.22, No.3, pp.1857-1862, July. 2007
[9] Helder J. Azevedo, Jose M. Ferreiraa, Antonio P. Martins, Adriano S. Carvalho, “An
active power filter with direct current control for power quality conditioning.” Electric
Power Component and System, Vol.26, pp.587-601, 2008.
[10] Z.Chen, E. Spooner, “Grid power quality with variable speed wind turbines”, IEEE
Trans on Energy Conversion, Vol.16, No.2, pp.148-156, June 2001.
[11] Dusan Graovac, Vladimir A. Katic, Alfred Rufer, “Power quality problems
compensation with universal power quality conditioning system.” IEEE Trans on Power
Delivery, Vol.22, No.2, pp.968-975, April 2007.
[12] Juan Manuel Carrasco, Leopoldo Garcia Franquelo, Jan. Bialasiewicz, “Power electronic
system for the grid integration of renewable energy sources: A survey.” IEEE Trans on
Industry Electronics, Vol.53, No.4, pp.1002-1010, Aug. 2006.
[13] “A report on Indian Wind Grid Code” – Committee draft, Version 1.0, pp 5-42 July 2009.
[14] J.F.Conroy, R. Watson, “Low-voltage ride though of full converter wind turbine with
permanent magnet generator”, Proc. IET Renew. Power Generation. Vol.2, No.2, pp.113-
122, 2008.
[15] Bousseau, P.: “Solution for the grid integration of wind farms – A survey”, Proc. of
European Wind Energy Conf., pp.12-16, Nov. 2004.
[16] S.W.Mohod, M.V.Aware, “A STATCOM-Control Scheme for Grid Connected Wind
Energy System for Power Quality Improvement”, IEEE System Journal, A special issue
on sustainable development, Vol.4, Issue-3, pp-346-352, Sept-2010.
36 An Update on Power Quality